Plan Review Details - Permit 15020030
Plan Review Stops For Permit 15020030
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-05-20 Cont ID  
Sent By jgomez Date 2015-05-20 Time 16:38 Rev Time 0.00
Received By jgomez Date 2015-05-20 Time 16:38 Sent To  
Notes
2015-05-20 17:00:35BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE DRAWINGS THAT MATCH SHEET INDEX ON SHEET
 A-0.
 2- WINDOWS ON SECOND FLOOR THAT HAVE WINDOW SILL LESS
 THAN 24" FROM FINISHED FLOOR OF THAT ROOM NEED TO
 COMPLY WITH THE FALL PREVENTION REQUIREMENTS OF SEC.
 R612.2. PROVIDE SPECIFICATIONS SHOWING COMPLIANCE.
 3- REVISE HANDRAIL AND GUARDRAILS DETAILS. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF HANDRAILS AND
 GUARDRAILS SHOWING COMPLIANCE WITH THE LIVE LOADS OF
 TABLE R301.5, SEC. R311.7.7 AND SEC. R312 OF 2010
 FBC-RESIDENTIAL.
 SPECIFY ALL FRAMING MEMBERS MATERIALS AND CONNECTORS.
 RAILING DETAIL SHOWN ON THE LEFT HAND SIDE DOESN'T
 MATCH ELEVATION ON THE RIGHT HAND SIDE.
 4-REVISE STEEL COLUMN DETAIL. SIZE TO-MATCH PLANS.
 CLEARLY SPECIFY TOP & BOTTOM CONNECTORS AND FASTENERS
 THAT MATCH ACTUAL FIELD CONDITIONS. SPECIFY BEAM SIZE.
 5- PROVIDE FLOOR FRAMING DETAILS FOR NEW 2ND FLOOR
 W-I-C.
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR FRENCH DOORS
 WITH SIZES AS SHOWN ON PLANS FOR ALL DOORS.
 7- REVISE THE WIND LOADS SHOWN ON THE EXTERIOR
 ELEVATIONS (SHEET A2 OR A3). REVISE EXPOSURE TO "D" AS
 SHOWN ON SHEET A0. AND REVISE THE DESIGN PRESSURES
 ACCORDINGLY. ALSO. KEY CORRECTLY THE "A" AND "B"
 WINDOWS/DOORS ON THE ELEVATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-05-20 Cont ID  
Sent By J. Gomez Date 2015-05-18 Time 18:41 Rev Time 0.00
Received By jgomez Date 2015-05-18 Time 18:41 Sent To  
Notes
2015-05-18 18:43:26 
  
 1- ENGINEER OF RECORD SEALED PLANS WITH AN OLD SEAL
 THAT READS "CERTIFICATE" INSTEAD OF "LICENSE". PROVIDE
 PLANS WITH CURRENT SEAL. RULE 61G15-23.001(1).
  
 *****REVIEW IN PROGRESS...
  
 1- REVISE HANDRAIL AND GUARDRAILS DETAILS. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION AND INSTALLATION OF HANDRAILS AND
 GUARDRAILS SHOWING COMPLIANCE WITH THE LIVE LOADS OF
 TABLE R301.5, SEC. R311.7.7 AND SEC. R312 OF 2010
 FBC-RESIDENTIAL.
  
 2- PROVIDE COMPLETE SHORING DETAILS AND SPECIFICATIONS
 FOR THE INSTALLATION OF THE NEW STEEL COLUMNS. SEC.
 107.2.1.3 CITY AMENDMENTS. REPEAT COMMENT. NOT
 ADDRESSED.
  
 4- PROVIDE PRODUCT APPROVAL (TWO COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) WINDOW MULLIONS. PROVIDE PRODUCT APPROVAL FOR BAY
 WINDOWS MULLIONS. AS SHOWN ON PLANS. FLORIDA PRODUCT
 APPROVAL FL15922 SUBMITTED IS FOR STRAIGHT MULLIONS
 ONLY. AND, CLEARLY SPECIFY MULLION SIZE FOR ALL WINDOWS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.
 NOTE: AS AN ALTERNATIVE YOU CAN SUBMIT PRODUCT APPROVAL
 FOR COMPLETE BAY WINDOWS ASSEMBLY AS SHOWN ON PLANS.
 REPEAT COMMENT. NOT ADDRESSED.
  
 B) THERE WAS INFORMATION SUBMITTED FOR CASEMENT
 WINDOWS. PLANS AND NEW WINDOW SCHEDULE DON'T SHOW
 CASEMENT WINDOWS. CLARIFY/REVISE AS REQUIRED. IF
 CASEMENT WINDOWS WILL BE INSTALLED, THEN PROVIDE THE
 APPROVED FLORIDA PRODUCT APPROVAL NUMBER THAT
 CORRESPOND TO INFORMATION SUBMITTED. IF THERE IS NONE,
 THEN MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL.
 REPEAT COMMENT. NOT ADDRESSED.
  
 C) NEED TWO COPIES OF DOUBLE HUNG PRODUCT APPROVALS.
 ONLY ONE WAS SUBMITTED. REPEAT COMMENT. NOT ADDRESSED.
  
 D) FRENCH DOORS WITH SIZES AS SHOWN ON PLANS FOR DOORS
 #1 AND #8. . NOTE: FLORIDA PRODUCT APPROVAL FL14285
 SUBMITTED IS NOT ACCEPTABLE. ALL THE CHARTS WERE
 BLOCKED OUT. PRODUCT APPROVAL CAN NOT BE ALTERED.
 PROVIDE COMPLETE PRODUCT APPROVAL AND PROVIDE PRODUCT
 APPROVAL THAT COVERS DOORS #1 AND #8. REPEAT COMMENT.
 NOT ADDRESSED.
  
 E) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED
 ON ALL DETAILS ON SHEET A-4. NOTE: PROVIDE ONLY THE
 FLORIDA PRODUCT APPROVAL FRONT PAGE AND PAGE SHOWING
 THE SPECIFIED CONNECTOR OR LIST THE FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO THE SPECIFIED CONNECTOR. REPEAT
 COMMENT. NOT ADDRESSED.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVAL. SEC. 107.3.4.1 CITY AMENDMENTS.
 REPEAT COMMENT. NOT ADDRESSED.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED SHEET AND
 SUBMIT OLD PLANS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-04-10 Cont ID  
Sent By jgomez Date 2015-04-10 Time 11:01 Rev Time 0.00
Received By jgomez Date 2015-04-10 Time 11:00 Sent To  
Notes
2015-04-10 11:05:22RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PHASE 2 OF THIS PROJECT (WINDOWS AND DOORS) WAS
 ADDED ON 3/11/15. PLEASE UPDATE VALUATION DECLARED IN
 THE PERMIT APPLICATION AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS TO FBC. PLEASE PROVIDE COPY OF SIGNED
 CONTRACT FOR THE OVERALL SCOPE OF WORK.
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- SHEET A-2:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 NEW HANDRAILS AND GUARDRAILS SHOWING COMPLIANCE WITH
 ALL THE REQUIREMENTS OF SEC. R311.7.7 AND SEC. R312 OF
 2010 FBC-RESIDENTIAL. ALSO, PROVIDE COMPLETE DETAILS
 AND SPECIFICATIONS SHOWING COMPLIANCE WITH THE LIVE
 LOAD REQUIREMENTS OF TABLE R301.5 OF 2010
 FBC-RESIDENTIAL. REPEAT COMMENT. "GUARDRAIL/HANDRAIL
 DETAILS" SUBMITTED DOESN'T MATCH PLANS. THERE ARE NOT
 DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE
 HANDRAIL AND GUARDRAIL SHOWING COMPLIANCE WITH THE LIVE
 LOAD OF TABLE R301.5. GUARDRAIL HEIGHT IS DIMENSIONED
 AS 36", WHILE GUARDRAIL NOTE STATES 42". REVISE AS
 REQUIRED TO MATCH. SEC. 1608.2 SPECIFIED ON GUARDRAIL
 DETAIL DOESN'T APPLY TO SINGLE FAMILY RESIDENCE (R3).
 THAT SECTIONS APPLIES TO THE BUILDING CODE NOT THE
 RESIDENTIAL CODE. BESIDES THAT SECTION IS "RESERVED".
 REVISE AS REQUIRED.
  
 3- PROVIDE COMPLETE SHORING DETAILS AND SPECIFICATIONS
 FOR THE INSTALLATION OF THE NEW STEEL COLUMNS. SEC.
 107.2.1.3 CITY AMENDMENTS. REPEAT COMMENT. NOT
 ADDRESSED.
  
 4- PROVIDE PRODUCT APPROVAL (TWO COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) WINDOW MULLIONS. PROVIDE PRODUCT APPROVAL FOR BAY
 WINDOWS MULLIONS. AS SHOWN ON PLANS. FLORIDA PRODUCT
 APPROVAL FL15922 SUBMITTED IS FOR STRAIGHT MULLIONS
 ONLY. AND, CLEARLY SPECIFY MULLION SIZE FOR ALL WINDOWS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.
 NOTE: AS AN ALTERNATIVE YOU CAN SUBMIT PRODUCT APPROVAL
 FOR COMPLETE BAY WINDOWS ASSEMBLY AS SHOWN ON PLANS.
 REPEAT COMMENT. NOT ADDRESSED.
  
 B) THERE WAS INFORMATION SUBMITTED FOR CASEMENT
 WINDOWS. PLANS AND NEW WINDOW SCHEDULE DON'T SHOW
 CASEMENT WINDOWS. CLARIFY/REVISE AS REQUIRED. IF
 CASEMENT WINDOWS WILL BE INSTALLED, THEN PROVIDE THE
 APPROVED FLORIDA PRODUCT APPROVAL NUMBER THAT
 CORRESPOND TO INFORMATION SUBMITTED. IF THERE IS NONE,
 THEN MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL.
 REPEAT COMMENT. NOT ADDRESSED.
  
 C) NEED TWO COPIES OF DOUBLE HUNG PRODUCT APPROVALS.
 ONLY ONE WAS SUBMITTED. REPEAT COMMENT. NOT ADDRESSED.
  
 D) FRENCH DOORS WITH SIZES AS SHOWN ON PLANS FOR DOORS
 #1 AND #8. . NOTE: FLORIDA PRODUCT APPROVAL FL14285
 SUBMITTED IS NOT ACCEPTABLE. ALL THE CHARTS WERE
 BLOCKED OUT. PRODUCT APPROVAL CAN NOT BE ALTERED.
 PROVIDE COMPLETE PRODUCT APPROVAL AND PROVIDE PRODUCT
 APPROVAL THAT COVERS DOORS #1 AND #8. REPEAT COMMENT.
 NOT ADDRESSED.
  
 E) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED
 ON ALL DETAILS ON SHEET A-4. NOTE: PROVIDE ONLY THE
 FLORIDA PRODUCT APPROVAL FRONT PAGE AND PAGE SHOWING
 THE SPECIFIED CONNECTOR OR LIST THE FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO THE SPECIFIED CONNECTOR. REPEAT
 COMMENT. NOT ADDRESSED.
  
 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVAL. SEC. 107.3.4.1 CITY AMENDMENTS.
 REPEAT COMMENT. NOT ADDRESSED.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED SHEET AND
 SUBMIT OLD PLANS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-12 Cont ID  
Sent By jgomez Date 2015-03-12 Time 18:24 Rev Time 0.00
Received By jgomez Date 2015-03-12 Time 18:09 Sent To  
Notes
2015-03-12 18:25:38RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC
  
 1- BOTH SETS OF PLANS NEED TO BE SIGNED AND SEALED BY
 THE ENGINEER OF RECORD AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE. ONLY ONE SET WAS SIGNED AND SEALED.
  
 2- PHASE 2 OF THIS PROJECT (WINDOWS AND DOORS) WAS
 ADDED ON 3/11/15. PLEASE UPDATE VALUATION DECLARED IN
 THE PERMIT APPLICATION AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS TO FBC. PLEASE PROVIDE COPY OF SIGNED
 CONTRACT FOR THE OVERALL SCOPE OF WORK.
  
 3-SHEET A-0:
 A) THIS IS ALTERATION LEVEL 3 NOT ALTERATION LEVEL 2.
 REVISE AS REQUIRED. SEC. 405 OF 2010 FBC-EXISTING
 BUILDING.
  
 B) REVISE THE WIND EXPOSURE CATEGORY. ACCORDING TO SEC.
 R301.2.1.4.3 OF 2010 FBC-RESIDENTIAL, THIS BUILDING IS
 LOCATED IN EXPOSURE "D" NOT "C".
  
 C) AREA CALCULATIONS CALLS FOR NEW LIVING SPACE ON
 SECOND FLOOR. CLEARLY IDENTIFY ON PLANS WHICH IS THE
 NEW LIVING AREA. BRING PLANS TO PALM BEACH COUNTY (2300
 N. JOG RD) TO ACCESS IMPACT IMPACT FEES. BRING BACK
 COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES
 ARE DUE. REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 4- REVISE THE DESIGN DATA ON SHEET A-3. REVISE THE WIND
 EXPOSURE AND REVISE THE WINDOWS/DOORS DESIGN PRESSURES
 TO CORRESPOND TO EXPOSURE "D".
  
 5- SHEET A-2:
 A) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 NEW HANDRAILS AND GUARDRAILS SHOWING COMPLIANCE WITH
 ALL THE REQUIREMENTS OF SEC. R311.7.7 AND SEC. R312 OF
 2010 FBC-RESIDENTIAL. ALSO, PROVIDE COMPLETE DETAILS
 AND SPECIFICATIONS SHOWING COMPLIANCE WITH THE LIVE
 LOAD REQUIREMENTS OF TABLE R301.5 OF 2010
 FBC-RESIDENTIAL.
  
 B) PROVIDE COMPLETE SECTION/DETAIL AND SPECIFICATIONS
 FOR THE INSTALLATION OF NEW STEEL COLUMNS BY THE GREAT
 ROOM AREA. SPECIFY ALL CONNECTORS TOP AND BOTTOM. AND
 ENGINEER TO PROVIDE SHORING SPECIFICATIONS. SEC.
 107.2.1.3 OF CITY AMENDMENTS.
  
 6- PROVIDE PRODUCT APPROVAL (TWO COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) WINDOW MULLIONS. PROVIDE PRODUCT APPROVAL FOR BAY
 WINDOWS MULLIONS. AS SHOWN ON PLANS. FLORIDA PRODUCT
 APPROVAL FL15922 SUBMITTED IS FOR STRAIGHT MULLIONS
 ONLY. AND, CLEARLY SPECIFY MULLION SIZE FOR ALL WINDOWS
 TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.
 NOTE: AS AN ALTERNATIVE YOU CAN SUBMIT PRODUCT APPROVAL
 FOR COMPLETE BAY WINDOWS ASSEMBLY AS SHOWN ON PLANS.
  
 B) THERE WAS INFORMATION SUBMITTED FOR CASEMENT
 WINDOWS. PLANS AND NEW WINDOW SCHEDULE DON'T SHOW
 CASEMENT WINDOWS. CLARIFY/REVISE AS REQUIRED. IF
 CASEMENT WINDOWS WILL BE INSTALLED, THEN PROVIDE THE
 APPROVED FLORIDA PRODUCT APPROVAL NUMBER THAT
 CORRESPOND TO INFORMATION SUBMITTED. IF THERE IS NONE,
 THEN MANUFACTURER MAY APPLY FOR LOCAL PRODUCT APPROVAL.
  
 C) NEED TWO COPIES OF DOUBLE HUNG PRODUCT APPROVALS.
 ONLY ONE WAS SUBMITTED.
  
 D) FRENCH DOORS WITH SIZES AS SHOWN ON PLANS FOR DOORS
 #1 AND #8. . NOTE: FLORIDA PRODUCT APPROVAL FL14285
 SUBMITTED IS NOT ACCEPTABLE. ALL THE CHARTS WERE
 BLOCKED OUT. PRODUCT APPROVAL CAN NOT BE ALTERED.
 PROVIDE COMPLETE PRODUCT APPROVAL AND PROVIDE PRODUCT
 APPROVAL THAT COVERS DOORS #1 AND #8.
  
 E) ALL USP AND SIMPSON STRUCTURAL CONNECTORS SPECIFIED
 ON ALL DETAILS ON SHEET A-4. NOTE: PROVIDE ONLY THE
 FLORIDA PRODUCT APPROVAL FRONT PAGE AND PAGE SHOWING
 THE SPECIFIED CONNECTOR OR LIST THE FLORIDA PRODUCT
 APPROVAL NUMBER NEXT TO THE SPECIFIED CONNECTOR.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVAL. SEC. 107.3.4.1 CITY AMENDMENTS.
  
 8- SHEET A-4: CLARIFY DOOR FRAMING DETAIL AND NEW
 HEADER DETAIL. WHERE IS THIS DETAIL TAKEN AT. THESE ARE
 TWO DIFFERENT FRAMING DETAILS. ONE IS FOR A WOOD FRAMED
 WALL AND THE OTHER ONE IS FOR AN EXISTING CBS WALL.
 REVISE BOTH DETAILS AS REQUIRED TO MATCH ACTUAL FIELD
 CONDITIONS. SEC. 107.2.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED SHEET AND
 SUBMIT OLD PLANS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-05-21 Cont ID  
Sent By jgomez Date 2015-05-21 Time 10:22 Rev Time 0.00
Received By rlecky Date 2015-05-21 Time 10:06 Sent To  
Notes
2015-05-21 10:23:45 
 5/21/15 APPROVED BY ROBERT LECKY. JG.
2015-05-20 18:39:21NEW DRAWINGS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-05-05 Cont ID  
Sent By R. Lecky Date 2015-05-05 Time 11:34 Rev Time 0.00
Received By rlecky Date 2015-05-05 Time 10:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-04-07 Cont ID  
Sent By rlecky Date 2015-04-07 Time 13:58 Rev Time 0.00
Received By rlecky Date 2015-04-07 Time 13:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-26 Cont ID  
Sent By rlecky Date 2015-02-26 Time 12:35 Rev Time 0.00
Received By rlecky Date 2015-02-26 Time 10:16 Sent To  
Notes
2015-02-26 12:41:0915020030
 1209 N. FLAGLER DR.
 SF REMODEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 SHOW THE LOCATION OF THE ELECTRICAL SERVICE AND
 DISCONNECT ON THE BUILDING. VERIFY THE MAIN DISCONNECT
 IS LOCATED AT THE POINT OF SERVICE. VERIFY THE
 UNPROTECTED SERVICE CONDUCTORS ARE NOT LOCATED IN THE
 BUILDING. INCLUDE A PANEL SCHEDULE FOR EACH PANEL. NEC
 230.70(A)(1)
  
 ADD RECEPTACLES (DINING, WALL AT STAIRS, KITCHEN,
 BEDROOM #3 AND #4) SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES 2 FEET OR
 MORE IN WIDTH HAVE A RECEPTACLE. NEC 210.52
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED AT FRONT AND
 REAR ELEVATIONS. NEC 210.8, 210.52(E)(1)
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED ON BALCONY. NEC
 210.8, 210.52(E)(3)
  
 SWITCH CONTROLLED LIGHTING OUTLETS ARE REQUIRED AT ALL
 ENTRANCES. NEC 210.70 (A) (2) (B)
  
 THE SMOKE DETECTORS MUST BE INTERCONNECTED. FBC R313.2
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-05-20 Cont ID  
Sent By jgomez Date 2015-05-20 Time 11:45 Rev Time 0.00
Received By jgomez Date 2015-04-27 Time   Sent To  
Notes
2015-04-28 09:28:48R-28

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-10 Cont ID  
Sent By jgomez Date 2015-04-10 Time 14:11 Rev Time 0.00
Received By jgomez Date 2015-03-17 Time 11:09 Sent To  
Notes
2015-03-18 11:10:04R13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-13 Cont ID  
Sent By jgomez Date 2015-03-13 Time 08:33 Rev Time 0.00
Received By jgomez Date 2015-02-02 Time 07:11 Sent To  
Notes
2015-02-03 07:13:11EXPEDITED. SENT TO R13 BIN FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2015-04-10 Cont ID  
Sent By jgomez Date 2015-04-10 Time 14:11 Rev Time 0.00
Received By jgomez Date 2015-04-10 Time 14:11 Sent To  
Notes
2015-04-10 14:12:20NO NEW LIVING AREA ADDED.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-03-13 Cont ID  
Sent By jgomez Date 2015-03-13 Time 07:52 Rev Time 0.00
Received By jgomez Date 2015-03-13 Time 07:51 Sent To  
Notes
2015-03-13 07:53:101- AREA CALCULATIONS ON SHEET A-0 CALLS FOR NEW LIVING
 SPACE ON SECOND FLOOR. CLEARLY IDENTIFY ON PLANS WHICH
 IS THE NEW LIVING AREA. BRING PLANS TO PALM BEACH
 COUNTY (2300 N. JOG RD) TO ACCESS IMPACT IMPACT FEES.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQURIED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2015-05-20 Cont ID  
Sent By J.Gomez Date 2015-05-20 Time 11:43 Rev Time 0.00
Received By jgomez Date 2015-05-20 Time 11:43 Sent To  
Notes
2015-05-20 11:45:43NO MECHANICAL INFORMATION SUBMITTED. NICK BESSENROTH
 (CONTRACTOR) SAID MECHANICAL CONTRACTOR WILL PROVIDE
 COMPLETE INFORMATION UNDER A SEPARATE PERMIT. JG.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-04-10 Cont ID  
Sent By jgomez Date 2015-04-10 Time 14:08 Rev Time 0.00
Received By jgomez Date 2015-04-10 Time 14:08 Sent To  
Notes
2015-04-10 14:11:12RESIDENTIAL (R3) ALTERATION SECOND MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- SCOPE OF WORK ON SHEET A-0 CALLS FOR THE RELOCATION
 OF A/C EQUIPMENT. THERE IS NOT INFORMATION SUBMITTED
 REGARDING THE RELOCATION. OF THE EQUIPMENT.. IS THE
 EQUIPMENT NEW? IF SO, PROVIDE EQUIPMENT SIZING
 CALCULATIONS. AND, THERE ARE NOT PLANS SUBMITTED
 SHOWING A/C WORK FOR THE PROPOSED LAYOUT. SEC. 107..5.3
 OF CITY AMENDMENTS TO FBC.
  
 2- PROPOSED LAUNDRY AREA: PROVIDE INFORMATION SHOWING
 COMPLIANCE WITH CLOTHES DRYER EXHAUST SEC. M1502 OF
 2010 FBC-RESIDENTIAL.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-03-13 Cont ID  
Sent By jgomez Date 2015-03-13 Time 08:24 Rev Time 0.00
Received By jgomez Date 2015-03-13 Time 07:07 Sent To  
Notes
2015-03-13 08:32:48RESIDENTIAL (R3) ALTERATION MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- SCOPE OF WORK ON SHEET A-0 CALLS FOR THE RELOCATION
 OF A/C EQUIPMENT. THERE IS NOT INFORMATION SUBMITTED
 REGARDING THE RELOCATION. OF THE EQUIPMENT.. IS THE
 EQUIPMENT NEW? IF SO, PROVIDE EQUIPMENT SIZING
 CALCULATIONS. AND, THERE ARE NOT PLANS SUBMITTED
 SHOWING A/C WORK FOR THE PROPOSED LAYOUT. SEC. 107..5.3
 OF CITY AMENDMENTS TO FBC.
  
 2- PROPOSED LAUNDRY AREA: PROVIDE INFORMATION SHOWING
 COMPLIANCE WITH CLOTHES DRYER EXHAUST SEC. M1502 OF
 2010 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2015-05-20 Cont ID  
Sent By tklarge Date 2015-05-20 Time 15:17 Rev Time 0.00
Received By tklarge Date 2015-05-20 Time 15:17 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-05-16 Cont ID  
Sent By TKLarge Date 2015-05-16 Time 06:28 Rev Time 0.00
Received By tklarge Date 2015-05-16 Time 04:56 Sent To  
Notes
2015-05-16 06:03:591) SHT.A-0 - SHEET INDEX LISTS SHEETS A-0,D-1, A-1,
 A-2, A-3,E-1. SHTS.D-1, A-1, & A-3 ARE NOT IN THESE SET
 OF PLANS. CLARIFY.
 2)) AS DRAWN, THE SANITARY RISER FOR THE 2ND FLOOR DOES
 NOT MEET THE2010 FBC-R CODE SEC. P3108.1 FOR A
 HORIZONTAL WET VENT. THE HORIZONTAL WET VENT HAS TOO
 MANY FIXTURES ON IT PER THE DEFINITION OF A "BATHROOM
 GROUP." NOT MORE THAN TWO FIXTURES OF ANY TYPE CAN BE
 CONNECTED TO THE WET VENT SYSTEM.
 NOTE: YOU MAY WANT TO CONTACT ME TO SET UP AN
 APPOINTMENT WITH ME TO REVIEW THE RISER DIAGRAM.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-04-04 Cont ID  
Sent By tklarge Date 2015-04-04 Time 12:20 Rev Time 0.00
Received By tklarge Date 2015-04-04 Time 10:37 Sent To  
Notes
2015-04-04 10:39:281) THE BATH FOR BEDROOM NUMBER 4 IS NOT SHOWN ON THE
 2ND FLOOR RISER DIAGRAM.WPB AMEND. TO 2010 FBC SEC.
 107.3.5.1.3.
 2) AS DRAWN, THE SANITARY RISER FOR THE 2ND FLOOR DOES
 NOT MEET CODE. THE HORIZONTAL WET VENT HAS ONE TOO MANY
 LAVATORIES, ONE TOO MANY SHOWERS AND EXCEEDS THE
 MAXIMUM NUMBER OF FIXTURE UNITS FOR A 2" WET VENT PER
 TABLE P3108.3 OF THE 2010 FBCR SEC. P3108.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-02-04 Cont ID  
Sent By tklarge Date 2015-02-04 Time 07:17 Rev Time 0.00
Received By tklarge Date 2015-02-04 Time 06:01 Sent To  
Notes
2015-02-04 07:17:121) SHOW THE RELOCATED LAVATORY IN BATH #1 ON THE
 SANITARY RISER. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 2) AS DRAWN, THE SANITARY RISER DOES NOT MEET CODE. THE
 HORIZONTAL WET VENT HAS ONE TOO MANY LAVATORIES, ONE
 TOO MANY SHOWERS AND EXCEEDS THE MAXIMUM NUMBER OF
 FIXTURE UNITS FOR A 2" WET VENT PER TABLE P3108.3 OF
 THE 2010 FBCR SEC. P3108.
 3) PLANS SHALL BEAR THE SEAL AND SIGNATURE OF THE
 DESIGN PROFESSIONAL PER THE FL. ADMIN. RULE 61G15
 -23.002.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-02-10 Cont ID  
Sent By ajones Date 2015-02-10 Time 10:37 Rev Time 0.00
Received By ajones Date 2015-02-10 Time 10:37 Sent To  
Notes
***NONE***