Plan Review Details - Permit 15020214
Plan Review Stops For Permit 15020214
Review Stop E ELECTRICAL
Rev No 1 Status N Date 2015-02-06 Cont ID  
Sent By skennedy Date 2015-02-06 Time 14:11 Rev Time 0.00
Received By skennedy Date 2015-02-06 Time 14:11 Sent To  
Notes
2015-02-06 14:13:281ST REVIEW: FBC 2010
  
 A SEPARATE APPLICATION WITH ELECTRICAL DETAILS IS
 REQUIRED FOR THE ELECTRICAL WORK.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2015-03-14 Cont ID  
Sent By tklarge Date 2015-03-14 Time 08:20 Rev Time 0.00
Received By tklarge Date 2015-03-14 Time 08:20 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2015-03-10 Cont ID  
Sent By tklarge Date 2015-03-10 Time 09:28 Rev Time 0.00
Received By tklarge Date 2015-03-10 Time 09:19 Sent To  
Notes
2015-03-10 09:27:481) THE TYPE OF PIPE TO BE USED FOR THE GAS LINE IS
 SHOWN AS 3/4" TYPE L COPPER. SECTION G2414.5.2 OF THE
 2010 FBCR PROHIBITS THE USE OF COPPER IF THE GAS
 CONTAINS MORE THAN AN AVERAGE OF 0.3 GRAINS OF HYDROGEN
 SULFIDE PER 100 STANDARD CUBIC FEET OF GAS.
 VERIFICATION FROM THE GAS PURVEYOR SHALL BE SUBMITTED
 AS TO THE AMOUNT OF HYDROGEN SULFIDE CONTAINED IN THE
 GAS PER 100 CU. FT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-02-07 Cont ID  
Sent By tklarge Date 2015-02-07 Time 09:51 Rev Time 0.00
Received By tklarge Date 2015-02-07 Time 09:08 Sent To  
Notes
2015-02-07 09:51:321) INDICATE THE TYPE OF PIPE BEING INSTALLED. 2010 FBCR
 SEC.G2414.1.
 2) SHOW THE PIPE SIZES FOR THE GAS AND THE WATER
 LINES.2010FBCR SEC.G2413.1
 3) INDICATE THE PSI OF THE GAS SYSTEM.2010FBCR
 SEC.G2413.6.
 4) INDICATE THE TYPE OF GAS ON THE PLAN. (LP OR
 NATURAL),
 5) SHOW THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM.2010 FBCR G2412.8, G2413.2,
 6) SHOW THE DISTANCE FROM THE POINT OF DELIVERY TO THE
 MOST REMOTE OUTLET IN THE STRUCTURE. 2010 FBCR
 SEC.G2413.4.1.
 7) THERE IS A NOTE ON THE PLAN WITH AN ARROW POINTING
 TO THE HEATER WHICH IS ILLEGIBLE. CLARIFY.
 8) SHOW THE REQUIRED SHUTOFF VALVE ON THE GAS LINE.
 2010 FBCR SEC.G2420.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-03-14 Cont ID  
Sent By tklarge Date 2015-03-14 Time 08:20 Rev Time 0.00
Received By tklarge Date 2015-03-12 Time 14:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-10 Cont ID  
Sent By tklarge Date 2015-03-10 Time 09:28 Rev Time 0.00
Received By tklarge Date 2015-02-25 Time 08:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-07 Cont ID  
Sent By tklarge Date 2015-02-07 Time 09:53 Rev Time 0.00
Received By tklarge Date 2015-02-06 Time 13:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-02-07 Cont ID  
Sent By tklarge Date 2015-02-07 Time 09:53 Rev Time 0.00
Received By tklarge Date 2015-02-07 Time 09:52 Sent To  
Notes
***NONE***