Plan Review Details - Permit 15020445
Plan Review Stops For Permit 15020445
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-03-18 Cont ID  
Sent By jwitmer Date 2015-03-18 Time 07:02 Rev Time 0.00
Received By jwitmer Date 2015-03-18 Time 06:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-19 Cont ID  
Sent By jwitmer Date 2015-02-19 Time 14:39 Rev Time 0.00
Received By jwitmer Date 2015-02-19 Time 12:00 Sent To  
Notes
2015-02-19 14:39:35BUILDING PLAN REVIEW
 PERMIT: 15020445
 ADD: 1501 NORTHPOINT PKWY # 103
 CONT: PHILIP E. JOHNSON
 TEL: (561)262-1795
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 2, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: THURS.FEB. 19/ 2015
 ACTION: DENIED
  
 1) SHEET 1.1 INDICATES A EXISITNG 2 STORY ATRIUM A
 BUSINESS OCCUPANCY. SHEET 2.1 NOW SHOWS A PROPOSED
 ASSEMBLY OCCUPANCY WITH A CASED OPENING BETWEEN THE 2
 OCCUPANCIES (STORAGE AS WELL AS BUSINESS OCCUPANCIES).
 PLEASE SHOW COMPLIANCE WITH 2010 FBC-B TABLE 508.4 1
 HOUR SEPARATION FOR SPRINKLERS, 2 HOURS FOR
 NON-SPRINKLERED BUILDING.
  
 2) PLEASE ALSO SEE ON SHEET A2.1 (2) ACCESSIBILITY
 ISSUES THAT ARE FOUND ON THE 2ND LEVEL AND NO VERTICAL
 ACCESSIBILITY, A BREAK ROOM AND A CONFERANCE ROOM, BOTH
 NOT SHOWN ON THE 1ST FLOOR.
  
 2A) 2010 FL ACC. CODE 206.2.3 MULTI-STORY BUILDINGS AND
 FACILITIES. AT LEAST ONE ACCESSIBLE ROUTE SHALL CONNECT
 EACH STORY AND MEZZANINE IN MULTI-STORY BUILDINGS AND
 FACILITIES. NOTWITHSTANDING THE REQUIREMENTS AND
 EXCEPTIONS OF THIS SECTION, SECTION 201.1.1 SHALL
 APPLY.
  
 2010 FL ACC. CODE 201.1.1 VERTICAL ACCESSIBILITY.
 SECTIONS 553.501-553.513, F.S., AND THE ADA STANDARDS
 FOR ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY
 BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE
 SECTIONS FROM THE DUTY TO PROVIDE VERTICAL
 ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE
 OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE
 STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH
 BUILDING, STRUCTURE OR FACILITY.
  
 2010 FL ACC. CODE 202.4.2 ACCESSIBLE FEATURES IN THE
 EVENT OF DISPROPORTIONALITY.WHEN THE COST OF
 ALTERATIONS NECESSARY TO MAKE THE PATH OF TRAVEL TO THE
 ALTERED AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO
 THE COST OF THE OVERALL ALTERATION, THE PATH OF TRAVEL
 SHALL BE MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE
 MADE ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE
 COSTS. IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE
 ROUTE TO THE ALTERED AREA; (III) AT LEAST ONE
 ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 2B) SHEET A2.1 INDICATES IN THE BREAK ROOM A NEW 2 BOWL
 SINK W/ GARBAGE DISPOSAL, PLANS FAIL TO PROVIDE
 COMPLIANCE WITH;
 2010 FL ACC. CODE 606.1-5.
  
 3) PLANS INDICATE IN THE WAREHOUSE AREA NEW DOCK
 LEVELERS BY OTHERS, IS THIS TO BE UNDER THIS PERMIT? OR
 IS THIS DELEGATED ENGINEERING UNDER THIS PERMIT?
 107.2.1.3 ADDITIONAL INFORMATION IS EQUIRED.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-16 Cont ID  
Sent By dhayes Date 2015-03-16 Time 11:55 Rev Time 0.00
Received By dhayes Date 2015-03-16 Time 11:55 Sent To  
Notes
2015-03-16 12:07:29VERIFY AND PROVIDE IF NEEDED ADAQUATE LIGHTING FOR PATH
 OF EGRESS, STAIRS AND LANDINGS. NEC 700.16

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-02-17 Cont ID  
Sent By rlecky Date 2015-02-17 Time 12:07 Rev Time 0.00
Received By rlecky Date 2015-02-17 Time 11:55 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-02-13 Cont ID  
Sent By pleduc Date 2015-02-13 Time   Rev Time 0.00
Received By pleduc Date 2015-02-13 Time 12:30 Sent To  
Notes
2015-02-13 13:09:38THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-18 Cont ID  
Sent By jwitmer Date 2015-03-18 Time 07:02 Rev Time 0.00
Received By jwitmer Date 2015-03-12 Time 10:36 Sent To  
Notes
2015-03-13 10:37:03C09
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-11 Cont ID  
Sent By hmoser Date 2015-03-11 Time 12:12 Rev Time 0.00
Received By hmoser Date 2015-02-12 Time 16:25 Sent To  
Notes
2015-02-12 16:27:24C9

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-03-11 Cont ID  
Sent By hmoser Date 2015-03-11 Time 12:12 Rev Time 0.00
Received By hmoser Date 2015-03-11 Time 10:56 Sent To  
Notes
***NONE***