Plan Review Details - Permit 15010559
Plan Review Stops For Permit 15010559
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2015-02-03 Cont ID  
Sent By skennedy Date 2015-02-03 Time 18:18 Rev Time 0.00
Received By skennedy Date 2015-02-03 Time 18:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-02-03 Cont ID  
Sent By skennedy Date 2015-02-03 Time 18:18 Rev Time 0.00
Received By skennedy Date 2015-02-03 Time 18:18 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2015-02-03 Cont ID  
Sent By skennedy Date 2015-02-03 Time 18:20 Rev Time 0.00
Received By skennedy Date 2015-02-03 Time 18:20 Sent To  
Notes
2015-02-03 18:30:481ST REVIEW: FBC 2010
  
 THERE ARE TWO SEPARATE DESIGNERS FOR TWO GAS PIPING
 DESIGNS ON THS PROJECT. ONE IS APPROVED UNDER PERMIT
 NUMBER 14100267. THE DESIGN SHOWN IN THIS REVISION WAS
 NOT REVIEWED UNDER THE ORIGINAL REVIEW FOR PRIMARY
 PERMIT 13080346. AS A SEPARATE GAS PERMIT EXISTS AND
 INSPECTIONS HAVE BEEN PERFORMED FOR THAT DESIGN, PLEASE
 REMOVE THE GAS DESIGN FROM THIS PAGE, OR OTHERWISE
 RESOLVE THE CONFLICT.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2015-07-30 Cont ID  
Sent By shill Date 2015-07-30 Time 11:00 Rev Time 0.00
Received By shill Date 2015-07-30 Time 11:00 Sent To  
Notes
2015-07-30 11:01:06NO HISTORIC REVIEW REQUIRED FOR THIS REVISION PER FM
 (INTERIOR RENOV, FLOOD VENTS)
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-30 Cont ID  
Sent By shill Date 2015-07-30 Time 11:01 Rev Time 0.00
Received By shill Date 2015-07-30 Time 11:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-30 Cont ID  
Sent By shill Date 2015-03-30 Time 17:44 Rev Time 0.00
Received By shill Date 2015-03-09 Time   Sent To  
Notes
2015-03-09 17:45:36SENT TO S. HILL'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-03 Cont ID  
Sent By skennedy Date 2015-02-03 Time 18:36 Rev Time 0.00
Received By skennedy Date 2015-01-28 Time 16:50 Sent To  
Notes
2015-01-28 16:53:51TO SAK DESK
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status P Date 2015-07-30 Cont ID  
Sent By shill Date 2015-07-30 Time 10:16 Rev Time 0.00
Received By shill Date 2015-07-30 Time 10:16 Sent To  
Notes
2015-07-30 10:16:48PROVISO
 COMPLIANT FINISHED CONSTRUCTION ELEVATION CERTIFICATE
 REQUIRED
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2015-03-30 Cont ID  
Sent By shill Date 2015-03-30 Time 16:45 Rev Time 0.00
Received By shill Date 2015-03-30 Time 16:45 Sent To  
Notes
2015-03-30 16:58:19****CORRECTIONS****
 EDITED ON 3/31/2015
  
 CONTRACTOR PROVIDED A HARD COPY OF THE "BUILDING UNDER
 CONSTRUCTION" ELEVATION CERTIFICATE PREVIOUSLY SENT VIA
 EMAIL
 ISSUE WAS DISCUSSED AT LENGTH ON THE TELEPHONE WITH
 CONTRACTOR
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 CORRECTIONS FOR ELEVATION CERTIFICATE (JOB #14-08-011)
 DATED 1/29/2015 PREPARED BY ERNEST W. DUNCAN, BASELINE
 ENGINEERING & LAND SURVEYING, "BUILDING UNDER
 CONSTRUCTION":
  
 1. A1, OWNER IS SHOWN AS "KELLY RESIDENCE" BUT THE
 OWNERS OF RECORD ARE DONALD FROUDE AND KIMBERLY FROUDE.
 PLEASE CORRELATE.
  
 2. A5, LAT/LONG TO BE PROVIDED TO 1 DECIMAL PLACE OR
 BETTER WHEN USING DEGRESS, MINUTES SECONDS FORMAT. ALSO
 PLEASE CONFIRM THE COORDINATES; THIS TO BE THE CENTER
 FRONT OF THE BUILDING AND ACCURATE WITHIN 66 FEET. THE
 COORDINATES APPEAR TO BE LOCATED IN THE ADJACENT PARCEL
 (OVER 66' AWAY).
  
 3. ADVISORY ONLY; COLOR PHOTOGRAPHS WILL BE REQUIRED
 FOR THE "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE.
 PHOTOGRAPHS OF THE INSTALLED FLOOD VENTS, IF INSTALLED,
 WILL ALSO BE REQUIRED. IF ENGINEERED FLOOD VENTS ARE
 INSTALLED, THE ENGINEERING OR PRODUCT APPROVAL IS TO BE
 INCLUDED WITH THE ELEVATION CERTIFICATE.
  
 4. ITEM A9; SEE SHEETS A2.0 (DEMO PLAN) AND A3.0, ROOM
 105 IS SHOWN AS A "GREAT ROOM" BUT APPEARS TO BE A
 GARAGE (SEE A5.0, NORTH ELEVATION). ELEVATION
 CERTIFICATE SHOWS GARAGE AS 400 SF, PAPA RECORDS SHOW
 THE GARAGE AS 440 SF. PLEASE RECONCILE THE
 DISCREPANCIES.
  
 5. A9, NO FLOOD VENTS INDICATED, BUT ITEM C2D SHOWS THE
 GARAGE AT 7.0 FEET. SEE CITY OF WEST PALM BEACH
 MUNICIPAL CODE 94-546(B), A 6INCH FREEBOARD REQUIRED
 FOR ALL NEW CONSTRUCTION AND SUBSTANTIAL IMPROVEMENTS.
 THIS CAN BE VIEWED AT WWW.MUNICODE.COM.
  
 SEE FBC 2010 EXISTING BUILDING 601.3: FLOOD HAZARD
 AREAS. IN FLOOD HAZARD AREAS, ALTERATIONS THAT
 CONSTITUTE SUBSTANTIAL IMPROVEMENT SHALL REQUIRE THAT
 THE BUILDING COMPLY WITH SECTION 1612 OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 FBC 2010 EXISTING BUILDING 1003.5 FOR ADDITIONAL
 REQUIREMENTS.
  
 SEE FBC 1612, SUBSTANTIAL IMPROVEMENT.
  
 OPTIONS FOR GARAGE ARE TO RAISE TO 7.5' OR TO INSTALL
 FLOOD VENTS WHICH WILL ALLOW THE WATER TO ENTER AND
 EXIT.
  
 ISO HAS PROVIDED INITIAL CLARIFICATION ON THIS ISSUE.
 PLEASE BE ADVISED THAT THE BUILDING OFFICIAL HAS
 REQUESTED FURTHER CLARIFICATION ON 3/30/15 WHICH MAY
 AFFECT YOUR PROJECT. THIS COMMENT LIST WILL BE REVISED
 BASED ON ISO'S CONVERSATION WITH THE BUILDING OFFICIAL
 IF NEW INFORMATION OR GUIDANCE AFFECTS YOUR PROJECT.
  
 6. C2B IS NA FOR NEXT HIGHER FLOOR; PERMIT DOCUMENTS
 (SEE SHEET A4.0) SHOW AN "EXISTING SECOND FLOOR."
  
 7. C2E SHOWS THE LOWEST MACHINERY/EQUIPMENT AS 6.80;
 THIS IS ALSO REQUIRED TO BE A MINIMUM OF 7.5'.
  
 8. SECTION D, LATITUDE / LONGITUDE PROVIDED BY A
 SURVEYOR, THE "NO" BOX IS CHECKED. AS FLORIDA STATUTE
 ONLY ALLOWS SURVEYORS TO PREPARE ELEVATION CERTIFICATES
 (AND NOT ARCHITECTS / ENGINEERS AS PERMITTED IN OTHER
 STATES), THIS BOX SHOULD ALWAYS BE "YES". IT IS
 UNDERSTOOD THAT THE SURVEYOR RELIES ON OTHER ENTITIES
 FOR THIS DATA - TYPICAL SOURCES ARE GOOGLE EARTH (WHICH
 SURVEYOR USED FOR THIS ELEVATION CERTIFICATE),
 LABINS.ORG, PALM BEACH COUNTY GIS, ETC.
  
 9. SECTION D, DESCRIBE EQUIPMENT FROM C2E.
  
 10. SECTION D, COMMENT STATES THAT THIS "BUILDING IS A
 CABANA." IT IS NOT CLEAR WHICH STRUCTURE THIS ELEVATION
 CERTIFICATE REPRESENTS; PLEASE PROVIDE CLARIFICATION.
 CABANA APPEARS TOO SMALL TO HAVE A GARAGE. AN ELEVATION
 CERTIFICATE IS REQUIRED FOR THE HOUSE. IF THIS
 ELEVATION CERTIFICATE IS FOR BOTH STRUCTURES, PROVIDE
 CLARIFICATION IN THE DESCRIPTION AND THE COMMENTS.
  
  
  
  
  
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2015-01-29 Cont ID  
Sent By shill Date 2015-01-29 Time 16:53 Rev Time 0.00
Received By shill Date 2015-01-29 Time 16:53 Sent To  
Notes
2015-01-29 16:55:53****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 AS DISCUSSED, PLEASE PROVIDE A "BUILDING UNDER
 CONSTRUCTION" ELEVATION CERTIFICATE FOR THIS
 SUBSTANTIAL IMPROVEMENT, FBC 2010 RESIDENTIAL 322, CITY
 OF WEST PALM BEACH MUNICIPAL CODE 94.
  
 THIS MAY BE SENT FOR PRELIMINARY REVIEW VIA EMAIL.
  
 THIS PROPERTY, ALTHOUGH IN A HISTORIC DISTRICT, IS NOT
 CONTRIBUTING. MECHANICAL EQUIPMENT AND ANY OTHER
 EQUIPMENT SERVICING THE BUILDING IS TO BE ELEVATED TO
 7.5', GARAGE IS TO BE ELEVATED TO 7.5' OR FLOOD VENTS
 INSTALLED (AND FLOOD RESISTANT MATERIALS ONLY BELOW
 7.5').
  
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-02-03 Cont ID  
Sent By skennedy Date 2015-02-03 Time 18:19 Rev Time 0.00
Received By skennedy Date 2015-02-03 Time 18:19 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-01-28 Cont ID  
Sent By fmittner Date 2015-01-28 Time 10:17 Rev Time 0.00
Received By fmittner Date 2015-01-28 Time 10:17 Sent To B
Notes
***NONE***