Plan Review Details - Permit 15020549
Plan Review Stops For Permit 15020549
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-08-06 Cont ID  
Sent By jgomez Date 2015-08-06 Time 12:51 Rev Time 0.00
Received By jgomez Date 2015-08-06 Time 12:50 Sent To  
Notes
2015-08-06 12:54:548/6/15
 RESPONSE TO STEVE KENNEDY FOR COMMENTS FROM MR. RAY
 PUZZITIELLO REGARDING THE PROVISO ITEMS:
  
 STEVE THIS ARE MY OBSERVATIONS ON THIS PROVISO:
 #1 IS OK.
 #2(A) IS OK.
 #2(B) ARCHITECT WILL PROVIDE INFORMATION.
 #3 (A) IS OK.
 #3 (B) A 2X4 DOOR BUCK DOESN'T PROVIDE FULL SUPPORT TO
 THE DOOR FRAME. THE DOOR FRAME IS WIDER THAN 3-1/2"
 ACTUAL SIZE OF 2X4 BUCK. I AM NOT SAYING THAT IT
 DOESN'T MEET THE PRODUCT APPROVAL REQUIREMENTS. I AM
 SAYING THAT IT NEEDS TO BE WIDER TO PROVIDE FUL SUPOORT
 TO THE DOOR FRAME AS REQUIRED BY SEC. R612.10.2.1
 #4(A) WIL BE SUBMITTED.
 #4(B) THERE ARE NOT INSULATED DOORS. SEE PLANS AND
 PRODUCT APPROVALS FOR TYPE OF DOORS. DOORS WITH GLAZING
 NEED TO BE INCLUDED IN THE GLAZING CALCULATIONS. PLANS
 DON'T SPECIFY GARAGE DOOR #2 TO BE INSULATED. PLANS AND
 ENERGY CALCUALTIONS TO MATCH.
 #4(C) WILL BE PROVIDED TO THE INSPECTOR.
 #5 (A) I DON'T SEE ANY FLORIDA PRODUCT APPROVAL
 FL15180.14 AS LISTED ON SHEET A4.
 #5 (B) I DON'T SEE ANY FLORIDA PRODUCT APPROVAL
 FL15180.16 AS LISTED ON SHEET A4.
 #6 IS OK
 #7 THIS IS THE ANSWER I GET ALL THE TIME " THE
 INSTALLATION IS IN THE PRODUCT APPROVAL". BUT, THIS
 DOESN'T TELL ME (AND THE INSPECTOR) IF THE PROPOSED
 INSTALLATION WILL WORK. WE HAVE A CITY POLICY AND CITY
 SAMPLE OF THE INSTALLATION SCHEDULE. AS FAR AS I KNOW
 WE ALWAYS ASK FOR THE INSTALLATION SCHEDULE.
 #8 IS OK.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-18 Cont ID  
Sent By jgomez Date 2015-06-18 Time 14:03 Rev Time 0.00
Received By jgomez Date 2015-06-18 Time 14:03 Sent To  
Notes
2015-06-18 14:03:576/18/15 TALKED TO DONNA FIEBIG. SHE AGREED TO PASS BLDG
 W/ PROVISO. FEES APPLY.
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE DRAINAGE PLAN. WATER CAN'T BE DIVERTED TO THE
 REAR PROPERTY.
 2- TYPICAL WALL SECTION: A) ROOF TILE FASTENING DOESN'T
 COMPLY W/ THE ROOF TILE MOMENT OF RESISTANCE (RAS 127).
 REVISE AS REQUIRED OR PROVIDE CALCULATIONS SHOWING
 COMPLIANCE. B) SPECIFY SPACING OF 4"X8" ROOF VENTS.
 3- SHEET S1.00: A) SPECIFY ALL LIVE LOADS, INCLUDING
 THE ATTIC LIVE LOADS. SEE FOOT NOTES B AND G OF TABLE
 R301.5. ONLY THE DEAD LOADS WERE SPECIFIED.
 B) DOOR STRUCTURAL BUCK DETAIL 2X4 DOESN'T PROVIDE FULL
 SUPPORT TO THE DOOR FRAMING. REVISE AS REQUIRED.
 4- ENERGY CALCULATIONS: A) PROVIDE ADDRESS OF JOB. B)
 REVISE DOOR INFORMATION ON PAGE 3 OF 6 TO-MATCH
 PLANS/PRODUCT APPROVALS. WHERE IS DOOR #2 ON PLANS?.
 C) COMPLETE THE COMPLIANCE CHECKLIST ON PAGE 6 OF 6.
 5- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: A) DOUBLE
 ENTRY DOOR SIZE AS SHOWN ON PLANS. B) CABANA STORAGE
 DOOR THAT MEETS THE CALCULATED DESIGN PRESSURES.
 6- ARCHITECT TO APPROVE ABOVE PRODUCT APPROVALS AND THE
 BAHAMAS SHUTTERS.
 7- PROVIDE BAHAMA SHUTTERS COMPLETE INSTALLATION
 SCHEDULE. REFERENCE PRODUCT APPROVAL SUBMITTED.
 8- PROVIDE COMPLETE SIGNED AND SEALED TRUSS PACKAGE AND
 ENGINEERED BEAMS AT TIME OF INSPECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-24 Cont ID  
Sent By jgomez Date 2015-03-24 Time 11:20 Rev Time 0.00
Received By jgomez Date 2015-03-24 Time 11:17 Sent To  
Notes
2015-03-24 11:36:32NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FORR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  
 2- SHEET G-1:
 A) REVISE LOAD SCHEDULE LIVE LOAD ON THE ROOFF BOTTOM
 CHORD TO COMPLY WITH FOOTNOTES B AND G OF TABLE R301.5
 OF 2010 FBC-RESIDENTIAL. AND, COORDINATE INFORMATION
 WITH THE DESIGN LOADS SHOWN ON SHEET S1.00.
  
 B) REVISE LOAD SCHEDULE INFORMATION. ACCORDING TO SEC.
 R301.2.1.4 OF 2010 FBC-RESIDENTIAL THIS BUILDING IS
 LOCATED IN EXPOSURE "C" NOT "B". REVISE AS REQUIRED.
  
 3- PROVIDE DRAINAGE PLAN. SEC. R401.3 OF 2010
 FBC-RESIDENTIAL.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR , MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND THE DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS TO FBC. VALUATION WAS UPDATED TO $485,032.
 THE PERMIT FEE BALANCE IS $8652.02.
  
 5- SHEET A-1:
 A) SPECIFY THE ATTIC ACCESS SIZE FOR THE ATTIC ACCESS
 SHOWN IN MASTER BEDROOM CLOSET. SEC. 807 OF 2010
 FBC-RESIDENTIAL.
  
 B) PROVIDE SPECIFICATIONS FOR THE GARAGE DOOR LEADING
 TO THE INTERIOR OF THE HOUSE TO SHOW COMPLIANCE WITH
 SEC. R302.5.1 OF 2010 FBC-RESIDENTIAL.
  
 6- TYPICAL WALL SECTION ON SHEET A-2:
 A) DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS.
  
 B) WALL SECTION CALLS FOR 2" CONT. SOFFIT VENTING,
 WHILE GENERAL NOTES ON SAME DRAWINGS STATES "NUMBER OF
 OF ROOF VENTS TO BE DETERMINED BY BUILDER". IT'S NOT
 THE BUILDER RESPONSIBILITY TO DETERMINE THE NUMBER OF
 VENTS. IT'S THE DESIGNER OF RECORD RESPONSIBILITY.
 REVISE AS REQUIRED. SEC. R806 OF 2010 FBC-RESIDENTIAL.
  
 C) SPECIFY FOOTING MINIMUM DEPTH AS REQUIRED BY SEC.
 R403.1.4 OF 2010 FBC-RESIDENTIAL. COORDINATE WITH
 STRUCTURAL DRAWINGS.
  
 D) THE CEILING INSULATION R- VALUE IS NOT TO BE
 VERIFIED BY THE BUILDER. IT'S THE DESIGNER OF RECORD
 RESPONSIBILITY TO SPECIFY IT. ON THE OTHER HAND
 COORDINATE WITH THE ENERGY CALCULATIONS. INFORMATION
 DOESN'T'T MATCH. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION. ARCHITECTURAL PLANS AND ENERGY
 CALCULATIONS NEED TO BE COORDINATED.
  
 E) OVERHANG AT GARAGE WINDOWS DETAIL. PROVIDE COMPLETE
 SPECIFICATIONS. SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. SEC. R301.1. PROVIDE COMPLETE
 SPECIFICATIONS FOR THE LATH AND STUCCO SOFFIT SHOWING
 COMPLIANCE WITH SEC. R703.1.3 OF 2010 FBC-RESIDENTIAL.
  
 F) FRONT ELEVATION: CLARIFY WHAT'S " CONCRETE FLAT TILE
 W/ FLAT STUCCO SOFFIT, TYP." SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 7- SHEET S1.00:
 A) SPECIFY ALL LIVE AND DEAD LOADS. NOTE #7 OF
 PREFABRICATED WOOD TRUSSES ONLY SPECIFY THE DEAD LOADS.
 CLEARLY SPECIFY ALL LIVE AND DEAD LOADS, INCLUDING THE
 ATTIC LIVE LOADS AS REQUIRED BY FOOT NOTES B AND G OF
 TABLE R301.5 OF 2010 FBC-RESIDENTIAL.
  
 B) PROVIDE DOOR AND WINDOW STRUCTURAL BUCK DETAIL
 SHOWING COMPLIANCE WITH SEC. R612.10.2.1 OF 2010
 FBC-RESIDENTIAL. (NOTE: DETAIL 2/S1.00 STATES "AS PER
 DOOR MANUFACTURER PRODUCT APPROVAL". DESIGNER OF RECORD
 NEED TO SPECIFY THE BUCK SIZE AND ATTACHMENT).
  
 8- SOIL TEST REPORT: SOIL TEST REPORT SUBMITTED IS
 MISSING INFORMATION. PROVIDE ALL ALL THE INFORMATION
 REQUIRED BY SEC. 1803.6 OF 2010 FBC.
  
 9- ENERGY CALCULATIONS:
 A) REVISE INFORMATION ON CEILING TYPES ITEM #10.
 INFORMATION DOESN''T MATCH FLOOR PLANS. COORDINATE AS
 REQUIRED TO MATCH. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 B) REVISE DOOR INFORMATION ON PAGE 3 OF 6 TO-MATCH
 FLOOR PLANS AND PRODUCT APPROVALS SUBMITTED. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION. (CLEARLY
 IDENTIFY ON-PLANS WHICH ARE THE INSULATED AND WOOD
 DOORS).
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) CONCRETE TILE UNDERLAYMENT FLORIDA PRODUCT APPROVAL
 FL14317-R4 SUBMITTED: THE MAXIMUM DESIGN PRESSURES FOR
 THIS UNDERLAYMENT IS -45PSF. SEE SEC. 5.5.2.1. THIS
 UNDERLAYMENT DOESN'T MEET THE DESIGN PRESSURES REQUIRED
 BY SEC. R301.1 OF 2010 FBC-RESIDENTIAL. PROVIDE PRODUCT
 APPROVAL THAT MEETS THE DESIGN PRESSURES FO ALL ROOF
 ZONES.
  
 B) CONCRETE ROOF TILE ADHESIVE IF SPECIFIED BY THE
 DESIGNER OF RECORD. SEE ITEM #6(A) ABOVE. NOTE: SEE
 ROOF TILE PRODUCT APPROVAL FOR LISTED ADHESIVES.
  
 C) BAHAMA SHUTTERS FLORIDA PRODUCT APPROVAL FL6566-R3:
 PROVIDE LEGIBLE DRAWINGS. SEC. 107.2.1.4 CITY
 AMENDMENTS TO FBC. LETTERING ON DRAWING SUBMITTED ARE
 TOO SMALL AND ARE NOT LEGIBLE. PLEASE PROVIDE LARGER
 PRINTS OR PRINT DRAWING IN A "LANDSCAPE" WAY. THAT WAY
 DRAWINGS WILL BE LEGIBLE.
  
 D) 8'-0" WIDE OVERHEAD GARAGE DOORS AS SHOWN ON PLANS.
 INFORMATION SUBMITTED IS FOR 16'-0" WIDE DOORS.
  
 E) FIXED WINDOW SIZES AS SHOWN ON PLANS IN THE MORNING
 AREA.
  
 F) ENTRY DOOR AS SHOWN ON PLANS.
  
 G) CEMENTIOUS SOFFIT AS SPECIFIED ON PLANS. SEE SEC.
 R616 OF 2020 FBC-RESIDENTIAL.
  
 H) PRECAST LINTELS AS SPECIFIED ON PLANS. (NOTE:
 DESIGNER OF RECORD MAY LIST THE MIAMI-DADE NOA OR
 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO THE SPECIFIED
 LINTEL).
  
 I) HUC410 CONNECTOR SHOWN ON THE TRUSS CONNECTOR
 SCHEDULE AND ALL THE CONNECTORS SPECIFIED ON FRAMING
 PLANS AND DETAILS THAT ARE NOT LISTED IN THE TRUSS
 CONNECTOR SCHEDULE. (NOTE: DESIGNER OF RECORD MAY LIST
 THE MIAMI-DADE NOA OR FLORIDA PRODUCT APPROVAL NUMBER
 NEXT TO THE SPECIFIED CONNECTOR ON EACH DETAIL).
  
 11- DESIGNER OF RECORD TO REVIEW AND APPROVE IN-WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 12- PROVIDE BAHAMA SHUTTERS COMPLETE INSTALLATION
 SCHEDULE (INCLUDING THE FAUX SHUTTERS SHOWN ON FRONT
 ELEVATION). SEE INSTALLATION SCHEDULE CITY SAMPLE OR
 PROVIDE ALL THE REQUIRED INFORMATION IN ANY-OTHER
 FORMAT. SEC. 107.2.1 CITY AMENDMENTS.
  
 13- TRUSS PACKAGE:
 A) COMPLETE TRUSS PACKAGE NEEDS TO BE REVIEWED AND
 APPROVED BY THE DESIGN PROFESSIONAL OF RECORD PRIOR TO
 SUBMITTAL.
  
 B) ALL ENGINEERED BEAMS AND TRUSS SHEETS NEED TO BE
 SIGNED AND SEALED AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTE.
  
 NOTE: AFTER ABOVE CORRECTIONS ARE DONE, THEN THE TRUSS
 PACKAGE MAY BE SUBMITTED TO THE INSPECTOR AT TIME OF
 FRAMING INSPECTION INSTEAD RE-SUBMITTING THE TRUSS
 PACKAGE TO THIS OFFICE NOW. (FOR RESIDENTIAL PROJECTS
 ONLY).
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS AND AVOID
 CONFLICTS OR DELAYS.
 **** PLEASE REMOVE AND REPLACE ANY REVISE
 DRAWING/PRODUCT APRPOVAL TO EXPEDITE THE REVIEW
 PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-06-25 Cont ID  
Sent By dhayes Date 2015-06-25 Time 15:33 Rev Time 0.00
Received By dhayes Date 2015-06-25 Time 15:33 Sent To  
Notes
2015-06-25 15:33:006/25/2015
 PROJECT: SPRINGDALE
 PERMIT#: 15020549
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: APPROVED WITH EXCEPTION. THE PLANS HAVE BEEN
 APPROVED PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION
 FEE(S).
  
 1) NEC 215.2 MINIMUM RATING AND SIZE.
 PROVIDE A LOAD CALCULATION IN ACCORDANCE WITH THE
 PROVISIONS OF THE THE NEC 220.16. 215.2 MINIMUM RATING
 AND SIZE AND REVISE THE RISER DIAGRAM AS NEEDED .
 (A) FEEDERS NOT MORE THAN 600 VOLTS. (1) GENERAL.
 FEEDER CONDUCTORS SHALL HAVE AN AMPACITY NOT LESS THAN
 REQUIRED TO SUPPLY THE LOAD AS CALCULATED IN PARTS III,
 IV, AND V OF ARTICLE 220.
  
 2) REVISE THE RISER DIAGRAM. THE CURRENT DESIGN IS
 INDICATING FEEDER CONDUCTORS UTILIZING A SERVICE
 DISCONNECT AS A RACEWAY.
 2A) REVISE THE GROUNDING ELECTRODE SYSTEM IN THE RISER
 DIAGRAM. THE CURRENT DESIGN INDICATES THE GROUNDING
 ELECTRODE CONDUTOR TERMINATING AT ONLY ONE OF THE TWO
 MAIN DISCONNECTS.
  
 3) NEC 110.33(B)
 PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO
 GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL
 EQUIPMENT INSTALLED IN THE ATTIC FOR THE AHU(S). NEC
 110.33(B)
  
 4) FBC-E 402.4.5 RECESSED LIGHTING.
 RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL
 ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED AND UNCONDITIONED SPACES. ALL RECESSED
 LUMINAIRES SHALL BE IC-RATED AND LABELED AS MEETING
 ASTM E 283 WHEN TESTED AT 1.57 PSF (75 PA) PRESSURE
 DIFFERENTIAL WITH NO MORE THAN 2.0 CFM (0.944 L/S) OF
 AIR MOVEMENT FROM THE CONDITIONED SPACE TO THE CEILING
 CAVITY. ALL RECESSED LUMINAIRES SHALL BE SEALED WITH A
 GASKET OR CAULK BETWEEN THE HOUSING AND THE INTERIOR
 WALL OR CEILING COVERING.
  
 5) FBC-E 404.1 LIGHTING EQUIPMENT.
 A MINIMUM OF 50 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICENCY
 LAMPS.
  
 6) NEC210.8
 CLARIFY ALL OUTLTS REQUIRING GFI PROTECTION. SEVERAL
 LOCATIONS NOT INDICATING PROPER GFI PROTECTION. GARAGE
 DOOR OUTLETS , KITCHEN COUNTER OUTLETS, BACK LANIA
 OUTLETS. SEE NEC210.8
  
 7) NEC 210.12, 406.11
 ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SWIMMING POOLS, GENERATORS. LOW
 VOLTAGE SYSTEMS, SECURITY, CABLE TV,, CCTV,
 AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-03-28 Cont ID  
Sent By dhayes Date 2015-03-28 Time 14:27 Rev Time 0.00
Received By dhayes Date 2015-03-28 Time 13:13 Sent To  
Notes
2015-03-28 14:27:023/28/2015
 PROJECT: SPRINGDALE
 PERMIT#: 15020549
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) NEC 215.2 MINIMUM RATING AND SIZE.
 PROVIDE A LOAD CALCULATION IN ACCORDANCE WITH THE
 PROVISIONS OF THE THE NEC 220.16. 215.2 MINIMUM RATING
 AND SIZE AND REVISE THE RISER DIAGRAM AS NEEDED .
 (A) FEEDERS NOT MORE THAN 600 VOLTS. (1) GENERAL.
 FEEDER CONDUCTORS SHALL HAVE AN AMPACITY NOT LESS THAN
 REQUIRED TO SUPPLY THE LOAD AS CALCULATED IN PARTS III,
 IV, AND V OF ARTICLE 220.
  
 2) NEC 440.11
 REVISE THE SYMBOL SHOWN FOR THE AHU 1 IN THE ATTIC
 SPACE IN THE GARAGE AND FOR THE CU UNIT(S) OUTSIDE. THE
 SYMBOL INDICATES A 240V RECEPTACLE OUTLET WHERE AN A/C
 UNITS REQUIRE DISCONNECTING MEANS CAPABLE OF
 DISCONNECTING THE UNITS FROM THE CIRCUIT CONDUCTORS.
 NEC 440.11
  
 3) NEC 110.33(B)
 PERMANENT LADDERS OR STAIRWAYS SHALL BE PROVIDED TO
 GIVE SAFE ACCESS TO THE WORKING SPACE AROUND ELECTRICAL
 EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, OR
 MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR SPACES.
 NEC 110.33(B)
  
 4) FBC-E 402.4.5 RECESSED LIGHTING.
 RECESSED LUMINAIRES INSTALLED IN THE BUILDING THERMAL
 ENVELOPE SHALL BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED AND UNCONDITIONED SPACES. ALL RECESSED
 LUMINAIRES SHALL BE IC-RATED AND LABELED AS MEETING
 ASTM E 283 WHEN TESTED AT 1.57 PSF (75 PA) PRESSURE
 DIFFERENTIAL WITH NO MORE THAN 2.0 CFM (0.944 L/S) OF
 AIR MOVEMENT FROM THE CONDITIONED SPACE TO THE CEILING
 CAVITY. ALL RECESSED LUMINAIRES SHALL BE SEALED WITH A
 GASKET OR CAULK BETWEEN THE HOUSING AND THE INTERIOR
 WALL OR CEILING COVERING.
  
 5) FBC-E 404.1 LIGHTING EQUIPMENT.
 A MINIMUM OF 50 PERCENT OF THE LAMPS IN PERMANENTLY
 INSTALLED LIGHTING FIXTURES SHALL BE HIGH-EFFICACY
 LAMPS.
  
 6) FBC-R 315.1 CARBON MONOXIDE PROTECTION.
 PROVIDE CARBON MONOXIDE DETECTOS WITHIN 10FT. OF
 SLEEPING AREAS.
  
 7) NEC210.8
 CLARIFY ALL OUTLTS REQUIRING GFI PROTECTION. SEVERAL
 LOCATIONS NOT INDICATING PROPER GFI PROTECTION. SEE
 NEC210.8
  
 8) NEC 210.12, 406.11
 ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SWIMMING POOLS, GENERATORS. LOW
 VOLTAGE SYSTEMS, SECURITY, CABLE TV,, CCTV,
 AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2015-06-11 Cont ID  
Sent By tklarge Date 2015-06-11 Time 04:30 Rev Time 0.00
Received By tklarge Date 2015-06-11 Time 04:30 Sent To  
Notes
2015-06-11 04:30:35NO GAS PLANS HAVE BEEN SUBMITTED WITH THIS SET OF
 PLANS. SEPARATE PERMIT REQUIRED FOR GAS.TKL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-25 Cont ID  
Sent By dhayes Date 2015-06-25 Time 15:33 Rev Time 0.00
Received By dhayes Date 2015-05-05 Time 11:38 Sent To  
Notes
2015-05-05 11:38:51RE-SUBMITTAL SENT TO R23 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-28 Cont ID  
Sent By dhayes Date 2015-03-28 Time 14:27 Rev Time 0.00
Received By dhayes Date 2015-02-17 Time 12:42 Sent To  
Notes
2015-02-18 12:42:40R30

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2015-06-18 Cont ID  
Sent By jgomez Date 2015-06-18 Time 14:24 Rev Time 0.00
Received By jgomez Date 2015-06-18 Time 14:24 Sent To  
Notes
2015-06-18 14:24:48MU-2015-010533 PAID. PAID RECEIPT E-MAILED BY MICHELE
 BONANNI FROM PBC.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-03-24 Cont ID  
Sent By jgomez Date 2015-03-24 Time 11:18 Rev Time 0.00
Received By jgomez Date 2015-03-24 Time 11:17 Sent To  
Notes
2015-03-24 11:20:361- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-06-19 Cont ID  
Sent By jgomez Date 2015-06-19 Time 07:16 Rev Time 0.00
Received By jgomez Date 2015-06-19 Time 07:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-03-27 Cont ID  
Sent By jgomez Date 2015-03-27 Time 13:33 Rev Time 0.00
Received By jgomez Date 2015-03-27 Time 07:26 Sent To  
Notes
2015-03-27 13:34:05NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS BASED
 ON THE BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION
 OF THE HOUSE AS REQUIRED BY SEC. 403.6 OF 2010
 FBC-ENERGY CONSERVATION. INFORMATION SUBMITTED IS ONLY
 A SUMMARY.
  
 2- ENERGY CALCULATIONS NEED TO BE REVISED BECAUSE IT
 DOESN'T MATCH INFORMATION SHOWN ON ARCHITECTURAL PLANS.
 FOR EXAMPLE ARCHITECT DIDN'T DESIGNED THE HOUSE WITH AN
 UNVENTED ATTIC. IT LOOKS LIKE EQUIPMENT SIZING
 CALCULATIONS WERE DONE BASED ON THE INFORMATION SHOWN
 ON THE ENERGY CALCULATIONS. INFORMATION ON THE
 EQUIPMENT SIZING CALCULATIONS NEED TO MATCH
 ARCHITECTURAL PLANS INCLUDING THE WALL FINISHES, ETC.
 THERE IS NOT SIDING FINISH ON WALLS. REVISE ALL THE
 INFORMATION AS REQUIRED TO MATCH ARCHITECTURAL PLANS.
 SEC. 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 3-PROVIDE MANUFACTURER SPECS FOR THE OUTDOOR KITCHEN
 HOOD AS REQUIRED D BY SEC. M1302.1 OF 2010
 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-06-11 Cont ID  
Sent By tklarge Date 2015-06-11 Time 04:29 Rev Time 0.00
Received By tklarge Date 2015-06-11 Time 04:12 Sent To  
Notes
2015-05-05 11:35:02NEW PLANS SUBMITTED. JG.

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-03-04 Cont ID  
Sent By tklarge Date 2015-03-04 Time 09:30 Rev Time 0.00
Received By tklarge Date 2015-03-04 Time 09:30 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2015-06-19 Cont ID  
Sent By jgomez Date 2015-06-19 Time 07:14 Rev Time 0.00
Received By jgomez Date 2015-06-19 Time 07:14 Sent To  
Notes
2015-06-19 07:16:291- BORAL SAXONY 900 CONCRETE TILE NOA 13-0723.05.
  
 2- BORAL TILESEAL UNDERLAYMENT NOA 12-1219.01

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2015-03-27 Cont ID  
Sent By jgomez Date 2015-03-27 Time 14:02 Rev Time 0.00
Received By jgomez Date 2015-03-26 Time 07:40 Sent To  
Notes
2015-03-27 14:09:06NEW SINGLE FAMILY RESIDENCE (R3) ROOFING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- DESIGNER OF RECORD TO SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SEC. 107.2.1.2 CITY AMENDMENTS.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES). DCA RULE 9N-3
 FOR:
  
 A) CONCRETE ROOF TILE ADHESIVE IF SPECIFIED BY THE
 DESIGNER OF RECORD. NOTE: SEE ROOF TILE PRODUCT
 APPROVAL FOR LISTED ADHESIVES.
  
 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN-WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712

Review Stop Z ZONING
Rev No 2 Status P Date 2015-05-08 Cont ID  
Sent By dkittred Date 2015-05-08 Time 14:39 Rev Time 0.00
Received By dkittred Date 2015-05-08 Time 12:52 Sent To  
Notes
2015-05-08 14:40:205/8/15 - LANDSCAPING PLANS SUBMITTED, BUT NEEDS
 SEPARATE PERMIT APPLICATION. CALLED CONTRACTOR TO
 SUBMIT APPLICATION. ZONING HOLDING LANDSCAPE PLANS. DK

Review Stop Z ZONING
Rev No 1 Status F Date 2015-02-26 Cont ID  
Sent By dkittred Date 2015-02-26 Time 17:08 Rev Time 0.00
Received By dkittred Date 2015-02-26 Time 15:29 Sent To  
Notes
2015-02-26 17:08:25PLANNING AND ZONING COMMENTS: ***FAILED***
  
 2/26/15
  
 1. THE 1/4" = 1' SCALE ON SHEET AS-1 IS NOT ACCURATE
 FOR THE PLAN. PLEASE CORRECT AND DIMENSION THE OVERHANG
 INTO THE FRONT SETBACK. ACCORDING TO ZLDR SEC.
 94-305(B)(2) - "STRUCTURAL OVERHANGS, INCLUDEING BUT
 NOT LIMTED TO BALCONIES, CORNICES, GUTTERS, EAVES, AND
 ROOF OVERHANG PROJECTIONS SHALL NOT EXTEND FARTHER THAN
 THREE FEET INTO ANY SETBACK."
  
 2. PRIOR TO ZONING APPROVAL OF THE PROPOSED
 CONSTRUCTION, A SEPARATE LANDSCAPE PERMIT IN
 CONFORMANCE WITH ARTICLE XIV SHALL BE SUBMITTED. (NOTE:
 ZLDR SEC. 94-442(B)(2)A. ? FOR SINGLE-FAMILY DWELLING
 UNITS, AT LEAST ONE SHADE, FLOWERING, OR FRUIT TREE
 SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF OPEN
 SPACE OR PORTION THEREOF. AND AT LEAST ONE SHRUB SHALL
 BE PLANTED FOR EACH 500 SQUARE FEET OF OPEN SPACE OR
 PORTION THEREOF. )
  
 GENERAL COMMENT:
  
 3. SEPARATE PERMIT IS REQUIRED FOR THE DRIVEWAY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2015-02-25 10:58:572/25/15