Plan Review Details - Permit 15020033
Plan Review Stops For Permit 15020033
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-03-26 Cont ID  
Sent By rmcdouga Date 2015-03-26 Time 06:24 Rev Time 0.00
Received By rmcdouga Date 2015-03-25 Time 15:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-03-19 Cont ID  
Sent By rmcdouga Date 2015-03-19 Time 16:59 Rev Time 0.00
Received By rmcdouga Date 2015-03-19 Time 15:51 Sent To  
Notes
2015-03-19 16:59:29PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE INSTALLATION DRAWINGS THAT WERE SUBMITTED WITH
 THE MULLIONS (NOA NO. 11-1031.07) WERE NOT SHRUNK TO
 FIT ON THE SMALLER 8.5" X 11" PAPER AND PARTS OF THE
 INFORMATION IS MISSING FROM EACH PAGE. SUBMIT TWO SETS
 OF DRAWINGS THAT ARE COMPLETE. FBC 107.2.1 & DCA RULE
 9N-7
  
 2) THE PRODUCT APPROVALS FOR THE FIXED WINDOW THAT WERE
 SUBMITTED (NOA NO.14-0515.11) ARE ONLY RATED FOR SMALL
 MISSILE IMPACT. THEY ARE REQUIRED TO HAVE IMPACT
 PROTECTION DEVICES FOR LARGE MISSLE IMPACT. FBC R
 301.2.1.2 SUBMIT TWO COPIES OF THE PRODUCT APPROVALS
 FOR THE IMPACT PROTECTION DEVICES ALONG WITH AN
 INSTALLATION SCHEDULE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-03 Cont ID  
Sent By rmcdouga Date 2015-03-03 Time 09:12 Rev Time 0.00
Received By rmcdouga Date 2015-03-03 Time 08:44 Sent To  
Notes
2015-03-03 09:22:06PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE SUBMITTALS FOR THE FIXED
 GLASS WINDOW AND THE STRUCTURAL MULLIONS.
  
 2) THE SCOPE OF WORK ON THE APPLICATION INCLUDES THE
 UPGRADE OF THE ELECTRICAL PANEL, HOWEVER, NO ELECTRIC
 WORK WAS SHOWN ON THE PLANS. PLEASE CLARIFY. FBC
 107.2.1

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-03-05 Cont ID  
Sent By fmittner Date 2015-03-05 Time 16:41 Rev Time 0.00
Received By fmittner Date 2015-03-05 Time 16:41 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-02-12 Cont ID  
Sent By fmittner Date 2015-02-12 Time 10:34 Rev Time 0.00
Received By fmittner Date 2015-02-12 Time 10:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-19 Cont ID  
Sent By rmcdouga Date 2015-03-19 Time 16:59 Rev Time 0.00
Received By rmcdouga Date 2015-03-05 Time 17:13 Sent To  
Notes
2015-03-05 17:14:08TO RM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-03 Cont ID  
Sent By rmcdouga Date 2015-03-03 Time 09:22 Rev Time 0.00
Received By rmcdouga Date 2015-02-02 Time 15:05 Sent To  
Notes
2015-02-03 15:05:54SENT TO R2 BIN FOR REVIEW. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2015-03-05 Cont ID  
Sent By fmittner Date 2015-03-05 Time 16:41 Rev Time 0.00
Received By fmittner Date 2015-03-05 Time 16:41 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-02-12 Cont ID  
Sent By fmittner Date 2015-02-12 Time 10:34 Rev Time 0.00
Received By fmittner Date 2015-02-12 Time 10:34 Sent To  
Notes
2015-02-10 10:41:582/10/15


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved