Plan Review Details - Permit 15020685
Plan Review Stops For Permit 15020685
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-06-10 Cont ID  
Sent By jwitmer Date 2015-06-10 Time 16:48 Rev Time 0.00
Received By jwitmer Date 2015-06-10 Time 16:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-03-25 Cont ID  
Sent By jwitmer Date 2015-03-25 Time 10:17 Rev Time 0.00
Received By jwitmer Date 2015-03-25 Time   Sent To  
Notes
2015-03-25 10:24:58BUILDING PLAN REVIEW
 PERMIT: 15020685
 ADD: 901 45TH ST
 CONT: HEDRICK BROTHERS
 TEL: (561)242-4316
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MAY 11, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 2ND REVIEW
 DATE: WED. MARCH 25/2015
 ACTION: DENIED
  
 1) THIS PERMIT IS FOR THE TEMPORARY INSTALLATION OF A
 CONSTRUCTION MODULAR BUILDING FOR 6 MONTHS,
 (TEMPORARY). THE 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, 102.2 BUILDING. THE
 FOLLOWING BUILDINGS, STRUCTURES AND FACILITIES ARE
 EXEMPT FROM THE FLORIDA BUILDING CODE AS PROVIDED BY
 LAW, AND ANY FURTHER EXEMPTIONS SHALL BE AS DETERMINED
 BY THE LEGISLATURE AND PROVIDED BY LAW:
  
 (E) MOBILE OR MODULAR STRUCTURES USED AS TEMPORARY
 OFFICES, EXCEPT THAT THE PROVISIONS OF PART V (SECTION
 553.501-553.513, FLORIDA STATUTES) RELATING TO
 ACCESSIBILITY BY PERSONS WITH DISABILITIES, AND PERMITS
 SHALL BE REQUIRED FOR STRUCTURAL SUPPORT AND TIE DOWN,
 ELECTRICAL SUPPLY, AND ALL UTILITY CONNECTIONS TO SUCH
 MOBILE OR MODULAR STRUCTURES.
  
 2ND REQUEST. THE SITE PLAN SUBMITTED FROM GLIDDEN SPINA
 IS NOT SIGNED NOR SEALED (61G16.003 FL ADMINISTRATIVE
 CODE), THE SITE PLAN DOES NOT SHOW AN ACCESSIBLE
 PARKING SPACE, ACCESS AISLE NOR ACCESSIBLE ROUTE TO THE
 CONSTRUCTION OFFICE. THE PLANS WERE SUBMITTED FOR THE
 RAMP, STAIRS, LANDING, GAURDRAIL/ HANDRAIL SYSTEM( SEE
 ACC CODE, 405.1-10.) IS A SHRUNK VERSION OF PLANS. NOT
 TO THE SCALE AS INDICATED ON THE PLANS. PLEASE COMPLY
 WITH 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING
 PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM.
  
 2) COMPLIED.
 IN LEU OF SHUTTERING THE MANUFACTURED BUILDING BECAUSE
 OF BEING LOCATED IN A WIND BORN DEBRIS REGION IF
 HEDRICK BROTHER WILL PROVIDE A LETTER ON THEIR LETTER
 HEAD STATING IF THE MANUFACTURED BUILDING IS STILL IN
 USE AND A HURRICANE WARNING OCCURS FOR THIS AREA THEY
 WILL EITHER MOVE THE UNIT FROM THE SITE OR APPLY
 PLYWOOD STORM PANELS OVER THE GLAZED OPENINGS. 1609.1.2
 PROTECTION OF OPENINGS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-26 Cont ID  
Sent By jwitmer Date 2015-02-26 Time 15:02 Rev Time 0.00
Received By jwitmer Date 2015-02-26 Time 14:30 Sent To  
Notes
2015-02-26 15:02:13BUILDING PLAN REVIEW
 PERMIT: 15020685
 ADD: 901 45TH ST
 CONT: HEDRICK BROTHERS
 TEL: (561)242-4316
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MAY 11, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: THURS. FEB. 26/2015
 ACTION: DENIED
  
 1) THIS PERMIT IS FOR THE TEMPORARY INSTALLATION OF A
 CONSTRUCTION MODULAR BUILDING FOR 6 MONTHS,
 (TEMPORARY). THE 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, 102.2 BUILDING. THE
 FOLLOWING BUILDINGS, STRUCTURES AND FACILITIES ARE
 EXEMPT FROM THE FLORIDA BUILDING CODE AS PROVIDED BY
 LAW, AND ANY FURTHER EXEMPTIONS SHALL BE AS DETERMINED
 BY THE LEGISLATURE AND PROVIDED BY LAW:
  
 (E) MOBILE OR MODULAR STRUCTURES USED AS TEMPORARY
 OFFICES, EXCEPT THAT THE PROVISIONS OF PART V (SECTION
 553.501-553.513, FLORIDA STATUTES) RELATING TO
 ACCESSIBILITY BY PERSONS WITH DISABILITIES, AND PERMITS
 SHALL BE REQUIRED FOR STRUCTURAL SUPPORT AND TIE DOWN,
 ELECTRICAL SUPPLY, AND ALL UTILITY CONNECTIONS TO SUCH
 MOBILE OR MODULAR STRUCTURES.
  
 NO PLANS WERE SUBMITTED FOR THE ACCESSIBLE PARKING
 SPACE, ACCESS AISLE, ACCESSIBLE ROUTE TO THE OFFICE,
 RAMP, STAIRS, LANDING, GAURDRAIL/ HANDRAIL SYSTEM.
 SEE ACC CODE, 405.1-10.
  
 2) IN LEU OF SHUTTERING THE MANUFACTURED BUILDING
 BECAUSE OF BEING LOCATED IN A WIND BORN DEBRIS REGION
 IF HEDRICK BROTHER WILL PROVIDE A LETTER ON THEIR
 LETTER HEAD STATING IF THE MANUFACTURED BUILDING IS
 STILL IN USE AND A HURRICANE WARNING OCCURS FOR THIS
 AREA THEY WILL EITHER MOVE THE UNIT FROM THE SITE OR
 APPLY PLYWOOD STORM PANELS OVER THE GLAZED OPENINGS.
 1609.1.2 PROTECTION OF OPENINGS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-06-20 Cont ID  
Sent By dhayes Date 2015-06-20 Time 13:03 Rev Time 0.00
Received By dhayes Date 2015-06-20 Time 11:52 Sent To  
Notes
2015-06-20 12:06:31APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) ELECTRICAL PERMIT REQUIRED.
  
 2) THE SITE PLAN IS NOT SIIGNED OR SEALED. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN. FBC, WPB AMENDMENTS 107.2.1
 1A) 471.025 668.001-668.006.
 ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS, OR
 DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND BEING
 FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS
 PROVIDED TO THE OWNER OR THE OWNER?S REPRESENTATIVE
 SHALL BE SIGNED BY THE LICENSEE, DATED, AND SEALED WITH
 SAID SEAL.
  
 3) THE LOAD FROM THE ENGINEER INDICATES A 95.75 AMP
 LOAD ON A 100AMP SERVICE. THE ELECTRICAL CONTRACTOR
 ALSO SUBMITTED A LOAD CALCULATION INDICATING A 54.27AMP
 LOAD ON THE TRAILER AND ANOTHER 46.15AMP LOAD FOR THE
 JOBSITE TEMPORARY POWER PANEL. CLARIFICATION IS
 REQUIRED. PROVIDE A REVISED LOAD CALCULATION TO THE
 ELECTRICAL INSPECTOR IN THE FIELD SIGNED BY THE
 ENGINEER OF RECORD REVISING THE LOAD CALCULATION
 SUBMITTED PREVIOUSLY ON PG 2 OF 4.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-04-08 Cont ID  
Sent By dhayes Date 2015-04-08 Time 11:10 Rev Time 0.00
Received By dhayes Date 2015-04-08 Time 11:09 Sent To  
Notes
2015-04-08 11:09:47 
 1) PROVIDE A LOAD CALCULATION TO INDICATE TOTAL
 CONNECTED LOAD FOR THE SIZE OF THE MAIN SERVICE OCPD.
 AND THE OCPD FEEDING THE TRAILER.
 2) INDICATE THE LOCATION ON THE SITE FOR THE ELECTRICAL
 SERVICE EQUIPMENT IN RELATION TO THE CONSTRUCTION
 TRAILER. THE SITE PLAN INDICATES THE LOCATION OF AN
 "EXISTING TRANSFORMER". IS THIS A UTILITY TRANSFORMER
 WITH ADAQUATE CAPACITY?
 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FL SS 471,
 668.001-668.006
 FBC, WPB AMENDMENTS 107.2.1. THE SITE PLAN AND
 ELECTRICAL RISER DIAGRAM HAVE NOT BEEN SIGNED.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-03-16 Cont ID  
Sent By dhayes Date 2015-03-16 Time 16:56 Rev Time 0.00
Received By dhayes Date 2015-03-16 Time 16:51 Sent To  
Notes
2015-03-16 16:56:14PROVIDE AN ELECTRICAL SERVICE RISER DIAGRAM TO INDICATE
 THE SERVICE MAIN OCPD CONDUIT AND WIRE SIZES BETWEEN
 THE SERVICE ENTRANCE AND THE FEEDER FROM THE NEW
 TEMPORARY ELECTRICAL SERVICE TO THE CONSTRCTION
 TRAILER.
 PROVIDE A TOTAL CONNECTED LOAD FROM THE MANUFACTURER
 PRODUCT APPROVALS INDICATING THE REQUIRED SIZE OF THE
 MAIN SERVICE OCPD.
 INDICATE THE OCATION ON THE SITE FOR THE ELECTRICAL
 SERVICE EQUIPMENT IN RELATION TO THE CONSTRUCTION
 TRAILER.
 INDICATE APPROVED WIREIN METHODS AND MATERIALS FOR ALL
 OF THE ABOVE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-02-26 Cont ID  
Sent By pleduc Date 2015-02-26 Time   Rev Time 0.00
Received By pleduc Date 2015-02-26 Time 09:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2015-06-16 Time   Rev Time 0.00
Received By   Date 2015-05-18 Time   Sent To  
Notes
2015-05-19 09:32:115/18/2015 SENT TO B13.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-08 Cont ID  
Sent By dhayes Date 2015-04-08 Time 11:17 Rev Time 0.00
Received By dhayes Date 2015-03-19 Time 15:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-19 Cont ID  
Sent By skennedy Date 2015-03-19 Time 15:06 Rev Time 0.00
Received By skennedy Date 2015-02-19 Time 12:42 Sent To  
Notes
2015-02-24 12:42:33SENT TO B3 BIN FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-02-26 Cont ID  
Sent By jwitmer Date 2015-02-26 Time 14:30 Rev Time 0.00
Received By jwitmer Date 2015-02-26 Time 14:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-03-19 Cont ID  
Sent By skennedy Date 2015-03-19 Time 15:06 Rev Time 0.00
Received By skennedy Date 2015-03-19 Time 15:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-06-11 Cont ID  
Sent By tklarge Date 2015-06-11 Time 04:48 Rev Time 0.00
Received By tklarge Date 2015-06-11 Time 04:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-04-07 Cont ID  
Sent By tklarge Date 2015-04-07 Time 14:06 Rev Time 0.00
Received By tklarge Date 2015-04-07 Time 13:47 Sent To  
Notes
2015-04-07 14:06:521) THE SITE PLAN SHALL BE SIGNED & SEALED BY THE DESIGN
 PROFESSIONAL OF RECORD PER THE F.A.C. SEC. 61G1-16.003.
 2) THE SITE PLAN SHOWS A NOTE THAT SAYS "EXISTING
 BACKFLOW PREVENTER"AND AN ARROW POINTING TO NOWHERE.
 CLARIFY THE LOCATION OF THE DEVICE ON THE PLAN AND
 INDICATE HOW THE 3/4 WATER SERVICE IS CONNECTED TO THE
 EXISTING BUILDING. WHAT IS IT TYING INTO?
 3) THE WATER SERVICE TO THE TRAILER IS TO BE BURIED
 WITH A MIN. OF 12" OF COVER. I AM ASSUMING THIS WILL BE
 DONE BUT IT IS UNCLEAR ON THE DRAWING HOW THIS PIPING
 WILL BE INSTALLED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-03-07 Cont ID  
Sent By tklarge Date 2015-03-07 Time 04:54 Rev Time 0.00
Received By tklarge Date 2015-03-07 Time 04:06 Sent To  
Notes
2015-03-07 04:52:461) SUBMIT A SITE PLAN SHOWING THE CONNECTION AND
 LOCATION OF THE WATER & SEWER SYSTEM TO THE MODULAR
 BUILDING. THE MINIMUM SIZE WATER SERVICE TO THE
 STRUCTURE SHALL BE 3/4" PER 2010 FPC SEC.603.1.
 2) AN APPROVED BACKFLOW PREVENTER SHALL BE INSTALLED ON
 THE WATER SERVICE AT THE METER PER WPB CITY ORDINANCE
 SEC.90-33. A MINIMUM OF A REDUCED PRESSURE ZONE
 BACKFLOW PREVENTION ASSEMBLY PER THE CITY OF WPB CROSS
 CONNECTION MANUAL & 2010 FPC SEC.608.1.SUBMIT 2 COPIES
 OF THE MANUF. SPECIFICATIONS FOR THE BFP DEVICE.
 3) INDICATE ON THE PLAN IF THE BUILDING WILL BE
 CONNECTED TO A SANITARY SEWER OR A HOLDING TANK. IF TO
 A HOLDING TANK, SHOW THE SIZE AND LOCATION OF THE TANK.
 A PERMIT MAY BE REQUIRED FROM THE PALM BEACH COUNTY
 HEALTH DEPT.ALSO, IF TO A HOLDING TANK, SUBMIT A COPY
 OF THE PUMP OUT CONTRACT TO CONFIRM THE TSNK WILL BE
 MAINTAINED IN A SANITARY CONDITION. 2010 FPC SEC.311.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-05-21 Cont ID  
Sent By dkittred Date 2015-05-21 Time 16:34 Rev Time 0.00
Received By dkittred Date 2015-05-21 Time 16:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2015-03-23 Cont ID  
Sent By dkittred Date 2015-03-23 Time 11:11 Rev Time 0.00
Received By dkittred Date 2015-03-23 Time 11:09 Sent To  
Notes
2015-03-23 11:11:10PLANNING AND ZONING COMMENTS: ***FAILED***
  
 3/23/15
  
 COMMENTS MADE ON 3/3/15, AS LISTED BELOW, WERE NOT
 ADDRESSED:
  
 1. PROPOSED TEMPORARY CONSTRUCTION ACCESS OFF OF 54TH
 STREET APPEARS IT COULD HAVE SOME IMPACT TO EXISTING
 TREES. PLEASE VERIFY IF ANY TREES WILL NEED TO BE
 REMOVED AND THAT THE VEHICLE TRAFFIC WILL NOT IMPACT
 THE ROOT ZONE OF THE EXISTING TREES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2015-03-03 Cont ID  
Sent By dkittred Date 2015-03-03 Time 15:49 Rev Time 0.00
Received By dkittred Date 2015-03-03 Time 15:12 Sent To  
Notes
2015-03-03 15:49:06PLANNING AND ZONING COMMENTS: ***FAILED***
  
 3/3/15
  
 1. PROPOSED TEMPORARY CONSTRUCTION ACCESS OFF OF 54TH
 STREET APPEARS IT COULD HAVE SOME IMPACT TO EXISTING
 TREES. PLEASE VERIFY IF ANY TREES WILL NEED TO BE
 REMOVED AND THAT THE VEHICLE TRAFFIC WILL NOT IMPACT
 THE ROOT ZONE OF THE EXISTING TREES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  