Plan Review Details - Permit 15010690
Plan Review Stops For Permit 15010690
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-06-29 Cont ID  
Sent By aclange Date 2015-06-29 Time 15:51 Rev Time 0.00
Received By aclange Date 2015-06-29 Time 15:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-05-13 Cont ID  
Sent By shill Date 2015-05-13 Time 09:33 Rev Time 0.00
Received By shill Date 2015-05-11 Time 13:06 Sent To  
Notes
2015-05-13 09:25:43****CORRECTIONS****
 ****REVISED 6/1/15****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM FIRST LIST:
  
 1. OK
  
 2. REVISE APPLICATION DESCRIPTION TO INDICATE LOCATION
 OF PROPOSED IMPROVEMENT, FBC 107. OR, PROVIDE A PLAN.
 THIS INFORMATION SHOULD BE EASILY DISCERNED, NOT IN THE
 MIDDLE OF A SPECIFICATION.
  
 2ND REVIEW - MORE WORK IS INCLUDED IN THE CONTRACT THAN
 WHAT IS INCLUDED IN THIS PERMIT APPLICATION. EITHER
 REVISE THE PERMIT APPLICATION TO INCLUDE ENTIRE SCOPE
 OR PROVIDE INFORMATION AS TO WHEN THE ADDITIONAL WORK
 WILL BE APPLIED FOR.
  
 3. OK
  
 4. NO INFORMATION REGARDING CHANGE IN ELEVATION
 DIFFERENCES, AND HOW THIS IMPROVEMENT WILL AFFECT MEANS
 OF EGRESS AND ACCESSIBILITY AND/OR FAIR HOUSING AS
 APPLICABLE, FBC 2010 BUILDING CHAPTER 10, FBC 2010
 ACCESSIBILITY.
  
 PROVIDE AN ARCHITECTURAL PLAN WHICH SHOWS ELEVATION
 DIFFERENCES, ALL DOORS WHICH ACCESS THIS BALCONY.
 INCLUDE THE OCCUPANCY CLASSIFICATION. CONFIRM (ON THE
 PLAN, NOT IN A LETTER) THAT THIS BALCONY SERVES ONLY
 ONE RESIDENTIAL UNIT, IF THIS IS THE CASE.
  
 2ND REVIEW, NOT ADDRESSED. THIS PERMIT WILL BE ISSUED
 WITH PROVISO THAT THERE WILL BE NO CHANGE IN ELEVATION
 (NO ADDITIONAL INFORMATION REQUIRED).
  
 5-6. OK
  
 NEW COMMENT:
  
 A RESIDENT INSPECTOR WILL BE REQUIRED FOR THIS JOB, FBC
 110.3.9. A RESIDENT INSPECTOR PACKAGE HAS BEEN EMAILED
 DIRECTLY TO THE CONTRACTOR.
  
 PLEASE PROVIDE A RESUME FOR THE CONTRACTOR AND PROPOSED
 RESIDENT INSPECTOR (USUALLY THE ENGINEER PROVIDING THE
 SPECIFICATION).
  
 6/1; PER KEN CONRAD, A PDF SIGNATURE IS ACCEPTABLE
 (ORIGINAL NOT REQUIRED DUE TO SCOPE AND THIS IS A
 RESIDENT INSPECTOR, NOT SPECIAL INSPECTOR).
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-01-23 Cont ID  
Sent By shill Date 2015-01-23 Time 08:58 Rev Time 0.00
Received By shill Date 2015-01-23 Time 08:58 Sent To  
Notes
2015-01-23 09:13:15****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. ENGINEERING REQUIRED, FS 471.
  
 2. REVISE APPLICATION DESCRIPTION TO INDICATE LOCATION
 OF PROPOSED IMPROVEMENT, FBC 107. OR, PROVIDE A PLAN.
 THIS INFORMATION SHOULD BE EASILY DISCERNED, NOT IN THE
 MIDDLE OF A SPECIFICATION.
  
 3. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB, FBC
 109.
  
 4. NO INFORMATION REGARDING CHANGE IN ELEVATION
 DIFFERENCES, AND HOW THIS IMPROVEMENT WILL AFFECT MEANS
 OF EGRESS AND ACCESSIBILITY AND/OR FAIR HOUSING AS
 APPLICABLE, FBC 2010 BUILDING CHAPTER 10, FBC 2010
 ACCESSIBILITY.
  
 PROVIDE AN ARCHITECTURAL PLAN WHICH SHOWS ELEVATION
 DIFFERENCES, ALL DOORS WHICH ACCESS THIS BALCONY.
 INCLUDE THE OCCUPANCY CLASSIFICATION. CONFIRM (ON THE
 PLAN, NOT IN A LETTER) THAT THIS BALCONY SERVES ONLY
 ONE RESIDENTIAL UNIT, IF THIS IS THE CASE.
  
 5. SCOPE NOT CLEAR, FBC 107. APPLICATION INCLUDES
 REMOVAL OF TILE AND WATERPROOFING, BUT DOES NOT INCLUDE
 INSTALLATION OF A FLOOR FINISH. PLEASE CLARIFY.
  
 6. PROVIDE A PLAN WHICH SHOWS WHAT IS UNDERNEATH THIS
 BALCONY, FBC 1207.2, FBC 1207.3.
  
  
 NOT ENOUGH INFORMATION SUBMITTED TO PROVIDE A COMPLETE
 CHECKLIST.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-06-29 Cont ID  
Sent By shill Date 2015-06-29 Time 15:50 Rev Time 0.00
Received By aclange Date 2015-06-23 Time   Sent To B
Notes
2015-06-24 12:12:25SENT TO S. HILL'S RE-SUB BOX ON HER DESK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-13 Cont ID  
Sent By shill Date 2015-05-13 Time 09:33 Rev Time 0.00
Received By shill Date 2015-04-29 Time 11:16 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-23 Cont ID  
Sent By shill Date 2015-01-23 Time 09:22 Rev Time 0.00
Received By shill Date 2015-01-23 Time 09:22 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status P Date 2015-06-30 Cont ID  
Sent By aclange Date 2015-06-30 Time 16:01 Rev Time 0.00
Received By aclange Date 2015-06-30 Time 16:01 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2015-06-01 Cont ID  
Sent By shill Date 2015-06-01 Time 09:04 Rev Time 0.00
Received By shill Date 2015-06-01 Time 09:04 Sent To  
Notes
2015-06-01 09:05:03SEE BUILDING COMMENTS
  