Plan Review Details - Permit 15020124
Plan Review Stops For Permit 15020124
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-03-21 Cont ID  
Sent By shill Date 2015-03-21 Time 11:19 Rev Time 0.00
Received By shill Date 2015-03-21 Time 11:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-03-10 Cont ID  
Sent By shill Date 2015-03-10 Time 15:20 Rev Time 0.00
Received By shill Date 2015-03-10 Time 15:18 Sent To  
Notes
2015-03-10 15:20:42****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. A SOLID RATHER THAN VENTED PRODUCT IS NOW PROPOSED.
  
 REVISE PLAN TO SHOW ATTIC VENTING REQUIRED BY FBC 2010
 RESIDENTIAL 806.1.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-02-24 Cont ID  
Sent By shill Date 2015-02-24 Time 15:38 Rev Time 0.00
Received By shill Date 2015-02-24 Time 15:38 Sent To  
Notes
2015-02-24 15:45:33****CORRECTIONS****
 ****REVISED 2/26 AND EMAILED APPLICANT****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE SOFFIT OPTION SELECTED HAS A DP LIMITATION OF +?
 / -64.4 PSF. FOR 10SF (AREA TRIBUTARY TO A FASTENER),
 20' MRH, EXPOSURE D, DESIGN PRESSURES REQUIRED ARE
 +48.5/-52.6 FOR ZONE 4, AND +48.5/-65PSF FOR ZONE 5.
 CONTRACTOR HAS SELECTED A SYSTEM WHICH DOES NOT HAVE A
 POSITIVE DESIGN PRESSURE LIMITATION (PLEASE CONTACT
 MANUFACTURER OR INDICATE WHERE IN THE PRODUCT APPROVAL
 THIS IS ADDRESSED) AND DOES NOT MEET THE NEGATIVE
 PRESSURE FOR ZONE 5.
  
 OBTAINING THE EXACT MRH AND/OR OBTAINING ENGINEERING
 MAY RESULT IN LOWER PRESSURES.
  
 FBC 2010 RESIDENTIAL 301
  
 **PLEASE ADVISE VIA EMAIL WHEN THIS IS RESUBMITTED -
 REVIEW WILL BE DONE TIMELY**
  
 ***2/26 - NEGATIVE DP FOR MRH20', ZONE5, 169MPH IS
 -64.75PSF (DOES NOT MEET REQUIREMENT OF -64.4; PLEASE
 VERIFY MRH OR OBTAIN ENGINEERING)***
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-04 Cont ID  
Sent By shill Date 2015-02-04 Time 17:54 Rev Time 0.00
Received By shill Date 2015-02-04 Time 17:54 Sent To  
Notes
2015-02-04 17:58:48****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THE SOFFIT OPTION SELECTED HAS A DP LIMITATION OF
 +80 / -42.2PSF. IT APPEARS THAT THIS IS EXPOSURE D, AND
 MEAN ROOF HEIGHT NOT PROVIDED (MRH IS THE AVERAGE OF
 ROOF PEAK AND EAVE). PLEASE PROVIDE SO THAT DESIGN
 PRESSURES CAN BE DETERMINED.
  
 FOR 10SF (AREA TRIBUTARY TO A FASTENER), 20' MRH,
 EXPOSURE D, DESIGN PRESSURES REQUIRED ARE +48.5/-52.6
 FOR ZONE 4, AND +48.5/-65PSF FOR ZONE 5. PLEASE
 ADDRESS.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-03-21 Cont ID  
Sent By shill Date 2015-03-21 Time 11:19 Rev Time 0.00
Received By shill Date 2015-03-18 Time 18:55 Sent To  
Notes
2015-03-20 18:55:39SENT TO SAMANTHA HILL FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-10 Cont ID  
Sent By shill Date 2015-03-10 Time 15:20 Rev Time 0.00
Received By shill Date 2015-03-04 Time 15:23 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-04 Cont ID  
Sent By shill Date 2015-02-04 Time 17:54 Rev Time 0.00
Received By shill Date 2015-02-04 Time 17:54 Sent To  
Notes
***NONE***