Plan Review Details - Permit 15020265
Plan Review Stops For Permit 15020265 |
Review Stop |
ENG |
ENGINEERING CSD |
Rev No |
1 |
Status |
P |
Date |
2015-03-16 |
|
|
Cont ID |
|
Sent By |
Mgonzale |
Date |
2015-03-16 |
Time |
|
Rev Time |
1.00 |
Received By |
|
Date |
2015-03-16 |
Time |
|
Sent To |
FIRE |
|
Notes |
2015-03-16 12:35:24 | NO OBJECTION TO CONNECTION. | | | | PLEASE REVISE FIRE DEPARTMENT COMMENTS. | | | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2015-04-02 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2015-04-02 |
Time |
11:06 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2015-04-02 |
Time |
09:42 |
Sent To |
M |
|
Notes |
2015-04-02 11:06:42 | | | JOINT RESTRAINT: PER NFPA 13 & 24, SECTION 10.8.1.1, | | ALL TEES, PLUGS, CAPS, BENDS, REDUCERS, VALVES, AND | | HYDRANT BRANCHES SHALL BE RESTRAINED AGAINST MOVEMENT | | BY USING THRUST BLOCKS OR RESTRAINED JOINT SYSTEMS. | | | | CORROSION RESISTANCE: PER NFPA 13 & 24, SECTION | | 10.8.3.5, AFTER INSTALLATION, RODS, NUTS, BOLTS, | | WASHERS, CLAMPS, AND OTHER RESTRAINING DEVICES SHALL BE | | CLEANED AND THOROUGHLY COATED WITH A BITUMINOUS OR | | OTHER ACCEPTABLE CORROSION-RETARDING MATERIAL. | | | | ACCEPTANCE REQUIREMENTS: PER NFPA 13 & 24, SECTION | | 10.10.2.1.3, UNDERGROUND PIPING, FROM THE WATER SUPPLY | | TO THE SYSTEM RISER, AND LEAD-IN CONNECTIONS TO THE | | SYSTEM RISER SHALL BE COMPLETELY FLUSHED BEFORE | | CONNECTION IS MADE TO DOWNSTREAM FIRE PROTECTION SYSTEM | | PIPING. THE MINIMUM RATE OF FLOW SHALL BE NOT LESS THAN | | THE FLOW NECESSARY TO PROVIDE A VELOCITY OF 10 FEET PER | | SECOND. | | | | FLUSHING PAPERS: PER NFPA 13 & 24, SECTION 10.10.1, THE | | INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR THE | | COMPLETING AND SIGNING THE CONTRACTOR'S MATERIAL AND | | TEST CERTIFICATE(S) SHOWN IN FIGURE 10.10.1. | | | | HYDROSTATIC TESTING: PER NFPA 13 & 24, SECTION | | 10.10.2.2.1 ALL PIPING AND ATTACHED APPURTENANCES | | SUBJECTED TO SYSTEM WORKING PRESSURE SHALL BE | | HYDROSTATICALLY TESTED AT 200 PSI OR 50 PSI IN EXCESS | | OF THE SYSTEM WORKING PRESSURE, WHICHEVER IS GREATER, | | AND SHALL MAINTAIN THAT PRESSURE +/-5 PSI FOR 2 HOURS. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2015-02-24 |
|
|
Cont ID |
|
Sent By |
wjolin |
Date |
2015-02-24 |
Time |
13:23 |
Rev Time |
0.00 |
Received By |
wjolin |
Date |
2015-02-24 |
Time |
13:21 |
Sent To |
M |
|
Notes |
2015-02-24 13:23:43 | 705 NORTH OLIVE AVENUE | | PERMIT #15020265 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | SUBMITTED 20 DRAWINGS; HOWEVER, ONLY 2 SHEETS APPEAR TO | | BE RELEVANT. REMOVE SUPERFLUROUS SHEETS. | | | | GENERAL: SUBMIT PRODUCT DATA FOR UNDERGROUND PIPING, | | JOINT RESTRAINT ASSEMBLIES, ETC. | | | | JOINT RESTRAINT: PER NFPA 13 & 24, SECTION 10.8.1.1, | | ALL TEES, PLUGS, CAPS, BENDS, REDUCERS, VALVES, AND | | HYDRANT BRANCHES SHALL BE RESTRAINED AGAINST MOVEMENT | | BY USING THRUST BLOCKS OR RESTRAINED JOINT SYSTEMS. | | | | CORROSION RESISTANCE: PER NFPA 13 & 24, SECTION | | 10.8.3.5, AFTER INSTALLATION, RODS, NUTS, BOLTS, | | WASHERS, CLAMPS, AND OTHER RESTRAINING DEVICES SHALL BE | | CLEANED AND THOROUGHLY COATED WITH A BITUMINOUS OR | | OTHER ACCEPTABLE CORROSION-RETARDING MATERIAL. | | | | ACCEPTANCE REQUIREMENTS: PER NFPA 13 & 24, SECTION | | 10.10.2.1.3, UNDERGROUND PIPING, FROM THE WATER SUPPLY | | TO THE SYSTEM RISER, AND LEAD-IN CONNECTIONS TO THE | | SYSTEM RISER SHALL BE COMPLETELY FLUSHED BEFORE | | CONNECTION IS MADE TO DOWNSTREAM FIRE PROTECTION SYSTEM | | PIPING. THE MINIMUM RATE OF FLOW SHALL BE NOT LESS THAN | | THE FLOW NECESSARY TO PROVIDE A VELOCITY OF 10 FEET PER | | SECOND. | | | | FLUSHING PAPERS: PER NFPA 13 & 24, SECTION 10.10.1, THE | | INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR THE | | COMPLETING AND SIGNING THE CONTRACTOR'S MATERIAL AND | | TEST CERTIFICATE(S) SHOWN IN FIGURE 10.10.1. | | | | HYDROSTATIC TESTING: PER NFPA 13 & 24, SECTION | | 10.10.2.2.1 ALL PIPING AND ATTACHED APPURTENANCES | | SUBJECTED TO SYSTEM WORKING PRESSURE SHALL BE | | HYDROSTATICALLY TESTED AT 200 PSI OR 50 PSI IN EXCESS | | OF THE SYSTEM WORKING PRESSURE, WHICHEVER IS GREATER, | | AND SHALL MAINTAIN THAT PRESSURE +/-5 PSI FOR 2 HOURS. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 805-6730 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-04-06 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2015-04-06 |
Time |
13:43 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2015-03-17 |
Time |
11:34 |
Sent To |
|
|
Notes |
2015-03-18 11:34:19 | SENT TO FIRE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-03-16 |
|
|
Cont ID |
|
Sent By |
cpuell |
Date |
2015-03-16 |
Time |
15:24 |
Rev Time |
0.00 |
Received By |
cpuell |
Date |
2015-02-24 |
Time |
13:21 |
Sent To |
|
|
Notes |
2015-02-09 11:48:02 | ROUTED TO FIRE |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2015-04-06 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2015-04-06 |
Time |
13:42 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2015-04-06 |
Time |
13:42 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2015-03-06 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2015-03-06 |
Time |
10:03 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2015-03-06 |
Time |
08:33 |
Sent To |
ENG |
|
Notes |
2015-03-06 10:03:27 | PLAN DENIED | | APPLICATION IS FOR UNDER GROUND FIRE SPRINKLER | | SUBMIT THOSE PAGES ONLY. PER SECTION 107 FBC. | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 | | |
|
|
|