Plan Review Details - Permit 15010691
Plan Review Stops For Permit 15010691
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-12-21 Cont ID  
Sent By lmarchan Date 2015-12-21 Time 10:44 Rev Time 0.00
Received By mvaldes Date 2015-12-21 Time 18:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-06-02 Cont ID  
Sent By dhayes Date 2015-06-02 Time 14:12 Rev Time 0.00
Received By dhayes Date 2015-06-02 Time 13:23 Sent To  
Notes
2015-06-02 13:29:496/2/2015
 PROJECT: INTERIOR REMODEL
 PERMIT#: 14071125
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW OF REVISION #15010691
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) PERMEANT PLAQUES ARE REQUIRED AT THE SERVICE
 ENTRANCE AND PANEL LOCATIONS TO IDENTIFY THE MEANS OF
 DISCONNECT(S) REQUIRED TO DISCONNECT ALL UNGROUNDED
 CONDUCTORS SUPPLYING THE NEWLY CREATED SPACE. WHERE A
 BUILDING OR STRUCTURE HAS ANY COMBINATION OF FEEDERS,
 BRANCH CIRCUITS, OR SERVICES PASSING THROUGH IT OR
 SUPPLYING IT, A PERMANENT PLAQUE OR DIRECTORY SHALL BE
 INSTALLED AT EACH FEEDER AND BRANCH-CIRCUIT DISCONNECT
 LOCATION DENOTING ALL OTHER SERVICES, FEEDERS, OR
 BRANCH CIRCUITS SUPPLYING THAT BUILDING OR STRUCTURE OR
 PASSING THROUGH THAT BUILDING OR STRUCTURE AND THE AREA
 SERVED BY EACH. NEC 225.37 SEE ALSO NEC 230.2(E)
  
 2) PROVIDE PANEL SCHEDULE(S) INDICATING ALL LIGHTING
 AND POWER OUTLET CIRCUITS. EVERY CIRCUIT AND CIRCUIT
 MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS
 CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4
  
 3) IDENTIFY THE CIRCUITS FEEDING THE EMERGENCY AND EXIT
 LIGHTING ON THE FLOOR PLAN IN COMPLIANCE WITH THE NEC
 700.12. THE BRANCH CIRCUIT FEEDING THE UNIT EQUIPMENT
 SHALL BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY
 LOCAL SWITCHES. NEC 700.12(F)
  
 4) THIS IS A REVISION TO EXISTING PERMIT AND PLAN. THE
 DESIGN PROFESSIONAL RESPONSIBLE IS JOHN HOLT PE OF
 WELLINGTON. WHILE YOU MAY PROVIDE INFORMATION IN THE
 WAY OF "MARKED UP" OR "RED LINED" PLANS TO THE DESIGN
 PROFESSIONAL, ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. FBC, WPB
 AMENDMENTS 107.2.1
 4B) ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS,
 OR DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND
 BEING FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS
 PROVIDED TO THE OWNER OR THE OWNER?S REPRESENTATIVE
 SHALL BE SIGNED BY THE LICENSEE, DATED, AND SEALED WITH
 SAID SEAL. FL SS 471.025 668.001-668.006.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-03-26 Cont ID  
Sent By   Date 2015-03-26 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2015-04-15 11:32:47PER STEVE CIADIELLO ON 3/26/15 THE PLANS WERE TURNED
 BACK IN FOR THE SECOND TIME AFTER SPEAKING WITH THE
 CONTRACTOR ABOUT THIS ISSUE: THE DESIGNERS TITLEBLOCK
 AND SIGNATURE ARE ON THE PLAN YET MARKED UP IN MARKER
 AND PENCIL BY THE CONTRACTOR AS HIS OWN PLAN. SEE THE
 WPB AMENDMENT TO THE FBC 107.2.1 AND FL STATE STATUTE
 BELOW:
  
 1) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. FBC, WPB
 AMENDMENTS 107.2.1
  
 2) FL SS 471.025 668.001-668.006.
 ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS, OR
 DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND BEING
 FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS
 PROVIDED TO THE OWNER OR THE OWNER?S REPRESENTATIVE
 SHALL BE SIGNED BY THE LICENSEE, DATED, AND SEALED WITH
 SAID SEAL.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-05 Cont ID  
Sent By sciard Date 2015-02-05 Time 06:39 Rev Time 0.00
Received By sciard Date 2015-02-05 Time 06:39 Sent To  
Notes
2015-02-05 06:46:091. FBC 107.2.1. DRAWINGS TO BEAR SIGNATURE FOR PERSON
 RESPONSIBLE FOR DESIGN.
 2. FBC 107.3.5.3. CIRCUITS TO BE SHOWN ON FLOOR PLAN
 FOR ADDITION OF EMERGENCY LIGHTS AND EXIT SIGNS.
 3. N.E.C. 700.12(F).THE BRANCH CIRCUIT FEEDING THE
 EMERGENCY LIGHTS(UNIT EQUIPMENT) SHALL BE THE SAME
 BRANCH CIRCUIT AS THAT SERVING THE NORMAL LIGHTING IN
 THE AREA .

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-12-16 Cont ID  
Sent By pleduc Date 2015-12-16 Time   Rev Time 0.00
Received By pleduc Date 2015-12-16 Time 13:40 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-03-25 Cont ID  
Sent By pleduc Date 2015-03-25 Time   Rev Time 0.00
Received By pleduc Date 2015-03-25 Time 15:56 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-02-05 Cont ID  
Sent By pleduc Date 2015-02-05 Time   Rev Time 0.00
Received By pleduc Date 2015-02-05 Time 12:31 Sent To PC
Notes
2015-02-05 12:35:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENT:
  
 PLEASE ADDRESS ELECTRICAL COMMENTS AND RESUBMIT.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-12-22 Cont ID  
Sent By cpuell Date 2015-12-22 Time 09:11 Rev Time 0.00
Received By cpuell Date 2015-12-14 Time 10:44 Sent To  
Notes
2015-12-15 10:44:47RESUB ROUTED TO FIRE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-12-15 Cont ID  
Sent By dahayes Date 2015-06-02 Time 10:44 Rev Time 0.00
Received By lmarchan Date 2015-05-21 Time   Sent To E
Notes
2015-05-21 07:27:59ON D.HAYES DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-26 Cont ID  
Sent By Fire Date 2015-03-26 Time   Rev Time 0.00
Received By   Date 2015-03-23 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-05 Cont ID  
Sent By sciard Date 2015-02-05 Time 06:39 Rev Time 0.00
Received By sciard Date 2015-01-21 Time 12:06 Sent To  
Notes
2015-01-21 12:06:43ROUTED TO ELECTRICAL $5000 & UNDER