Plan Review Stops For Permit 15020119 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2015-07-14 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-07-14 |
Time |
12:30 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-07-14 |
Time |
12:30 |
Sent To |
E |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2015-05-11 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-05-11 |
Time |
13:22 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-05-11 |
Time |
13:17 |
Sent To |
|
|
Notes |
2015-05-11 13:25:05 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FROM PREVIOUS LIST: | | | | 1. PROVIDE A STRUCTURAL DETAIL FOR THE EXISTING SLAB, | | ANCHORING FOR PROPOSED FUEL TANK AND GENERATOR. SLAB TO | | RESIST DEAD LOADS, TANK AND GENERATOR TO RESIST SLIDING | | AND OVERTURNING CAUSED BY WIND LOADS, FBC 1609. | | | | 2ND REVIEW, PLAN STATES THAT THE ENCLOSURE IS TO COMPLY | | WITH 170MPH EXPOSURE D. | | | | THE GENERATOR IS TO ALSO RESIST WIND LOADS. ANCHORING | | PER THE PLAN IS "PER MANUFACTURER'S INSTRUCTIONS." THIS | | WAS NOT PROVIDED. THE ANCHORING FOR THE GENERATOR IS TO | | BE VERIFIED BY A FLORIDA PE THAT THE ANCHORING METHOD | | PER MANUFACTURER MEETS THE 170MPH EXPOSURE C MINIMUM | | REQUIREMENT. SINCE THE MANUFACTURER'S INSTRUCTIONS HAVE | | NOT BEEN PROVIDED, IT CANNOT BE DETERMINED AT THIS TIME | | WHETHER OR NOT THE MANUFACTURER'S SPECIFICATION IS | | VERIFIED BY A FLORIDA PE. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2015-03-06 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-03-06 |
Time |
17:19 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-03-06 |
Time |
17:19 |
Sent To |
|
|
Notes |
2015-03-06 17:22:06 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. PROVIDE A STRUCTURAL DETAIL FOR THE EXISTING SLAB, | | ANCHORING FOR PROPOSED FUEL TANK AND GENERATOR. SLAB TO | | RESIST DEAD LOADS, TANK AND GENERATOR TO RESIST SLIDING | | AND OVERTURNING CAUSED BY WIND LOADS, FBC 1609. | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2015-07-21 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-07-21 |
Time |
15:00 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-07-21 |
Time |
15:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
N |
Date |
2015-07-16 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-07-16 |
Time |
13:23 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2015-07-16 13:23:22 | NO NEW ELECTRICAL INFORMATION SUBMITTED WITH THIS NEW | | RESUBMITTAL FORM DATED JULY 9, 2015. I SPOEKE TO | | CHARLIE OF MALONE ELECTRIC AND TOLD HIM I HAVE BEEN | | WAITING FOR THE MANUFACTURER EQUIPMENT SUBMITTALS. HE | | WILL PASS THAT INFORMATION TO RAY MURDOCK AND THEY WILL | | BRING THE INFORMATION ONCE ACQUIRED. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2015-05-01 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-05-01 |
Time |
16:29 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-05-01 |
Time |
16:24 |
Sent To |
B |
|
Notes |
2015-05-01 16:33:17 | 5/01/2015 | | PROJECT: FL DEPT OF HEALTH | | PERMIT#: 15020119 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 2ND ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) PROVIDE MANUFACTURER DATA SHEETS ON ATS AND | | GENERATOR. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2015-02-26 |
|
|
Cont ID |
|
Sent By |
MISC2 |
Date |
2015-02-23 |
Time |
14:07 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-02-23 |
Time |
14:08 |
Sent To |
B |
|
Notes |
2015-02-26 14:07:38 | 2/23/2015 | | PROJECT: FL DEPT OF HEALTH | | PERMIT#: 15020119 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) SHEET E-1 | | NOTE 13 INDICATED ON PARTIAL 1ST FL DEMOLITION PLAN | | STATES EXISTING FUSE CABINET TO BE RELOCATED BY OWNER. | | THIS FUSE CABINET DOES NOT APPEAR ON THE NEW PLANS. | | WHERE IS THE NEW LOCATION?/ IS IT UNDER THIS SCOPE OR | | ON A FUTURE SCOPE UNDER A SEPARATE PERMIT? | | | | 2) PROVIDE MANUFACTURER DATA SHEETS ON ATS AND | | GENERATOR. | | | | 3) PROVIDE LOAD CALCULATION FOR MDP3 TO INDICATE | | AVAILABLE CAPACITY FOR INCREASED LOAD. | | | | 4) PROVIDE A DETAILED PANEL SCHEDULE AND LOAD | | CALCULATION FOR NEW PANEL LSI. NEC 408.4 AND 215.5 | | | | 5) SHEET E-2 | | PROVIDE THE SIZE OF GUTTER INDICATED IN NOTE 10 | | | | 6) INDICATE THE SIZE OF THE OCPD AT ECB-GLS. | | | | 7) PROVIDE SUPPORT DOCUMENTATION FOR PROJECT VALUATION | | INDICATED ON THE PERMIT APPLICATION. VALUATION SHALL | | INCLUDE ALL EQUIPMENT INSTALLATION COSTS OVERHEAD AND | | PROFFIT TO COVER THE COMPETE COST OF THE INSTALLATION | | FBC WPB AMENDMENTS. SECTION 109.3 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2015-07-21 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-07-21 |
Time |
15:00 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2015-07-17 09:04:43 | DHAYES DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2015-07-16 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-07-16 |
Time |
13:23 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-07-09 |
Time |
12:57 |
Sent To |
|
|
Notes |
2015-07-14 12:31:15 | 7/14 TO DAH DESK | | | 2015-07-09 12:57:55 | ON SHILL DESK |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-05-11 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-05-11 |
Time |
13:26 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-04-23 |
Time |
15:35 |
Sent To |
|
|
Notes |
2015-04-23 15:35:48 | TO DAH DESK | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-03-06 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-03-06 |
Time |
17:22 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-03-06 |
Time |
17:22 |
Sent To |
|
|
Notes |
2015-02-04 12:21:12 | ROUTED TO ZONING |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2015-02-05 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2015-02-05 |
Time |
10:22 |
Rev Time |
0.00 |
Received By |
sgraham |
Date |
2015-02-05 |
Time |
10:22 |
Sent To |
E |
|
Notes |
|
|