Plan Review Details - Permit 15010822
Plan Review Stops For Permit 15010822
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-03-27 Cont ID  
Sent By dhayes Date 2015-03-27 Time 10:39 Rev Time 0.00
Received By dhayes Date 2015-03-27 Time 10:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-03-06 Cont ID  
Sent By dhayes Date 2015-03-06 Time 13:29 Rev Time 0.00
Received By dhayes Date 2015-03-06 Time 13:29 Sent To  
Notes
2015-03-06 13:40:501) NO WINDLOAD CALCULATIONS HAVE BEEN INCLUDED I THE
 SUBMITTAL. PROVIDE WIND LOAD CALCULATIONS THAT INCLUDE
 THE LUMINAIRE AND CAMERA INSTALLATION. WPB AMENDMENTS
 TO THE FBC 107
  
 2) REVISE THE GROUNDING DETAIL FOR THE BROOKS PULL BOX
 AND THE LIGHT POLES ON SHEET E-2 TO INDICATE THE
 EQUIPMENT GROUNDING CONDUCTOR CONNECTING TO THE DRIVEN
 GROUND ROD. NEC 250.32
  
 3) REVISE THE DETAILS FOR THE POLES THAT ARE PROPOSED
 TO SHARE THE LOW VOLTAGE CAMERA WIRING WITH THE HIGH
 VOLTAGE LIGHTING WIRING.
 A) THE LIGHTH POLE DETAIL INDICATES A 1" PVC WITH
 WIRING FOR LIGHTING ONLY, PLEASE CLARIFY. ARE THERE
 CAMERAS INSTALLED ON THESE POLES?
 B) THE SECURITY CAMERA DETAIL INDICATES AN ALUMINUM
 CONDUIT FOR THE CAMERAS BUT ALSO INDICATES IN THE TITLE
 OF THE DETAIL THESE POLES SHARE THE CIRCUITRY FOR THE
 LIGHTING BUT DOES NOT INDICATE ANY DETAIL AS TO HOW.
 C) THE 5FT SECURITY CAMERA POLE DETAIL INDICATES A 1"
 PVC WITH PULL BOX AND NOTES THAT THERE IS A 120V GFI
 MOUNTED INSIDE A STAINLESS STEEL CAMERA CABINET BUT
 AGAIN DOES NOT INDICATE HOW THE POWER AND LIGHTING
 CIRCUITRY ARE PROPOSED TO BE INSTALLED.
 THERE IS NO MENTION OF THE ROUTING OR INSTALLATION OF
 THE SPECIFIC WIRING METHODS AND HOW THEY WILL BE
 SEPARARTED OR HOW THE BONDING AND GROUNDING WILL BE
 ACCOMPLISHED. ALL THREE OF THESE DETAILS NEED TO BE
 REVISED TO SHOW MORE DETAIL THE INSTALLATION AND
 SEPARATION OF SYSTEMS WIRING AND THE GROUNDING AND
 BONDING IN ACCORDANCE WITH THE NEC.
  
 4) PROVIDE MANUFACTURER PRODUCT APPROVALS ON ALL CAMERA
 AND RELATED EQUIPMENT SUCH AS POWER SUPPLIES, STAINLESS
 STEEL ENCLOSURES AND THE CAMERAS THEMSELVES.
  
 5) THE INTERIOR OF AN UNDERGROUND RACEWAY SHALL BE
 CONSIDERED A WET LOCATION. ALL CONDUCTORS WITHIN THE
 RACEWAY SHALL BE LISTED ACCORDINGLY. SUITABILITY FOR
 INSTALLATION AND USE IN CONFORMITY WITH THE PROVISIONS
 OF THIS CODE. INDICATE ON THE PLAN AND PROVIDE A
 SUBMITTALE OF THE FIBER OPTIC CABLE PROPOSED TO BE
 INSTALLED IN AN UNDERGROUND RACEWAY. NEC 110.3(B)
  
 6) INDICATE HOW THE PROPOSED EXTERIOR LIGHTING IS
 INTENDED TO COMPLY WITH THE FBC-ENERGY SECTION 505.2.4
 EXTERIOR LIGHTING CONTROLS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-05 Cont ID  
Sent By dhayes Date 2015-02-05 Time 17:10 Rev Time 0.00
Received By dhayes Date 2015-02-05 Time 16:14 Sent To Z
Notes
2015-02-05 17:11:01NO WINDLOAD CALCULATIONS WERE INCLUDED I THE SUBMITTAL.
 PROVIDE WIND LOAD CALCULATIONS THAT INCLUDE THE
 LUMINAIRE AND CAMERA INSTALLATION.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-03-27 Cont ID  
Sent By dhayes Date 2015-03-27 Time 10:39 Rev Time 0.00
Received By dhayes Date 2015-03-20 Time 18:06 Sent To  
Notes
2015-03-20 18:07:02RE-SUBMITTAL SENT TO DAVID HAYES FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-06 Cont ID  
Sent By dhayes Date 2015-03-06 Time 13:42 Rev Time 0.00
Received By dhayes Date 2015-02-20 Time 16:36 Sent To  
Notes
2015-02-25 16:36:44RE-SUBMITTAL SENT TO DAVID HAYES FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-12 Cont ID  
Sent By eschneid Date 2015-02-12 Time 17:59 Rev Time 0.00
Received By eschneid Date 2015-01-23 Time 16:14 Sent To  
Notes
2015-01-23 12:00:45ELECTRICAL OVER 5K

Review Stop Z ZONING
Rev No 1 Status P Date 2015-02-12 Cont ID  
Sent By dhayes Date 2015-02-12 Time 17:59 Rev Time 0.25
Received By eschneid Date 2015-02-12 Time 17:59 Sent To  
Notes
***NONE***