Plan Review Details - Permit 15020521
Plan Review Stops For Permit 15020521
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-04-03 Cont ID  
Sent By jwitmer Date 2015-04-03 Time 09:18 Rev Time 0.00
Received By jwitmer Date 2015-04-03 Time 08:10 Sent To  
Notes
2015-04-03 09:11:25BUILDING PROVISO:
 2010 FBC-B 1013.2 GUARD HEIGHT 42 INCHES HIGH
 2010 FBC-B 1013.3 EXC. # 4. IN AREAS THAT ARE NOT OPEN
 TO THE PUBLIC
 WITHIN OCCUPANCIES IN GROUP I-3, F, H OR S, AND FOR
 ALTERNATING TREAD
 DEVICES AND SHIP LADDERS, GUARDS SHALL NOT HAVE
 OPENINGS WHICH ALLOW
 PASSAGE OF A SPHERE 21 INCHES (533 MM) IN DIAMETER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-03 Cont ID  
Sent By jwitmer Date 2015-03-03 Time 09:13 Rev Time  
Received By jwitmer Date 2015-03-03 Time   Sent To FIRE
Notes
2015-03-03 09:13:44BUILDING PLAN REVIEW
 MASTER: 14040379
 PERMIT: 15020521
 ADD: 2101 OKEECHOBEE BLVD
 CONT: FLORES CONSTRUCTION
 TEL: (813) 323-7895
 E-MAIL:[email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: MARCH 03/ 2015
 ACTION: DENIED
  
 1) A LETTER FROM THE QUALIFIER OF BOTH THE PRIME/
 MASTER CONTRACTOR (HEDRICK BROTHERS) AND MEZZANINE
 CONTRACTOR MUST BE PROVIDED BEFORE THE MEZZINE PERMIT
 CAN BE ISSUED, IF THE MEZZANINE CONTRACTOR WISHES TO
 START WORK BEFORE THE SHELL / MASTER/ PRIME PERMIT WORK
 HAS RECEIVED A CERTIFICATE OFOCCUPANCY, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER.
 PLEASE PROVIDE THE PERMIT NUMBER, ADDRESS WITH SUITE
 NUMBER WITHIN THE DOCUMENT.
  
 2) THE SUBMITTED MEZININE PLANS WERE NOT REVIEWED BY
 THE DESIGNER OF RECORD. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC...
  
 3A) THE MEZZININE PLANS DO NOT SHOW ANY GUARD RAIL
 SYSTEM AROUND THE OPEN AREA AT THE PART DELIVERY AREA
 OR THE VLM. 2010 FBC-B 1013.1 WHERE REQUIRED.
 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING
 SURFACES, INCLUDING MEZZANINES, EQUIPMENT PLATFORMS,
 STAIRS, RAMPS AND LANDINGS THAT ARE LOCATED MORE THAN
 30 INCHES (762 MM) MEASURED VERTICALLY TO THE FLOOR.
  
 3B) SHOW COMPLIANCE WITH; 1013.3 OPENING LIMITATIONS.
 EXCEPTIONS: 4. IN AREAS THAT ARE NOT OPEN TO THE PUBLIC
 WITHIN OCCUPANCIES IN GROUP I-3, F, H OR S, AND FOR
 ALTERNATING TREAD DEVICES AND SHIP LADDERS, GUARDS
 SHALL NOT HAVE OPENINGS WHICH ALLOW PASSAGE OF A SPHERE
 21 INCHES (533 MM) IN DIAMETER.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-04-02 Cont ID  
Sent By scaldero Date 2015-04-02 Time 13:08 Rev Time 0.00
Received By scaldero Date 2015-04-02 Time 13:07 Sent To B
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-03-04 Cont ID  
Sent By scaldero Date 2015-03-04 Time 14:16 Rev Time 0.00
Received By scaldero Date 2015-03-04 Time 13:57 Sent To I
Notes
2015-03-04 14:24:29PERMIT # 15020521
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
 1) REVIEW AND COMPLY WITH ALL BUILDING PLANS REVIEWER
 COMMENTS
 2) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
 3) PROVIDE A LAYOUT PLAN THAT SHOWS THE MEZZANINE SIZE,
 IN RELATION TO THE OPEN AREA OF THIS ROOM TO VERIFY
 COMPLIANCE WITH NFPA 101: 8.6.10.2.1 : THE AGGREGATE
 AREA OF MEZZANINES LOCATED WITHIN A ROOM, OTHER THAN
 THOSE LOCATED IN SPECIAL-PURPOSE INDUSTRIAL
 OCCUPANCIES, SHALL NOT EXCEED ONE-THIRD THE OPEN AREA
 OF THE ROOM IN WHICH THE MEZZANINES ARE LOCATED.
  
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By shill Date 2015-03-19 Time 07:23 Sent To  
Notes
2015-03-20 07:23:21TO FIRE
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-04 Cont ID  
Sent By scaldero Date 2015-03-04 Time 14:24 Rev Time 0.00
Received By scaldero Date 2015-02-17 Time 14:09 Sent To  
Notes
2015-02-17 14:09:26TO JWITMER DESK