Plan Review Details - Permit 15020001
Plan Review Stops For Permit 15020001
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-03-19 Cont ID  
Sent By rmcdouga Date 2015-03-19 Time 09:52 Rev Time 0.00
Received By rmcdouga Date 2015-03-19 Time 09:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-03-12 Cont ID  
Sent By rmcdouga Date 2015-03-18 Time 11:05 Rev Time 0.00
Received By rmcdouga Date 2015-03-12 Time 18:01 Sent To  
Notes
2015-03-12 18:18:25PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE NOA THAT WAS SUBMITTED FOR THE SINGLE HUNG
 WINDOWS (NOA NO. 12-0127.16) WAS SUPERSEDED BY NOA NO.
 14-0908.10 ON NOVEMBER 06, 2014. SUBMIT TWO COPIES OF
 THE CURRENT PRODUCT APPROVAL.
  
 2) THE NOA THAT WAS SUBMITTED FOR THE STRUCTURAL
 MULLIONS (NOA NO. 12-0127.07) WAS SUPERSEDED BY NOA NO.
 14-0908.08 ON NOVEMBER 06, 2014. THE INSTALLATION
 INSTRUCTION SHEETS WERE NOT SHRUNK TO FIT ON THE 8.5" X
 11" PAPER AND SOME OF THE INFORMATION IS MISSING. MARK
 THE SIZES AND PRESSURES ON THE PRODUCT APPROVAL FOR THE
 MULLIONS THAT WILL BE USED. FBC 107.3.4 & DCA RULE 9N-3
  
 3) SPECIFY THE DESIGN PRESSURE AND THE GLASS TYPE FOR
 THE WINDOWS BY MARKING THEM ON THE PRODUCT APPROVALS.
 FBC 107.3.4
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-24 Cont ID  
Sent By rmcdouga Date 2015-02-24 Time 15:42 Rev Time 0.00
Received By rmcdouga Date 2015-02-24 Time 15:42 Sent To  
Notes
2015-02-24 16:24:54PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE NOA THAT WAS SUBMITTED FOR THE SINGLE HUNG
 WINDOWS HAS BEEN SUPERSEDED. THE CURRENT ONE IS NOA NO.
 14-0908.09.
  
 2) IT APPEARS THAT SOME OF THE WINDOWS ARE DOUBLES THAT
 ARE CONNECTED WITH A STRUCTURAL MULLION. PLEASE
 CLARIFY. SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 STRUCTURAL MULLIONS. MARK THE SIZES AND PRESSURES ON
 THE PRODUCT APPROVAL FOR THE ONES THAT WILL BE USED.
 FBC 107.3.4 & DCA RULE 9N-3
  
 3) SPECIFY THE DESIGN PRESSURE AND THE GLASS TYPE FOR
 THE WINDOWS BY MARKING THEM ON THE PRODUCT APPROVALS.
 FBC 107.3.4
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-02-02 Cont ID  
Sent By fmittner Date 2015-02-02 Time 08:34 Rev Time 0.00
Received By fmittner Date 2015-02-02 Time 08:34 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-19 Cont ID  
Sent By rmcdouga Date 2015-03-19 Time 09:52 Rev Time 0.00
Received By rmcdouga Date 2015-03-18 Time 11:05 Sent To  
Notes
2015-03-18 11:05:51SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-18 Cont ID  
Sent By rmcdouga Date 2015-03-18 Time 11:04 Rev Time 0.00
Received By rmcdouga Date 2015-03-12 Time 08:12 Sent To B
Notes
***NONE***