Plan Review Details - Permit 15020068
Plan Review Stops For Permit 15020068
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-06-23 Cont ID  
Sent By jgomez Date 2015-06-23 Time 17:06 Rev Time 0.00
Received By jgomez Date 2015-06-23 Time 16:19 Sent To E
Notes
2015-06-23 17:07:266/23/15 PLANS SENT TO DAVID HAYES FOR ELECTRICAL
 REVIEW. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-03-24 Cont ID  
Sent By jgomez Date 2015-03-24 Time 10:33 Rev Time 0.00
Received By jgomez Date 2015-03-24 Time 10:26 Sent To  
Notes
2015-03-24 10:37:531- NEW DRAWINGS SUBMITTED NEED TO HAVE THE ARCHITECT'S
 SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 481 FLORIDA
 STATUTES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
2015-03-20 17:31:32NEW DRAWINGS SUBMITTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-03-13 Cont ID  
Sent By jgomez Date 2015-03-13 Time 14:22 Rev Time 0.00
Received By jgomez Date 2015-03-13 Time 13:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-07-07 Cont ID  
Sent By albarran Date 2015-07-07 Time 09:24 Rev Time 0.00
Received By albarran Date 2015-07-07 Time 09:24 Sent To I
Notes
2015-07-07 09:31:31AFTER A DISCUSSION W/THE GC & EC, IT WAS DETERMINED
 THAT THE ELECTRICAL DRAWING SUBMITTED FOR PERMITTING
 WENT WAY BEYOND THE INTENDED SCOPE OF THE JOB WHICH IS
 ONLY TO RETURN THE WATER HEATER TO ITS ORIGINAL
 LOCATION AND CONNECTED TO THE EXISTING CIRCUIT. ADD THE
 CEILING GFCI OUTLET FOR THE GARAGE DOOR OPENER AND AN
 ADDITIONAL GFCI OUTLET IN THE GARAGE.
 PER NEC & FBC REQUIREMENTS, ALL GARAGE OUTLETS SHALL BE
 GFCI PROTECTED. ALL NEW INSTALLATIONS SHALL BE
 ARC-FAULT PROTECTED. PER FBC-R314-315 SMOKE DETECTOR
 COMPLIANCE IS MANDATED. CO DETECTION AS PER FBC-315 IS
 REQUIRED.
  
 THIS PERMIT IS READY TO BE ISSUED WITH THE PROVISO TO
 SUBMIT A CORRECTED AS-BUILT PLANS FOR APPROVAL PRIOR TO
 THE FIRST ELECTRICAL INSPECTION.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-06-24 Cont ID  
Sent By albarran Date 2015-06-24 Time 14:26 Rev Time 0.00
Received By albarran Date 2015-06-24 Time 12:59 Sent To I
Notes
2015-06-24 14:26:56PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE CORRECTIONS NOTED.
 THE FOLLOWING ITEMS SHALL BE CORRECTED AND THE PLANS
 RESUBMITTED FOR A SECOND REVIEW:
  
 1. PER NFPA 72 ? 29.8.3.4(4), SMOKE DETECTORS SHALL NOT
 BE INSTALLED WITHIN 3? FROM THE TIP OF A CEILING FAN
 BLADE OR ANY OTHER SOURCE OF FORCED AIR (A/C VENT OR
 RETURN).
 2. PER FBC-R ? 315, YOU SHALL INSTALL A CO (CARBON
 MONOXIDE) DETECTOR WITHIN 10? OF THE BEDROOM DOOR.
 THEREFORE THE CEILING DETECTOR IN THE VESTIBULE OUTSIDE
 THE BEDROOMS SHALL BE A COMBINATION UNIT.
 3. PER NEC 230.70, YOU SHALL HAVE A DISCONNECT ON THE
 OUTSIDE OF THE STRUCTURE OR AT A POINT NEAREST THE
 ENTRY THERETO. IN YOUR CASE ADJACENT TO THE SERVICE
 METER WILL DO.
 4. PER NEC 440.14, THE DISCONNECT FOR THE RELOCATED AHU
 SHALL BE READILY ACCESSIBLE.
 5. CONFIRM THE NEED FOR ?NOTE 21?, OF THE GENERAL
 NOTES.
 6. CORRECT CONDUCTOR INSULATION AS INDICATED ON ?NOTE
 28? OF GENERAL NOTES.
 7. CORRECT THE RISER DIAGRAMS TO INCLUDE THE REQUIRED
 SERVICE DISCONNECT AND RENAME PANEL ?A? AS ?RELOCATED?
 RATHER THAN ?EXISTING?.
 8. CORRECT ?NOTE 2? OF NOTE ().
 9. PER NEC 210.52(C), THE KITCHEN OUTLETS ARE INDICATED
 ON THE DRAWING ARE NOT COMPLIANT WITH MINIMUM CODE
 REQUIREMENTS.
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2015-03-24 Cont ID  
Sent By tklarge Date 2015-03-24 Time 11:05 Rev Time 0.00
Received By tklarge Date 2015-03-24 Time 11:05 Sent To  
Notes
2015-03-24 11:05:49SEE BUILDING & PLUMBING COMMENTS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-03-16 Cont ID  
Sent By dhayes Date 2015-03-16 Time 09:44 Rev Time 0.00
Received By dhayes Date 2015-03-16 Time 09:19 Sent To  
Notes
2015-03-16 09:44:263/16/2015
 PROJECT: CONVERT STUDY BACK INTO GARAGE
 PERMIT#: 15020068
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) NEC 408.4
 PROVIDE A PANEL SCHEDULE TO INDICATE ALL CIRCUITRY
 INVOLVED IN CONVERSION. EVERY CIRCUIT AND CIRCUIT
 MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS
 CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4
  
 2) FBC 107
 INDICATE CIRCUIT NUMBERS ON THE FLOOR PLAN WITH
 CORRESPONDING OCPD AND WIRE SIZE AS INDICATED ION THE
 PANEL SCHEDULE. FBC 107
  
 3) NEC 210.8
 INDICATE ALL OUTLETS IN THE GARAGE TO BE GFI PROTECTED.
 INCLUDING THE GARAGE DOOR OPENER OUTLET. NEC 210.8
  
 4) NEC 210.12, 406.11
 ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 5) FBC-RESIDENTIAL 314 AND 315.
 WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. ADD SMOKE AND CO
 DETECTOR OUTSIDE OF SLEEPING AREAS. FBC-RESIDENTIAL 314
 AND 315.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-07-07 Cont ID  
Sent By albarran Date 2015-07-07 Time 09:32 Rev Time 0.00
Received By albarran Date   Time   Sent To  
Notes
2015-07-07 09:32:31SEE ELECTRICAL PROVISO

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-06-24 Cont ID  
Sent By albarran Date 2015-06-24 Time 14:30 Rev Time 0.00
Received By albarran Date 2015-05-07 Time 15:37 Sent To  
Notes
2015-06-24 14:32:47FAILED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED VIA
 EMAIL. SENT TO SMALL DENIED BIN "A". MA
2015-05-07 15:40:37R20
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-24 Cont ID  
Sent By tklarge Date 2015-03-24 Time 11:06 Rev Time 0.00
Received By tklarge Date 2015-03-20 Time 10:42 Sent To  
Notes
2015-03-24 10:42:36NEW DRAWING SUBMITTED. SENT TO TIM LARGE FOR REVIEW.
 JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-16 Cont ID  
Sent By dhayes Date 2015-03-16 Time 09:44 Rev Time 0.00
Received By dhayes Date 2015-02-03 Time 15:01 Sent To  
Notes
2015-02-04 15:01:07R05

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2015-06-23 Cont ID  
Sent By jgomez Date 2015-06-23 Time 17:05 Rev Time 0.00
Received By jgomez Date 2015-06-23 Time 17:05 Sent To  
Notes
2015-06-23 17:06:19NO MECHANICAL INFORMATION SUBMITTED. PROVIDE COMPLETE
 INFORMATION UNDER A SEPARATE PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-03-13 Cont ID  
Sent By jgomez Date 2015-03-13 Time 14:23 Rev Time 0.00
Received By jgomez Date 2015-03-13 Time 14:23 Sent To  
Notes
2015-03-13 14:29:501- PROPOSED FLOOR PLAN ON SHEET A2.1 SHOWS AIR HANDLER
 UNIT LOCATED IN THE NEW GARAGE SPACE. THERE IS NOT
 INFORMATION SUBMITTED REGARDING THE A/C. PROVIDE
 COMPLETE INFORMATION FOR THE MECHANICAL SCOPE OF WORK
 UNDER A SEPARATE PERMIT. . SEC. 107.3.5.3(10) OF CITY
 AMENDMENTS TO FBC. AND SEC. 105.1 CITY AMENDMENTS.
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-06-11 Cont ID  
Sent By tklarge Date 2015-06-11 Time 10:30 Rev Time 0.00
Received By tklarge Date 2015-06-11 Time 10:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-03-24 Cont ID  
Sent By tklarge Date 2015-03-24 Time 10:57 Rev Time 0.00
Received By tklarge Date 2015-03-24 Time 10:57 Sent To  
Notes
2015-03-24 10:58:38PLANS SHALL BE SIGNED AND SEALED BY DESIGN PROFESSIONAL
 (ARCHITECT) PER FL. ADMIN. CODE RULE 61G1-16.001
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
2015-03-20 17:30:59NEW DRAWINGS SUBMITTED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-02-07 Cont ID  
Sent By tklarge Date 2015-02-07 Time 08:12 Rev Time 0.00
Received By tklarge Date 2015-03-07 Time 04:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-05-19 Cont ID  
Sent By sgraham Date 2015-05-19 Time 15:54 Rev Time 0.00
Received By sgraham Date 2015-05-19 Time 15:54 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-02-10 Cont ID  
Sent By sgraham Date 2015-02-10 Time 16:08 Rev Time 0.00
Received By sgraham Date 2015-02-10 Time 16:08 Sent To  
Notes
2015-02-10 10:42:462/10/15