Plan Review Details - Permit 15020329
Plan Review Stops For Permit 15020329
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-02-19 Cont ID  
Sent By rmcdouga Date 2015-02-19 Time 08:06 Rev Time 0.00
Received By rmcdouga Date 2015-02-19 Time 07:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-12 Cont ID  
Sent By rmcdouga Date 2015-02-12 Time 09:03 Rev Time 0.00
Received By rmcdouga Date 2015-02-12 Time 07:11 Sent To  
Notes
2015-02-12 09:03:30PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SPECIFY THE MEAN ROOF HEIGHT OF THE STRUCTURE. FBC
 107.2.1
  
 2) THE POLYGLASS MODIFIED BITUMEN SYSTEM W-9 THAT WAS
 SELECTED HAS A MAXIMUM DESIGN PRESSURE OF - 90.0 PSF.
 THE PROJECT IS LOCATED IN EXPOSURE CATEGORY C, THE
 UPLIFT PRESSURE IN THE CORNER AREAS WILL EXCEED - 90.0
 PSF. FBC R301.2.1
  
 3) SPECIFY THE SYSTEM AND THE MAXIMUM DESIGN PRESSURE
 FOR THE TILE ROOF UNDERLAYMENT THAT WILL BE USED. SEE
 PAGES 5 THROUGH 11 OF THE PRODUCT APPROVAL (FL529-R20)
 FBC R301.1
  
 4) SPECIFY THE TYPE AND PROFILE (LOW, MEDIUM OR HIGH)
 OF THE ENTEGRA ROOF TILE THAT WILL BE INSTALLED. FBC
 R301.1
  
 5) SPECIFY THE PADDY PLACEMENT AND ALLOWABLE
 OVERTURNING MOMENT FROM THE TABLE ON PAGE 3 OF PRODUCT
 APPROVAL FL6332-R4 FOR THE 3M AH-160 FOAM ROOF TILE
 ADHESIVE.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-12 Cont ID  
Sent By rmcdouga Date 2015-02-12 Time 09:03 Rev Time 0.00
Received By rmcdouga Date 2015-02-10 Time 14:04 Sent To B
Notes
2015-02-10 14:04:50TO R. MCDOUGALS'S DESK