Plan Review Details - Permit 15020073
Plan Review Stops For Permit 15020073
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-27 Cont ID  
Sent By jwitmer Date 2015-02-27 Time 09:24 Rev Time 0.00
Received By jwitmer Date 2015-02-27 Time 07:01 Sent To  
Notes
2015-02-27 08:15:26BUILDING PLAN REVIEW
 PERMIT: 15020073
 ADD: 513 N. SAPODILLA AVE.
 CONT: MISO CONSTRUCTION
 TEL: ( 561)246-0411
 E-MAIL:[email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MAY 11, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
  
 1ST REVIEW
 DATE: FRI. FEB. 27/ 2015
 ACTION: DENIED
  
 1) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) WALL LOUVERS,
 (E) SHUTTERS/ IF WINDOWS ARE NOT IMPACT RESISTANT
 TESTED
  
 2) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 3) THE COVERSHEET INDICATE THIS IS A LEVEL LL
 ALTERATION AND DRYWALL IS TO BE PATCHED, THE PLANS DOES
 NOT PROVIDE AS TO HOW MUCH IN AREA THIS DRYWALL PATCH
 WORK WILL BE, SECTION 703.4.1 OF THE EXST. BLDG. CODE
 MAY APPLY. 703.4.1 SUPPLEMENTAL INTERIOR FINISH
 REQUIREMENTS.
 WHERE THE WORK AREA ON ANY FLOOR EXCEEDS 50 PERCENT OF
 THE FLOOR AREA, SECTION 703.4 SHALL ALSO APPLY TO THE
 INTERIOR FINISH IN EXITS AND CORRIDORS SERVING THE WORK
 AREA THROUGHOUT THE FLOOR.
  
 4) THE PLANS DO NOT INDICATE WHERE THE WORK AREA IS
 CLEARLY, DOES THE GUARDRAILS COMPLY WITH EXST. BLDG.
 CODE 703.5.
  
 5) SHEET A-2 LIST THIS PROJECT AS A R-3 OCCUPANCY, SEE
 WIND DESIGN, PLEASE REVISE 2010 FBC-B 310.1 R-2.
 APARTMENT HOUSES.
  
 6) SHEET A-1 1ST FLOOR VERSES SHEET A-3 THE 2ND FLOOR,
 THE 1ST FLOOR SHOWS DROPPED CEILINGS TO RUN THE A/C
 DUCT, THE 2ND FLOOR PLANS DO NOT SHOW A HATCHED AREA
 BUT IT APPEARS ON THE 2ND FLOOR MECHANICAL SOME OF THE
 A/C DROPS WILL BE SIDE WALL WHERE OTHERS WILL BE
 CEILING GRILLES. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED, MAY BE A DISSCREPANCY IN THE PLANS.
  
 7) SHEET A-3 NOTES TENANT SEPARATION WALL INDICATES IN
 NOTE # 1 SOUND INSULATION IS REQUIRED FOR THE TENANT
 SEPARATION WALL. PLEASE PROVIDE COMPLIANCE WITH 2010
 FBC-B 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM
 EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45
 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS OR OPENINGS IN
 CONSTRUCTION ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES;
 RECESSED CABINETS; BATHTUBS; SOFFITS; OR HEATING,
 VENTILATING OR EXHAUST DUCTS SHALL BE SEALED, LINED,
 INSULATED OR OTHERWISE TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT APPLY TO DWELLING
 UNIT ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 8) THE PLANS WILL ALSO NEED ON THE 2ND FLOOR, FLOOR
 SYSTEM TO SHOW COMPLIANCE WITH 2010 FBC-B 1207.3
 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492.
  
 9) A-3 FLOOR FINISHES SHOW CARPET FOR ALL FLOORS, WILL
 THERE BE CARPET IN THE BATHROOMS AND KITCHEN AREAS AS
 WELL? THE PLANS ARE NOT CLEAR IF DRYWALL IS BEING
 REPLACED IN THE SHOWER COMPARTMENTS AS WELL? 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 10) PLEASE SHOW COMPLIANCE WITH 2010 FBC-B 1209.2 ATTIC
 SPACES.
 AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM
 BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A
 CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A 30-INCH (762
 MM) MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE
 PROVIDED AT OR ABOVE THE ACCESS OPENING.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-05 Cont ID  
Sent By dhayes Date 2015-02-05 Time 11:02 Rev Time 0.00
Received By dhayes Date 2015-02-05 Time 09:57 Sent To  
Notes
2015-02-05 11:02:322/5/2015
 PROJECT: 513 SAPODILLA
 PERMIT#: 15020073
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) CHANGE TITLE BLOCK ON COVER SHEET TO CORRECT THE
 PROJECT ADDRESS. WPB AMENDMENTS TO FBC 107.2.1
  
 2) PROVIDE FAULT CURRENT RATING CALCULATION AND VERIFY
 THE ELECTRICAL SERVICE HAS A FAULT CURRENT RATING THAT
 IS SUFFICIENT AT NOMINAL CIRCUIT VOLTAGE FOR THE
 CURRENT THAT MUST BE INTERRUPTED. NEC 110.9
  
 3) PROVIDE CIRCUIT NUMBERS ON THE FLOOR PLAN
 CORESPONDING TO THE PANEL DIRECTORY. WPB AMENDMENTS TO
 FBC 107.2.1
  
 4) PROVIDE DISCONNECTS WHERE REQUIRED FOR EQUIPMERNT
 SUCH AS WATER HEATER AND AHU. WPB AMENDMENTS TO FBC
 107.2.1
  
 5) PROVIDE SMOKE ALARMS LOCATED AS REQUIRED FOR NEW
 DWELLINGS. SMOKE DETECTOR REQUIRED OUTSIDE OF SLEEPING
 ROOMS. FBC-RESIDENTIAL 314 AND 315.
  
 6) ADD A NOTE FOR THE LUMINAIRES IN CLOTHES CLOSETS
 SHALL BE INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF
 THE NEC 410.16(A) AND (B).
  
 7) PROVIDE A LIGHT FOR THE STAIRS THAT CAN BE CONTROLED
 FROM THE TOP OR BOTTOM LANDINGS. FBC 1205.4, 1205.5,
 1006.1, NEC 210.70
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-02-11 Cont ID  
Sent By pleduc Date 2015-02-11 Time   Rev Time 0.00
Received By pleduc Date 2015-02-11 Time 10:20 Sent To  
Notes
2015-02-11 11:16:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE PLANS WERE NOT STAPLED OR SEALED TOGETHER. THE
 PALNS SHALL BE SUBMITTED STAPLED OR SEALED TOGETHER TO
 NOT BE SEPARATED.
  
 SHEET C - 1 HAS AN INCORRECT ADDRESS IN THE ENGINEER
 COLUMN NOTED AS MIAMI, PLEASE DELETE AND CORRECT.
  
 SHEET C - 1 HAS THE INCORRECT EDITION OF THE FLORIDA
 FIRE PREVENTION CODE AS 2010. IT SHOULD INDICATE THE
 2012 EDITION OF NFPA 1 AND 101.
  
 ALL CONSTUCTION SHALL COMPLY WITH THE REQUIRMENTS OF
 NFPA 101, CHAPET 43, BUILDING REHABILITATION, SECTION
 43.6 RECONSTRUCTION.
  
 PER NFPA 101 43.6.4.1 IN A BUILDING WITH REHABILITATION
 WORK AREAS INVOLVING OVER 50 PERCENT OF THE AGGREGATE
 BUILDING AREA, AUTOMATIC SPRINKLER SYSTEMS SHALL BE
 PROVIDED ON THE HIGHEST FLOOR CONTAINING REHABILITATION
 WORK AREA AND ON ALL FLOORS BELOW IN ACCORDANCE WITH
 THE REQUIREMENTS OF OTHER SECTIONS OF THIS CODE
 APPLICABLE TO NEW CONTRUCTION FOR THE OCCUPANCY. THIS
 OCCUPANCY SHALL MEET THE REQUIREMENTS OF NFPA 101,
 CHAPTER 30 NEW APARTMENT BUILDINGS.THE FIRE SPRINKLER
 SYSTEM SHALL BE SUPERVISED PER NFPA 30.
  
 PER SECTION 43.6.2.2 ILLUMINATION, EMERGENCY LIGHTING
 AND MARKING OF MEANS OF EGRESS, 43.6.2.2.2 WHERE THE
 RECONSTRUCTION REHABILITATION WORK AREA ON ANY FLOOR
 EXCEEDS 50 PERCENT OF THEAT FLOOR AREA, MEANS OF EGRESS
 THROUGHOUT THE FLOOR SHALL BE PROVIDED WITH
 ILLUMINATION, EMERGENCY LIGHTING AND MARKING OF MEANS
 OF EGRESS IN ACCORDANCE WITH THE REQUIREMENTS OF OTHER
 SECTIONS OF THIS CODE APPLICABLE TO NEW CONTRUCTION FOR
 THE OCCUPANCY.
  
 PER SECTION 43.6.5 FIRE ALARM SYSTEMS - SMOKE ALARMS,
 43.6.5.1 IN LODGING OR ROOMING HOUSES, HOTELS, AND
 DORMITORIES, AND APARTMENT BUILDINGS, INDIVIDUAL
 SLEEPING ROOMS, GUEST ROOMS, AND DWELLING UNITS WITHIN
 REHABILITATION WORK AREA SHALL BE PROVIDED WITH SMOKE
 ALARMS COMPLYING WITH THE REQUIRMENTS OF OTHER SECTIONS
 OF THIS CODE APPLICABLE TO NEW CONSTRUCTION FOR THE
 OCCUPANCY.
  
 THE CONSTUCTION SHALL COMPLY WITH NFPA 101, CHAPTER 30,
 NEW APARTMENT BUILDINGS.
  
 EMERGENCY LIGHTING IS REQUIRED AT EACH PORCH AREA. EXIT
 SIGNAGE IS REQUIRED AT THE SECOND FLOOR LEVEL PORCH
 AREA.
  
 EACH ENTRY DOOR IN THE FIRST AND SECOND FLOOR AREA IS
 REQUIRED TO HAVE NOT LESS THAN A 20 MINUTE FIRE
 PROTECTION RATING AND SHALL BE SELF CLOSING AND
 LATCHING.
  
  
  
  
  
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2015-03-30 Cont ID  
Sent By fmittner Date 2015-03-30 Time 16:20 Rev Time 0.00
Received By fmittner Date 2015-03-30 Time 16:20 Sent To Z
Notes
2015-03-30 16:21:51NO PRODUCT APPROVALS PROVIDED FRO WINDOWS....SHALL BE
 WHITE FRAME 1/1/ SINGLE HUNG ALUMINUM WITH CLEAR OR LOW
 E GLASS. QUESTIONS CONTACT FRIEDERIKE MITTNER AT
 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-12 Cont ID  
Sent By skennedy Date 2015-05-12 Time 10:07 Rev Time 0.00
Received By skennedy Date 2015-02-03 Time 09:57 Sent To  
Notes
2015-02-05 09:56:43C21

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-03-10 Cont ID  
Sent By hmoser Date 2015-03-10 Time 10:35 Rev Time 0.00
Received By hmoser Date 2015-03-10 Time 09:44 Sent To  
Notes
2015-03-10 10:34:59PLAN DENIED
 1) PROVIDE DUCT SIZE ON PLAN,
 PROVIDE CAN AND GRILL SIZE ON PLAN
 PROVIDE CFM ON EACH SUPPLY DUCT.
 PER SECTION 107 FBC 2010
 2) SHOW LOCATION OF RETURN AIR ON PLANS.
 PER SECTION 107 FBC 2010
 3) REFER TO SECTION 601.4 BALANCED
 RETURN AIR 2010 FBC (M)
 4) REFER TO SECTION 601.4 MATERIALS
 WITHIN PLENUM'S INCLUDING CLOSET DOOR
 AND CONDENSATE LINE 2010 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-02-07 Cont ID  
Sent By tklarge Date 2015-02-07 Time 06:55 Rev Time 0.00
Received By tklarge Date 2015-02-07 Time 06:55 Sent To  
Notes
2015-02-07 06:58:321) THE APPLICATION STATES "DEMO AND COMPLETE BUILDOUT
 PER PLAN" ON THE APPLICATION BUT THE PLANS DO NOT
 INDICATE ANY NEW PLUMBING WORK. CLARIFY. SHOW THE
 COMPLETE SCOPE OF PLUMBING WORK TO BE DONE. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.

Review Stop Z ZONING
Rev No 1 Status F Date 2015-04-23 Cont ID  
Sent By fmittner Date 2015-04-23 Time 16:07 Rev Time 0.00
Received By aaponte Date 2015-04-23 Time 16:07 Sent To  
Notes
2015-04-23 16:18:311. PROPOSED RENOVATIONS EXCEED 50% OF THE STRUCTURE
 VALUE, THEREFORE THE SITE SHALL BE BROUGHT INTO
 COMPLIANCE WITH LANDSCAPING REQUIREMENTS.
 2. PLEASE PROVIDE A SURVEY OF THE PROPERTY.
 3. A LANDSCAPE PLAN FOR THE PARKING AREA SHALL BE
 SUBMITTED.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.