2015-01-30 08:35:40 | PLAN REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C WITH | | A 170 MPH VULT WIND SPEED AND HAS A 22' MEAN ROOF | | HEIGHT. THE REQUIRED COMPONENT AND CLADDING NEGATIVE | | PRESSURE FOR THE FLAT ROOF IS -103 PSF FOR THE CORNERS | | (ROOF ZONE 3). THIS UPLIFT EXCEEDS THE MAXIMUM DESIGN | | PRESSURE OF -90 PSF FOR THE SYSTEM THAT YOU SELECTED | | FROM THE PRODUCT APPROVAL. |
|
|
|