Plan Review Details - Permit 15020265
Plan Review Stops For Permit 15020265
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-03-16 Cont ID  
Sent By Mgonzale Date 2015-03-16 Time   Rev Time 1.00
Received By   Date 2015-03-16 Time   Sent To FIRE
Notes
2015-03-16 12:35:24NO OBJECTION TO CONNECTION.
  
 PLEASE REVISE FIRE DEPARTMENT COMMENTS.
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-04-02 Cont ID  
Sent By wjolin Date 2015-04-02 Time 11:06 Rev Time 0.00
Received By wjolin Date 2015-04-02 Time 09:42 Sent To M
Notes
2015-04-02 11:06:42 
 JOINT RESTRAINT: PER NFPA 13 & 24, SECTION 10.8.1.1,
 ALL TEES, PLUGS, CAPS, BENDS, REDUCERS, VALVES, AND
 HYDRANT BRANCHES SHALL BE RESTRAINED AGAINST MOVEMENT
 BY USING THRUST BLOCKS OR RESTRAINED JOINT SYSTEMS.
  
 CORROSION RESISTANCE: PER NFPA 13 & 24, SECTION
 10.8.3.5, AFTER INSTALLATION, RODS, NUTS, BOLTS,
 WASHERS, CLAMPS, AND OTHER RESTRAINING DEVICES SHALL BE
 CLEANED AND THOROUGHLY COATED WITH A BITUMINOUS OR
 OTHER ACCEPTABLE CORROSION-RETARDING MATERIAL.
  
 ACCEPTANCE REQUIREMENTS: PER NFPA 13 & 24, SECTION
 10.10.2.1.3, UNDERGROUND PIPING, FROM THE WATER SUPPLY
 TO THE SYSTEM RISER, AND LEAD-IN CONNECTIONS TO THE
 SYSTEM RISER SHALL BE COMPLETELY FLUSHED BEFORE
 CONNECTION IS MADE TO DOWNSTREAM FIRE PROTECTION SYSTEM
 PIPING. THE MINIMUM RATE OF FLOW SHALL BE NOT LESS THAN
 THE FLOW NECESSARY TO PROVIDE A VELOCITY OF 10 FEET PER
 SECOND.
  
 FLUSHING PAPERS: PER NFPA 13 & 24, SECTION 10.10.1, THE
 INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR THE
 COMPLETING AND SIGNING THE CONTRACTOR'S MATERIAL AND
 TEST CERTIFICATE(S) SHOWN IN FIGURE 10.10.1.
  
 HYDROSTATIC TESTING: PER NFPA 13 & 24, SECTION
 10.10.2.2.1 ALL PIPING AND ATTACHED APPURTENANCES
 SUBJECTED TO SYSTEM WORKING PRESSURE SHALL BE
 HYDROSTATICALLY TESTED AT 200 PSI OR 50 PSI IN EXCESS
 OF THE SYSTEM WORKING PRESSURE, WHICHEVER IS GREATER,
 AND SHALL MAINTAIN THAT PRESSURE +/-5 PSI FOR 2 HOURS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-02-24 Cont ID  
Sent By wjolin Date 2015-02-24 Time 13:23 Rev Time 0.00
Received By wjolin Date 2015-02-24 Time 13:21 Sent To M
Notes
2015-02-24 13:23:43705 NORTH OLIVE AVENUE
 PERMIT #15020265
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SUBMITTED 20 DRAWINGS; HOWEVER, ONLY 2 SHEETS APPEAR TO
 BE RELEVANT. REMOVE SUPERFLUROUS SHEETS.
  
 GENERAL: SUBMIT PRODUCT DATA FOR UNDERGROUND PIPING,
 JOINT RESTRAINT ASSEMBLIES, ETC.
  
 JOINT RESTRAINT: PER NFPA 13 & 24, SECTION 10.8.1.1,
 ALL TEES, PLUGS, CAPS, BENDS, REDUCERS, VALVES, AND
 HYDRANT BRANCHES SHALL BE RESTRAINED AGAINST MOVEMENT
 BY USING THRUST BLOCKS OR RESTRAINED JOINT SYSTEMS.
  
 CORROSION RESISTANCE: PER NFPA 13 & 24, SECTION
 10.8.3.5, AFTER INSTALLATION, RODS, NUTS, BOLTS,
 WASHERS, CLAMPS, AND OTHER RESTRAINING DEVICES SHALL BE
 CLEANED AND THOROUGHLY COATED WITH A BITUMINOUS OR
 OTHER ACCEPTABLE CORROSION-RETARDING MATERIAL.
  
 ACCEPTANCE REQUIREMENTS: PER NFPA 13 & 24, SECTION
 10.10.2.1.3, UNDERGROUND PIPING, FROM THE WATER SUPPLY
 TO THE SYSTEM RISER, AND LEAD-IN CONNECTIONS TO THE
 SYSTEM RISER SHALL BE COMPLETELY FLUSHED BEFORE
 CONNECTION IS MADE TO DOWNSTREAM FIRE PROTECTION SYSTEM
 PIPING. THE MINIMUM RATE OF FLOW SHALL BE NOT LESS THAN
 THE FLOW NECESSARY TO PROVIDE A VELOCITY OF 10 FEET PER
 SECOND.
  
 FLUSHING PAPERS: PER NFPA 13 & 24, SECTION 10.10.1, THE
 INSTALLING CONTRACTOR SHALL BE RESPONSIBLE FOR THE
 COMPLETING AND SIGNING THE CONTRACTOR'S MATERIAL AND
 TEST CERTIFICATE(S) SHOWN IN FIGURE 10.10.1.
  
 HYDROSTATIC TESTING: PER NFPA 13 & 24, SECTION
 10.10.2.2.1 ALL PIPING AND ATTACHED APPURTENANCES
 SUBJECTED TO SYSTEM WORKING PRESSURE SHALL BE
 HYDROSTATICALLY TESTED AT 200 PSI OR 50 PSI IN EXCESS
 OF THE SYSTEM WORKING PRESSURE, WHICHEVER IS GREATER,
 AND SHALL MAINTAIN THAT PRESSURE +/-5 PSI FOR 2 HOURS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-06 Cont ID  
Sent By hmoser Date 2015-04-06 Time 13:43 Rev Time 0.00
Received By hmoser Date 2015-03-17 Time 11:34 Sent To  
Notes
2015-03-18 11:34:19SENT TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-16 Cont ID  
Sent By cpuell Date 2015-03-16 Time 15:24 Rev Time 0.00
Received By cpuell Date 2015-02-24 Time 13:21 Sent To  
Notes
2015-02-09 11:48:02ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-04-06 Cont ID  
Sent By hmoser Date 2015-04-06 Time 13:42 Rev Time 0.00
Received By hmoser Date 2015-04-06 Time 13:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-03-06 Cont ID  
Sent By hmoser Date 2015-03-06 Time 10:03 Rev Time 0.00
Received By hmoser Date 2015-03-06 Time 08:33 Sent To ENG
Notes
2015-03-06 10:03:27PLAN DENIED
 APPLICATION IS FOR UNDER GROUND FIRE SPRINKLER
 SUBMIT THOSE PAGES ONLY. PER SECTION 107 FBC.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  