Plan Review Details - Permit 15020170
Plan Review Stops For Permit 15020170
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-04-01 Cont ID  
Sent By shill Date 2015-04-01 Time 17:07 Rev Time 0.00
Received By shill Date 2015-04-01 Time 17:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-03-31 Cont ID  
Sent By shill Date 2015-03-31 Time 18:13 Rev Time 0.00
Received By shill Date 2015-03-31 Time 18:13 Sent To  
Notes
2015-03-31 18:13:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
  
 4. EITHER HIGHLIGHT THE DETAILS FOR LEXAN IN THE ROOF
 AND WALLS IN THE AAF DOCUMENTS OR PROVIDE ENGINEERING
 FOR THIS DESIGN, FBC 2010 RESIDENTIAL 301.
  
 A SPEC SHEET FOR A LEXAN PANEL HAS BEEN PROVIDED. THE
 SCREEN ENCLOSURE DETAILS PROVIDED ARE FOR INSTALLATION
 OF SCREEN IN ALUMINUM FRAME. PROVIDE THE DETAIL IN THE
 AAF GUIDE (OR ENGINEERING) WHICH ADDRESSES INSTALLATION
 OF LEXAN PANELS IN THE ROOF AND THE WALLS.
  
 AAF GUIDE DOES NOT APPEAR TO ADDRESS INSTALLATION OF
 LEXAN PANELS IN LIEU OF SCREEN MATERIAL. PROVIDE
 ENGINEERING FOR PROPOSED INSTALLATION.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-03-25 Cont ID  
Sent By shill Date 2015-03-25 Time 07:45 Rev Time 0.00
Received By shill Date 2015-03-25 Time 07:45 Sent To  
Notes
2015-03-25 07:51:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. NA - PER CONTRACTOR, NO PLUMBING OR ELECTRICAL WORK
 TO BE DONE
  
 2-3. OK
  
 4. EITHER HIGHLIGHT THE DETAILS FOR LEXAN IN THE ROOF
 AND WALLS IN THE AAF DOCUMENTS OR PROVIDE ENGINEERING
 FOR THIS DESIGN, FBC 2010 RESIDENTIAL 301.
  
 A SPEC SHEET FOR A LEXAN PANEL HAS BEEN PROVIDED. THE
 SCREEN ENCLOSURE DETAILS PROVIDED ARE FOR INSTALLATION
 OF SCREEN IN ALUMINUM FRAME. PROVIDE THE DETAIL IN THE
 AAF GUIDE (OR ENGINEERING) WHICH ADDRESSES INSTALLATION
 OF LEXAN PANELS IN THE ROOF AND THE WALLS.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-07 Cont ID  
Sent By shill Date 2015-03-07 Time 17:16 Rev Time 0.00
Received By shill Date 2015-03-07 Time 17:16 Sent To P
Notes
2015-03-07 17:23:54****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. REVISE PLANS TO INCLUDE ALL WORK IN CONTRACT WITH
 THE EXCEPTION OF THE PATIO DOORS WHICH HAVE ALREADY
 BEEN PERMITTED.
  
 2. PROVIDE A FLOOR PLAN WITH ROOM DESIGNATIONS WHICH
 SHOW TYPES OF ROOMS AFFECTED BY THE PROPOSED SCREEN
 ENCLOSURE.
  
 3. PROVIDE A STRUCTURAL DETAIL FOR THE "NEW CBS WALL".
 IF THE DETAIL IS NOT PREPARED BY A DESIGN PROFESSIONAL,
 INCLUDE CALCULATIONS FOR FOOTING, BEAM, AND VERTICAL
 REINFORCEMENT, FBC 2010 RESIDENTIAL 301.
  
 4. EITHER HIGHLIGHT THE DETAILS FOR LEXAN IN THE ROOF
 AND WALLS IN THE AAF DOCUMENTS OR PROVIDE ENGINEERING
 FOR THIS DESIGN, FBC 2010 RESIDENTIAL 301.
  
 5. VALUE HAS BEEN ADJUSTED FOR THIS PERMIT AND FOR
 15020667.
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2015-03-25 Cont ID  
Sent By shill Date 2015-03-25 Time 07:51 Rev Time 0.00
Received By shill Date 2015-03-25 Time 07:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-03-09 Cont ID  
Sent By   Date 2015-03-09 Time 09:00 Rev Time 0.00
Received By dhayes Date 2015-03-09 Time 09:00 Sent To  
Notes
2015-03-09 09:03:481) PROVIDE AN APPLICATION SIGNED BY A LICENSED
 ELECTRICAL CONTRACTOR FOR THE RELOCATION OF THE
 ELECTRICAL WORK DESCRIBED IN THE ATTACHED CONTRACT. WPB
 AMEND. TO 2010 FBC SEC. 105.1.
 2) SUBMIT A PLAN SHOWING THE EXISTING LOCATION OF THE
 PROPOSED ELECTRICAL WORK DESCRIBED IN THE ATTACHED
 CONTRACT. WPB AMEND. TO 2010 FBC SEC.107.2.1.
  
 DAVID HAYES,
 ELECTRICAL PLANS EXAMINER, PX3421
 CITY OF WEST PALM BEACH, FL 33401
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-25 Cont ID  
Sent By shill Date 2015-03-25 Time 07:51 Rev Time 0.00
Received By shill Date 2015-03-25 Time 07:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-09 Cont ID  
Sent By dhayes Date 2015-03-09 Time 09:04 Rev Time 0.00
Received By dhayes Date 2015-03-07 Time 17:24 Sent To  
Notes
2015-03-07 17:24:203/7 TO TL DESK
  
2015-02-05 13:36:21ROUTED TO ZONING
  

Review Stop P PLUMBING
Rev No 2 Status N Date 2015-03-25 Cont ID  
Sent By shill Date 2015-03-25 Time 07:51 Rev Time 0.00
Received By shill Date 2015-03-25 Time 07:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-03-09 Cont ID  
Sent By tklarge Date 2015-03-09 Time 07:34 Rev Time 0.00
Received By tklarge Date 2015-03-09 Time 07:34 Sent To  
Notes
2015-03-09 07:34:051) PROVIDE AN APPLICATION SIGNED BY A LICENSED PLUMBING
 CONTRACTOR FOR THE RELOCATION OF THE SHOWER VALVE AND
 HEAD.WPB AMEND. TO 2010 FBC SEC. 105.1.
 2) SUBMIT A PLAN SHOWING THE EXISTING LOCATION OF THE
 SHOWER HEAD AND VALVE AND THE PROPOSED LOCATION.WPB
 AMEND. TO 2010 FBC SEC.107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-02-06 Cont ID  
Sent By sgraham Date 2015-02-06 Time 10:23 Rev Time 0.00
Received By sgraham Date 2015-02-06 Time 10:23 Sent To B
Notes
***NONE***