Plan Review Details - Permit 15010988
Plan Review Stops For Permit 15010988 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2015-02-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2015-02-18 |
Time |
13:41 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-02-18 |
Time |
11:13 |
Sent To |
E |
|
Notes |
2015-02-18 13:32:35 | PLAN REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SHOW THAT THE GUEST HOUSE COMPLIES WITH FBC-R314.3.1 | | ALTERATIONS, REPAIRS AND ADDITIONS. | | WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | LOCATED AS REQUIRED FOR NEW DWELLINGS. | | | | 2) SHOW THAT THE GUEST HOUSE COMPLIES WITH FBC-R315.1 | | CARBON MONOXIDE PROTECTION. | | EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING | | BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS | | ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR | | APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER | | FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE | | AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL | | CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH | | ROOM USED FOR SLEEPING PURPOSES. | | | | 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 | | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD. SPECIFICALLY, PROVIDE ROOFING, | | WINDOW, MULLION AND DOOR SUBMITTALS. | | | | 4) SHOW COMPLIANCE WITH FBC 1503.4.2.1 OVERFLOW | | SCUPPERS. | | WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT | | PROVIDED, OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR | | PARAPETS NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4 | | INCHES (102 MM) ABOVE THE FINISHED ROOF COVERING AND | | SHALL BE LOCATED AS CLOSE AS PRACTICAL TO REQUIRED | | VERTICAL LEADERS OR DOWNSPOUTS OR WALL AND PARAPET | | SCUPPERS. AN OVERFLOW SCUPPER SHALL BE SIZED IN | | ACCORDANCE WITH THE FLORIDA BUILDING CODE, PLUMBING. | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2015-02-19 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-02-19 |
Time |
16:52 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-02-19 |
Time |
15:45 |
Sent To |
|
|
Notes |
2015-02-19 16:52:07 | 2/19/2015 | | PROJECT: RIVERA | | PERMIT#: 15010988 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) REVISE THE RISER DIAGRAM TO INDICATE A SINGLE | | GROUNDING ELECTRODE CONDUCTOR SIZED IN ACCORDANCE WITH | | NEC 250.66 TO ONE COMMON GROUNDING ELECTRODE SYSTEM. | | NEC 250.66 | | | | 2) AN INTERSYSTEM BONDING TERMINATION FOR CONNECTING | | INTERSYSTEM BONDING AND GROUNDING CONDUCTORS REQUIRED | | FOR OTHER SYSTEMS SHALL BE PROVIDED EXTERNAL TO | | ENCLOSURES AT THE SERVICE EQUIPMENT AND AT THE | | DISCONNECTING MEANS FOR ANY ADDITIONAL BUILDINGS OR | | STRUCTURES. NEC 250.94. | | | | 3) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE | | LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND | | SPECIFIC PURPOSE OR USE. NEC 408.4 | | | | 4) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS | | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT | | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE | | INTERRUPTED. NEC 110.9 | | | | 5) OCPD?S SHALL NOT BE LOCATED IN THE VICINITY OF | | EASILY IGNITIBLE MATERIAL, SUCH AS IN CLOTHES CLOSETS. | | NEC 240.24(B)(2)(D) | | | | 6) PROVIDE SPECS ON TANKLESS WATER HEATERS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | | | | | | | | | |
|
|
Review Stop |
HIST |
HISTORICAL |
Rev No |
1 |
Status |
P |
Date |
2015-02-03 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2015-02-03 |
Time |
09:42 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2015-02-03 |
Time |
09:42 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-02-19 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-02-19 |
Time |
16:52 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-01-28 |
Time |
16:08 |
Sent To |
|
|
Notes |
2015-02-04 16:11:19 | R20 | 2015-01-28 15:52:15 | ROUTED TO HISTORIC ~NSD |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
F |
Date |
2015-02-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2015-02-18 |
Time |
07:58 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-02-18 |
Time |
07:58 |
Sent To |
|
|
Notes |
2015-02-18 08:03:38 | CONVERTING FROM STORAGE TO HABITABLE SPACE. BEFORE A | | PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES MUST BE | | PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE SET OF | | PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM BEACH | | COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH THE | | IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT MUST BE | | RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE THE | | BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL | | PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2015-02-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2015-02-18 |
Time |
09:18 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-02-18 |
Time |
08:35 |
Sent To |
|
|
Notes |
2015-02-18 08:43:16 | PLAN REVIEW COMMENTS | | | | 1ST REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) FBC ENERGY CONSERVATION - SECT. 403.6.1 EQUIPMENT | | SIZING. | | HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN | | ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT | | LOADS CALCULATED IN ACCORDANCE WITH MANUAL J OR OTHER | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES, | | BASED ON BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION | | OF THE BUILDING. THE MANUFACTURER AND MODEL NUMBER OF | | THE OUTDOOR AND INDOOR UNITS (IF SPLIT SYSTEM) SHALL BE | | SUBMITTED ALONG WITH THE SENSIBLE AND TOTAL COOLING | | CAPACITIES AT THE DESIGN CONDITIONS DESCRIBED IN | | SECTION 302.1. THIS CODE DOES NOT ALLOW DESIGNER SAFETY | | FACTORS, PROVISIONS FOR FUTURE EXPANSION OR OTHER | | FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM SIZING | | CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY LOCAL | | INTERMITTENT MECHANICAL VENTILATION SUCH AS STANDARD | | KITCHEN AND BATHROOM EXHAUST SYSTEMS. PROVIDE EQUIPMENT | | SIZING CALCULATIONS. | | | | 2) FBC - 107.3.5.3 PROVIDE A MECHANICAL PLAN TO SHOW | | SUPPLY DUCTS PER FBC-R M16 & BATH EXHAUST PER FBC-R | | M15. | | | | 3) FBC -107.3.5.1.4 MECHANICAL MINIMUM PLAN REVIEW | | CRITERIA: SHOW, EXHAUST SYSTEMS, CLOTHES DRYER EXHAUST, | | KITCHEN EQUIPMENT EXHAUST, SPECIALTY EXHAUST SYSTEMS, | | EQUIPMENT, EQUIPMENT LOCATION, MAKE-UP AIR, | | ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS, VENTILATION, | | COMBUSTION AIR, CHIMNEYS, FIREPLACES AND VENTS, | | APPLIANCES, BOILERS, REFRIGERATION, BATHROOM | | VENTILATION, LABORATORY, DESIGN FLOOD ELEVATION. | | | | 4) FBC 107.2.1 PROVIDE THE MODEL NUMBERS AND | | SPECIFICATIONS OF THE HEATING AND COOLING EQUIPMENT IN | | AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN THAT | | CORRESPONDS WITH THE EQUIPMENT SIZING CALCULATIONS. | | | | 5) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT | | BEDROOMS. | | | | 6) M1602.2 PROHIBITED SOURCES. OUTDOOR AND RETURN AIR | | FOR A FORCED-AIR HEATING OR COOLING SYSTEM SHALL NOT BE | | TAKEN FROM THE FOLLOWING LOCATIONS: | | 4. A CLOSET, BATHROOM, TOILET ROOM, KITCHEN, GARAGE, | | MECHANICAL ROOM, BOILER ROOM, FURNACE ROOM, | | UNCONDITIONED ATTIC OR OTHER DWELLING UNIT. | | THE PROPOSED FLOOR PLAN ON SHEET A-1 SHOWS THE NEW AIR | | HANDLER LOCATED IN A CLOSET IN THE KITCHEN. | | | | | | | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2015-02-13 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-02-13 |
Time |
10:59 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-02-13 |
Time |
09:26 |
Sent To |
|
|
Notes |
2015-02-13 11:00:03 | SEPARATE PERMIT REQD. FOR GAS. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2015-02-03 |
|
|
Cont ID |
|
Sent By |
fmittner |
Date |
2015-02-03 |
Time |
09:42 |
Rev Time |
0.00 |
Received By |
fmittner |
Date |
2015-02-03 |
Time |
09:42 |
Sent To |
|
|
Notes |
|
|
|