2015-03-24 11:36:32 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| COMMENTS. |
| CODE: 2010 FBC. |
| |
| 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.) |
| FORR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED |
| PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE |
| UNIFIED LAND DEVELOPMENT CODE. |
| |
| 2- SHEET G-1: |
| A) REVISE LOAD SCHEDULE LIVE LOAD ON THE ROOFF BOTTOM |
| CHORD TO COMPLY WITH FOOTNOTES B AND G OF TABLE R301.5 |
| OF 2010 FBC-RESIDENTIAL. AND, COORDINATE INFORMATION |
| WITH THE DESIGN LOADS SHOWN ON SHEET S1.00. |
| |
| B) REVISE LOAD SCHEDULE INFORMATION. ACCORDING TO SEC. |
| R301.2.1.4 OF 2010 FBC-RESIDENTIAL THIS BUILDING IS |
| LOCATED IN EXPOSURE "C" NOT "B". REVISE AS REQUIRED. |
| |
| 3- PROVIDE DRAINAGE PLAN. SEC. R401.3 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR , MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AND THE DESIGN |
| PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| AMENDMENTS TO FBC. VALUATION WAS UPDATED TO $485,032. |
| THE PERMIT FEE BALANCE IS $8652.02. |
| |
| 5- SHEET A-1: |
| A) SPECIFY THE ATTIC ACCESS SIZE FOR THE ATTIC ACCESS |
| SHOWN IN MASTER BEDROOM CLOSET. SEC. 807 OF 2010 |
| FBC-RESIDENTIAL. |
| |
| B) PROVIDE SPECIFICATIONS FOR THE GARAGE DOOR LEADING |
| TO THE INTERIOR OF THE HOUSE TO SHOW COMPLIANCE WITH |
| SEC. R302.5.1 OF 2010 FBC-RESIDENTIAL. |
| |
| 6- TYPICAL WALL SECTION ON SHEET A-2: |
| A) DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS |
| REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| B) WALL SECTION CALLS FOR 2" CONT. SOFFIT VENTING, |
| WHILE GENERAL NOTES ON SAME DRAWINGS STATES "NUMBER OF |
| OF ROOF VENTS TO BE DETERMINED BY BUILDER". IT'S NOT |
| THE BUILDER RESPONSIBILITY TO DETERMINE THE NUMBER OF |
| VENTS. IT'S THE DESIGNER OF RECORD RESPONSIBILITY. |
| REVISE AS REQUIRED. SEC. R806 OF 2010 FBC-RESIDENTIAL. |
| |
| C) SPECIFY FOOTING MINIMUM DEPTH AS REQUIRED BY SEC. |
| R403.1.4 OF 2010 FBC-RESIDENTIAL. COORDINATE WITH |
| STRUCTURAL DRAWINGS. |
| |
| D) THE CEILING INSULATION R- VALUE IS NOT TO BE |
| VERIFIED BY THE BUILDER. IT'S THE DESIGNER OF RECORD |
| RESPONSIBILITY TO SPECIFY IT. ON THE OTHER HAND |
| COORDINATE WITH THE ENERGY CALCULATIONS. INFORMATION |
| DOESN'T'T MATCH. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| CONSERVATION. ARCHITECTURAL PLANS AND ENERGY |
| CALCULATIONS NEED TO BE COORDINATED. |
| |
| E) OVERHANG AT GARAGE WINDOWS DETAIL. PROVIDE COMPLETE |
| SPECIFICATIONS. SPECIFY ALL FRAMING MEMBERS AND |
| CONNECTORS. SEC. R301.1. PROVIDE COMPLETE |
| SPECIFICATIONS FOR THE LATH AND STUCCO SOFFIT SHOWING |
| COMPLIANCE WITH SEC. R703.1.3 OF 2010 FBC-RESIDENTIAL. |
| |
| F) FRONT ELEVATION: CLARIFY WHAT'S " CONCRETE FLAT TILE |
| W/ FLAT STUCCO SOFFIT, TYP." SEC. 107.2.1 CITY |
| AMENDMENTS TO FBC. |
| |
| 7- SHEET S1.00: |
| A) SPECIFY ALL LIVE AND DEAD LOADS. NOTE #7 OF |
| PREFABRICATED WOOD TRUSSES ONLY SPECIFY THE DEAD LOADS. |
| CLEARLY SPECIFY ALL LIVE AND DEAD LOADS, INCLUDING THE |
| ATTIC LIVE LOADS AS REQUIRED BY FOOT NOTES B AND G OF |
| TABLE R301.5 OF 2010 FBC-RESIDENTIAL. |
| |
| B) PROVIDE DOOR AND WINDOW STRUCTURAL BUCK DETAIL |
| SHOWING COMPLIANCE WITH SEC. R612.10.2.1 OF 2010 |
| FBC-RESIDENTIAL. (NOTE: DETAIL 2/S1.00 STATES "AS PER |
| DOOR MANUFACTURER PRODUCT APPROVAL". DESIGNER OF RECORD |
| NEED TO SPECIFY THE BUCK SIZE AND ATTACHMENT). |
| |
| 8- SOIL TEST REPORT: SOIL TEST REPORT SUBMITTED IS |
| MISSING INFORMATION. PROVIDE ALL ALL THE INFORMATION |
| REQUIRED BY SEC. 1803.6 OF 2010 FBC. |
| |
| 9- ENERGY CALCULATIONS: |
| A) REVISE INFORMATION ON CEILING TYPES ITEM #10. |
| INFORMATION DOESN''T MATCH FLOOR PLANS. COORDINATE AS |
| REQUIRED TO MATCH. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| CONSERVATION. |
| |
| B) REVISE DOOR INFORMATION ON PAGE 3 OF 6 TO-MATCH |
| FLOOR PLANS AND PRODUCT APPROVALS SUBMITTED. SEC. |
| 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. (CLEARLY |
| IDENTIFY ON-PLANS WHICH ARE THE INSULATED AND WOOD |
| DOORS). |
| |
| 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9N-3 FOR: |
| A) CONCRETE TILE UNDERLAYMENT FLORIDA PRODUCT APPROVAL |
| FL14317-R4 SUBMITTED: THE MAXIMUM DESIGN PRESSURES FOR |
| THIS UNDERLAYMENT IS -45PSF. SEE SEC. 5.5.2.1. THIS |
| UNDERLAYMENT DOESN'T MEET THE DESIGN PRESSURES REQUIRED |
| BY SEC. R301.1 OF 2010 FBC-RESIDENTIAL. PROVIDE PRODUCT |
| APPROVAL THAT MEETS THE DESIGN PRESSURES FO ALL ROOF |
| ZONES. |
| |
| B) CONCRETE ROOF TILE ADHESIVE IF SPECIFIED BY THE |
| DESIGNER OF RECORD. SEE ITEM #6(A) ABOVE. NOTE: SEE |
| ROOF TILE PRODUCT APPROVAL FOR LISTED ADHESIVES. |
| |
| C) BAHAMA SHUTTERS FLORIDA PRODUCT APPROVAL FL6566-R3: |
| PROVIDE LEGIBLE DRAWINGS. SEC. 107.2.1.4 CITY |
| AMENDMENTS TO FBC. LETTERING ON DRAWING SUBMITTED ARE |
| TOO SMALL AND ARE NOT LEGIBLE. PLEASE PROVIDE LARGER |
| PRINTS OR PRINT DRAWING IN A "LANDSCAPE" WAY. THAT WAY |
| DRAWINGS WILL BE LEGIBLE. |
| |
| D) 8'-0" WIDE OVERHEAD GARAGE DOORS AS SHOWN ON PLANS. |
| INFORMATION SUBMITTED IS FOR 16'-0" WIDE DOORS. |
| |
| E) FIXED WINDOW SIZES AS SHOWN ON PLANS IN THE MORNING |
| AREA. |
| |
| F) ENTRY DOOR AS SHOWN ON PLANS. |
| |
| G) CEMENTIOUS SOFFIT AS SPECIFIED ON PLANS. SEE SEC. |
| R616 OF 2020 FBC-RESIDENTIAL. |
| |
| H) PRECAST LINTELS AS SPECIFIED ON PLANS. (NOTE: |
| DESIGNER OF RECORD MAY LIST THE MIAMI-DADE NOA OR |
| FLORIDA PRODUCT APPROVAL NUMBER NEXT TO THE SPECIFIED |
| LINTEL). |
| |
| I) HUC410 CONNECTOR SHOWN ON THE TRUSS CONNECTOR |
| SCHEDULE AND ALL THE CONNECTORS SPECIFIED ON FRAMING |
| PLANS AND DETAILS THAT ARE NOT LISTED IN THE TRUSS |
| CONNECTOR SCHEDULE. (NOTE: DESIGNER OF RECORD MAY LIST |
| THE MIAMI-DADE NOA OR FLORIDA PRODUCT APPROVAL NUMBER |
| NEXT TO THE SPECIFIED CONNECTOR ON EACH DETAIL). |
| |
| 11- DESIGNER OF RECORD TO REVIEW AND APPROVE IN-WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 12- PROVIDE BAHAMA SHUTTERS COMPLETE INSTALLATION |
| SCHEDULE (INCLUDING THE FAUX SHUTTERS SHOWN ON FRONT |
| ELEVATION). SEE INSTALLATION SCHEDULE CITY SAMPLE OR |
| PROVIDE ALL THE REQUIRED INFORMATION IN ANY-OTHER |
| FORMAT. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 13- TRUSS PACKAGE: |
| A) COMPLETE TRUSS PACKAGE NEEDS TO BE REVIEWED AND |
| APPROVED BY THE DESIGN PROFESSIONAL OF RECORD PRIOR TO |
| SUBMITTAL. |
| |
| B) ALL ENGINEERED BEAMS AND TRUSS SHEETS NEED TO BE |
| SIGNED AND SEALED AS REQUIRED BY CHAPTER 471 FLORIDA |
| STATUTE. |
| |
| NOTE: AFTER ABOVE CORRECTIONS ARE DONE, THEN THE TRUSS |
| PACKAGE MAY BE SUBMITTED TO THE INSPECTOR AT TIME OF |
| FRAMING INSPECTION INSTEAD RE-SUBMITTING THE TRUSS |
| PACKAGE TO THIS OFFICE NOW. (FOR RESIDENTIAL PROJECTS |
| ONLY). |
| |
| ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO EXPEDITE THE REVIEW PROCESS AND AVOID |
| CONFLICTS OR DELAYS. |
| **** PLEASE REMOVE AND REPLACE ANY REVISE |
| DRAWING/PRODUCT APRPOVAL TO EXPEDITE THE REVIEW |
| PROCESS. |
| |