Plan Review Details - Permit 15020200
Plan Review Stops For Permit 15020200
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-02-18 Cont ID  
Sent By skennedy Date 2015-02-18 Time 09:53 Rev Time 0.00
Received By skennedy Date 2015-02-18 Time 09:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-10 Cont ID  
Sent By dhayes Date 2015-02-10 Time 08:41 Rev Time 0.00
Received By dhayes Date 2015-02-10 Time 08:40 Sent To  
Notes
2015-02-10 08:42:41SEE PLUMBING COMMENTS.
 TWO COPIES OF MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION DATA SHEETS FOR THE PURA SPRAY BOOTH. WPB
 AMENDMENTS TO FBC 107.2.1.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-18 Cont ID  
Sent By tklarge Date 2015-02-18 Time 09:58 Rev Time 0.00
Received By tklarge Date 2015-02-17 Time 09:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-10 Cont ID  
Sent By hmoser Date 2015-02-10 Time 13:38 Rev Time  
Received By hmoser Date 2015-02-06 Time   Sent To  
Notes
2015-02-07 07:25:09INCOMING SENT TO T. LARGES' DESK.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-02-10 Cont ID  
Sent By hmoser Date 2015-02-10 Time 13:38 Rev Time 0.00
Received By hmoser Date 2015-02-10 Time 13:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-02-18 Cont ID  
Sent By tklarge Date 2015-02-18 Time 09:58 Rev Time 0.00
Received By tklarge Date 2015-02-18 Time 09:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-02-09 Cont ID  
Sent By tklarge Date 2015-02-09 Time 06:51 Rev Time 0.00
Received By tklarge Date 2015-02-09 Time 05:18 Sent To  
Notes
2015-02-09 06:51:351) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION INSTRUCTIONS FOR THE
 PURA SPRAY TAN BOOTHS. WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 2) INDICATE THE TYPE OF EFFLUENT THAT WILL BE
 DISCHARGED TO THE SANITARY SYSTEM. WPB AMEND. TO 2010
 FBC SEC.107.2.1.
 3) RESEARCH ON THIS BOOTH SHOWS THE USE OF A FOUR PART
 SOLUTION. SUBMIT SPECIFICATIONS / MSDS FOR THE
 SOLUTIONS THAT WILL BE USED IN THE SPRAY TANNING
 PROCESS THE WATER SUPPLY TO THESE BOOTHS SHALL BE
 PROTECTED WITH A BACKFLOW PREVENTION DEVICE. 2010 FPC
 SEC.608.1.
 4) SUBMIT 2 COPIES OF MANUF. SPECIFICATION SHEETS FOR
 THE LINT TRAP.WPB AMEND. TO 2010 FBC SEC.107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  