Plan Review Details - Permit 15010622
Plan Review Stops For Permit 15010622
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-03-10 Cont ID  
Sent By rmcdouga Date 2015-03-10 Time 12:19 Rev Time 0.00
Received By rmcdouga Date 2015-03-10 Time 10:15 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-02-10 Cont ID  
Sent By rmcdouga Date 2015-02-10 Time 18:01 Rev Time 0.00
Received By rmcdouga Date 2015-02-10 Time 18:01 Sent To  
Notes
2015-02-10 11:46:17PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE 3/4" CONDUIT SHOWN ON THE REVISED ELECTRICAL
 RISER DIAGRAM BETWEEN THE EXISTING 200 AMP PANEL AND
 THE NEW 150 AMP SUB-PANEL IS TOO SMALL FOR THE 150 AMP
 SUB-PANEL. NEC 310.15
  
 2) SPECIFY THE WIRE SIZES AND NUMBER OF FEEDERS AND
 CONDUIT TYPE AND SIZE FOR THE 150 AMP PANEL. NEC 310.15
  
 3) SPECIFY THE TYPE OF CONDUIT THAT IS INSTALLED (IE.
 RIGID METAL CONDUIT (RMC), RIGID PVC, EMT, ETC.) FBC
 107.2.1 NOTE IF PVC CONDUIT IS AN EQUIPMENT GROUNDING
 CONDUCTOR IS REQUIRED. NEC 250.118
  
 4) PROVIDE A PANEL SCHEDULE AND LOAD CALCULATIONS FOR
 BOTH PANELS ON THE REVISED ELECTRICAL PLANS. NEC 220.40
 & FBC 107.3.5.3
  
 5) SHOW THAT THE FEEDERS FOM THE 200AMP PANEL TO THE
 150 AMP SUB-PANEL HAVE OVERCURRENT PROTECTION. NEC
 240.4
  
 6) THE INTERSYSTEM BONDING IS NOT DRAWN CORRECTLY. THE
 DIAGRAM APPEARS TO SHOW #6 MIN EQUIPMENT GROUNDS FROM
 THE MAIN DISCONNECT, 200 AMP PANEL AND 150 AMP
 SUB-PANEL TIED TO THE INTERSYSTEM BONDING. THE
 EQUIPMENT GROUND WIRE IS REQUIRED IF PVC CONDUIT IS
 USED, IT IS NOT REQUIRED FOR METAL CONDUIT. THE
 INTERSYSTEM BONDING IS REQUIRED FOR BONDING "LIMITED
 ENERGY" SYSTEMS SUCH AS COMMUNICATIONS, RADIO,
 TELEPHONE, TV AND CATV CIRCUITS TOGETHER TO THE SERVICE
 GROUNDING AND BONDING SYSTEM. NEC 250.94
  
 7) THERE SHOULD NOT BE A #6 EQUIPMENT GROUND WIRE
 BETWEEN THE METER CAN AND THE MAIN DISCONNECT. NEC
 250.110
  
 8) THE ADDRESS SHOULD BE 2015 BRADLEY CT. AND NOT 2015
 BRADLEY CY. FBC 107.2.1
  
 9) THE REVISED ELECTRICAL RISER DIAGRAM SPECIFIES A #2
 CU GROUNDING ELECTRODE CONDUCTOR. PLEASE VERIFY THAT
 THIS IS ACCURATE. FBC 107.2.1

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-01-26 Cont ID  
Sent By rmcdouga Date 2015-01-26 Time 07:28 Rev Time 0.00
Received By rmcdouga Date 2015-01-26 Time 08:57 Sent To  
Notes
2015-01-26 07:30:38PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. THE APPROVED
 ELECTRICAL PLANS WERE SIGNED AND SEALED BY A FLORIDA
 LICENSED ENGINEER, DANIEL J. MOSS. ANY REVISIONS TO THE
 DRAWINGS ARE REQUIRED TO BE SIGNED AND SEALED BY THE
 ENGINEER. FLORIDA STATUTES 471
  
 2) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL
 BE PROVIDED.
  
 3) NEC 230.70 - MEANS SHALL BE PROVIDED TO DISCONNECT
 ALL CONDUCTORS IN A BUILDING OR OTHER STRUCTURE FROM
 THE SERVICE ENTRANCE CONDUCTORS.
  
 4) FBC 107.1.2 PLEASE CLARIFY THE SIZE OF THE
 CONDUCTORS AT THE WEATHER HEAD. THE DRAWING HAS 3-1#1
 C.U. DID YOU MEAN 3-#1/0 CU OR 3-#1 CU ?
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jgomez Date 2015-02-24 Time 12:43 Sent To  
Notes
2015-02-25 12:44:09ELECTRICAL REVISION RE-SUBMITTAL SENT TO ROBERT
 MCDOUGAL FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-10 Cont ID  
Sent By rmcdouga Date 2015-02-10 Time 18:01 Rev Time 0.00
Received By rmcdouga Date 2015-02-03 Time 11:48 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-26 Cont ID  
Sent By rmcdouga Date 2015-01-26 Time 07:28 Rev Time 0.00
Received By rmcdouga Date 2015-01-20 Time 08:57 Sent To E
Notes
***NONE***