Plan Review Details - Permit 15020239
Plan Review Stops For Permit 15020239
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-03-04 Cont ID  
Sent By jwitmer Date 2015-03-04 Time 08:16 Rev Time 0.00
Received By jwitmer Date 2015-03-04 Time 08:16 Sent To  
Notes
2015-03-04 08:16:19WILL STAMP NEW PLANS WHEN SUBMITTED FOR ZONING. JW

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-13 Cont ID  
Sent By jwitmer Date 2015-03-13 Time 10:52 Rev Time 0.00
Received By dhayes Date 2015-03-13 Time 10:52 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-25 Cont ID  
Sent By misc2 Date 2015-02-20 Time 16:14 Rev Time 0.00
Received By dhayes Date 2015-02-20 Time 16:14 Sent To B
Notes
2015-02-26 07:39:282/25/2015
 PROJECT: LUX AUTO SPA SIGN
 PERMIT#: 15020239
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE ELECTRICAL PLANS AND PERMIT INDICATE
 COMPLIANCE WITH THE NEC ARTICLE 600 AND THE FBC CHAPTER
 5 SECTION 505.2.4. SEE BELOW:
  
 2) ELECTRIC SIGNS, SECTION SIGNS, AND OUTLINE LIGHTING
 ? FIXED, MOBILE, OR PORTABLE ? SHALL BE LISTED AND
 INSTALLED IN CONFORMANCE WITH THAT LISTING, UNLESS
 OTHERWISE APPROVED BY SPECIAL PERMISSION. 600.3
 LISTING.
  
 3) EACH SIGN AND OUTLINE LIGHTING SYSTEM, OR FEEDER
 CIRCUIT OR BRANCH CIRCUIT SUPPLYING A SIGN OR OUT-LINE
 LIGHTING SYSTEM, SHALL BE CONTROLLED BY AN EXTERNALLY
 OPERABLE SWITCH OR CIRCUIT BREAKER THAT WILL OPEN ALL
 UNGROUNDED CONDUCTORS WITHIN SIGHT OF THE SIGN NEC
 600.6(A)(1)
  
 4) ALL EXTERIOR LIGHTING NOT EXEMPTED BY FBC 505.1
 SHALL HAVE AUTOMATIC CONTROLS TO TURN OFF AT DAYLIGHT
 OR WHEN NOT REQUIRED. CONTROLS SHALL BE PHOTOSENSOR &
 TIME CLOCK OR ASTRONOMICAL TIME SWITCH. ALL TIME
 SWITCHES SHALL BE CAPABLE OF RETAINING PROGRAMING
 DURING A LOSS OF POWER FOR A MINIMUM OF 10 HOURS. FBC-E
 505.2.4
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jgomez Date 2015-03-04 Time 10:35 Sent To  
Notes
2015-03-09 10:36:08RE-SUBMITTAL SENT TO ZONING BIN FOR DANIELLE'S REVIEW.
 JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-04 Cont ID  
Sent By jwitmer Date 2015-03-04 Time 08:16 Rev Time 0.00
Received By jwitmer Date 2015-02-06 Time 11:31 Sent To  
Notes
2015-02-06 16:56:21ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status N Date 2015-03-09 Cont ID  
Sent By dkittred Date 2015-03-09 Time 17:10 Rev Time 0.00
Received By dkittred Date 2015-03-09 Time 17:08 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-02-12 Cont ID  
Sent By dkittred Date 2015-02-12 Time 07:58 Rev Time 0.00
Received By dkittred Date 2015-02-10 Time 11:31 Sent To E
Notes
2015-02-12 08:01:06PLANNING AND ZONING COMMENTS:
  
 2/12/15
  
 PASSED WITH PROVISO ON PLANS - "APPROVED PROVIDED THERE
 ARE NO ILLUMINATED FEATURES ON THE SIGN BASE/POLE."
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  