Plan Review Details - Permit 15011106
Plan Review Stops For Permit 15011106
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-02-25 Cont ID  
Sent By shill Date 2015-02-25 Time 16:05 Rev Time 0.00
Received By shill Date 2015-02-25 Time 16:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-02-24 Cont ID  
Sent By shill Date 2015-02-24 Time 07:13 Rev Time 0.00
Received By shill Date 2015-02-24 Time 07:13 Sent To  
Notes
2015-02-24 07:13:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THERE IS A CONFLICT BETWEEN THE WIND DP CHART/WIND
 SPEC SHEETS AND THE WINDOW DIAGRAM SHEET. THE FIRST TWO
 PAGES SHOW A 38IN HIGH BEDROOM WINDOW, BUT THE WINDOW
 DIAGRAM SHEETS SHOWS THIS OPENING AS A KITCHEN.
  
 NOT ENOUGH INFORMATION TO DETERMINE CODE COMPLIANCE.
 PLEASE CORRELATE SHEETS AND ROOM DESIGNATIONS SO A
 COMPLETE REVIEW CAN BE DONE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-02 Cont ID  
Sent By shill Date 2015-02-02 Time 09:41 Rev Time 0.00
Received By shill Date 2015-02-02 Time 09:41 Sent To  
Notes
2015-02-02 09:48:04****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. TYPES OF WINDOWS PROPOSED ARE NOT CLEAR. DOUBLE HUNG
 AND HORIZONTAL ROLLER WINDOW PRODUCT APPROVALS WERE
 SUBMITTED. THE WINDOW SCHEDULE HAS A NAMING CONVENTION
 OF "DHIM" AND "DHBI" (SEE BELOW). REVISE PLANS TO
 CLEARLY CORRELATE PRODUCT APPROVALS SUBMITTED WITH THE
 WINDOWS ON THE PLAN.
  
 FOR EXAMPLE - ONE WINDOWS IS "PGT 9700 DHBI" BUT THE
 PGT WINDOW PRODUCT APPROVAL IS A HORIZONTAL ROLLER
 MODEL 510. THE OTHER WINDOWS ARE "AC86 DHIM" BUT THE
 DOUBLE HUNG PRODUCT APPROVAL IS "WEATHER STOPPER 9500".
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-24 Cont ID  
Sent By shill Date 2015-02-24 Time 07:13 Rev Time 0.00
Received By shill Date 2015-02-06 Time   Sent To  
Notes
2015-02-07 06:59:23INCOMING SENT TO S. HILLS' DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-02 Cont ID  
Sent By shill Date 2015-02-02 Time 09:48 Rev Time 0.00
Received By shill Date 2015-02-02 Time 09:48 Sent To  
Notes
2015-01-30 14:31:09MISC 1