Plan Review Details - Permit 15010449
Plan Review Stops For Permit 15010449
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-02-14 Cont ID  
Sent By rmcdouga Date 2015-02-14 Time 10:09 Rev Time 0.00
Received By rmcdouga Date 2015-02-14 Time 09:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-04 Cont ID  
Sent By rmcdouga Date 2015-02-04 Time 18:18 Rev Time 0.00
Received By rmcdouga Date 2015-02-04 Time 07:17 Sent To  
Notes
2015-02-05 08:26:28PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHEET S-2.0 SHOWS THAT THE ATTIC WILL BE USED
 STORAGE. FBC-R301.5 REQUIRES A 20 PSF LIVE LOAD FOR THE
 BOTTOM CORD OF TRUSSES USED FOR LIMITED STORAGE.
  
 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. (1) SUBMIT THE INSTALLATION
 INSTRUCTIONS FOR SIMPSON HETAL 12 CONNECTOR. (2) NOA
 NO. 12-0209.13 THAT WAS SUBMITTED FOR THE 8" CAST -
 CRETE LINTELS WAS SUPERSEDED ON 10/9/2014 BY NOA NO.
 14-0903.02. SUBMIT THE CURRENT ONE.
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-02-14 Cont ID  
Sent By rmcdouga Date 2015-02-14 Time 11:16 Rev Time 0.00
Received By rmcdouga Date 2015-02-14 Time 09:57 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-05 Cont ID  
Sent By rmcdouga Date 2015-02-05 Time 08:06 Rev Time 0.00
Received By rmcdouga Date 2015-02-05 Time 06:50 Sent To  
Notes
2015-02-05 10:35:01PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRIC
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NEC 110.9 - SPECIFY THE A.I.C. RATING OF THE
 ELECTRICAL SERVICE EQUIPMENT ON THE PLANS.
  
 2) NEC 210.11 (C) (3) AT LEAST ONE 20 - AMP BRANCH
 CIRCUIT SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLETS.
  
 3) NEC 250.94 - INTERSYSTEM BONDING TERMINATION SHALL
 BE PROVIDED.
  
 4) NEC 250.104(B) THE GAS PIPING IS REQUIRED TO BE
 BONDED.
  
 5) NEC 210.52 (B) IN THE KITCHEN, PANTRY, BREAKFAST
 ROOM, DINING ROOM, OR SIMILAR AREA OF A DWELLING UNIT,
 THE TWO OR MORE 20 - AMPERE BRANCH CIRCUITS REQUIRED BY
 210.11 (C)(1) SHALL SERVE ALL WALL AND FLOOR RECEPTACLE
 OUTLETS COVERED BY 210.52(C), AND RECEPTACLE OUTLETS
 FOR REFRIGERATION EQUIPMENT. SEE EXCEPTIONS FOR
 SWITCHED RECEPTACLES AND REFRIGERATION SUPPLIED BY AN
 INDIVIDUAL BRANCH CIRCUIT.
  
 6) FBC 107.2.1 SPECIFY THE CIRCUITS NUMBERS ON THE
 ELECTRICAL FLOOR PLAN IN COORDINATION WITH THE PANEL
 SCHEDULE.
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-02-17 Cont ID  
Sent By tklarge Date 2015-02-17 Time 07:02 Rev Time 0.00
Received By tklarge Date 2015-02-17 Time 07:00 Sent To  
Notes
2015-02-17 07:01:50PROVISO: SUBMIT 2 COPIES OF CODE COMPLIANT GAS RISER
 DIAGRAM FOR REVIEW AND APPROVAL PRIOR TO ROUGH GAS
 INSPECTION.

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2015-01-24 Cont ID  
Sent By tklarge Date 2015-01-24 Time 12:13 Rev Time 0.00
Received By tklarge Date 2015-01-24 Time 12:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-17 Cont ID  
Sent By tklarge Date 2015-02-17 Time 07:03 Rev Time 0.00
Received By tklarge Date 2015-02-10 Time 09:45 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-05 Cont ID  
Sent By rmcdouga Date 2015-02-05 Time 11:45 Rev Time  
Received By rmcdouga Date 2015-01-15 Time   Sent To  
Notes
2015-01-15 16:46:21SENT TO R01.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2015-02-04 Cont ID  
Sent By rmcdouga Date 2015-02-04 Time 07:20 Rev Time 0.00
Received By rmcdouga Date 2015-02-04 Time 07:18 Sent To  
Notes
2015-02-04 07:20:08MU2015-711, NO FEES WERE DUE.

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2015-02-05 Cont ID  
Sent By rmcdouga Date 2015-02-05 Time 08:27 Rev Time 0.00
Received By rmcdouga Date 2015-02-05 Time 08:26 Sent To  
Notes
2015-02-05 08:53:39LANDSCAPE PLAN IS OK PER S. GRAHAM. A SEPARATE
 LANDSCAPE SUB-PERMIT IS REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-02-14 Cont ID  
Sent By rmcdouga Date 2015-02-14 Time 09:57 Rev Time 0.00
Received By rmcdouga Date 2015-02-14 Time 09:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-02-05 Cont ID  
Sent By rmcdouga Date 2015-02-05 Time 07:42 Rev Time 0.00
Received By rmcdouga Date 2015-02-04 Time 18:18 Sent To  
Notes
2015-02-05 08:06:11PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBCR-M1602.2 OUTDOOR AND RETURN AIR FOR A FORCED-AIR
 HEATING OR COOLING SYSTEM SHALL NOT BE TAKEN FROM THE
 FOLLOWING LOCATIONS: 4. A CLOSET, BATHROOM, TOILET
 ROOM, KITCHEN, GARAGE, MECHANICAL ROOM, BOILER ROOM,
 FURNACE ROOM, UNCONDITIONED ATTIC OR OTHER DWELLING
 UNIT. RETURN CAN NOT BE IN THE KITCHEN WALL.
  
 2) FBCR- M1602.4 RESTRICTED RETURN AIR OCCURS IN
 BUILDINGS WHEN RETURNS ARE LOCATED IN CENTRAL ZONES AND
 CLOSED INTERIOR DOORS IMPEDE AIR FLOW TO THE RETURN
 GRILL OR WHEN CEILING SPACES ARE USED AS RETURN PLENUMS
 AND FIRE WALLS RESTRICT AIR MOVEMENT FROM ONE PORTION
 OF THE RETURN PLENUM TO ANOTHER. PROVISIONS SHALL BE
 MADE IN BOTH RESIDENTIAL AND COMMERCIAL BUILDINGS TO
 AVOID UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS
 CAUSED BY RESTRICTED RETURN AIR. EXCEPTIONS:
 1. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER 1-1/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR
 SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCH UNDERCUT TO ACHIEVE PROPER RETURN
 AIR BALANCE.
 2. TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1 INCH UNDERCUTTING OF DOORS TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 3. HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE
 REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS,
 EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL
 BE INCLUDED.
 THE TRANSFER GRILLES ARE TOO SMALL IN THE MASTER
 BEDROOM (250 CFM = 125 SQIN OF GRILL AREA) , BEDROOM 2
 (140 CFM = 70 SQIN OF GRILL AREA) AND BEDROOM 4 (125
 CFM = 62.5 SQIN OF GRILL AREA).
  
 4) THERE IS WHAT APPEARS TO BE A RETURN WITH 20 CFM
 SHOWN IN THE HALLWAY IN FRONT OF THE LINEN CLOSEST.
 PLEASE CLARIFY. FBC 107.2.1

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-02-17 Cont ID  
Sent By tklarge Date 2015-02-17 Time 07:02 Rev Time 0.00
Received By tklarge Date 2015-02-17 Time 06:35 Sent To  
Notes
2015-02-17 07:00:14PROVISO: SUBMIT 2 COPIES OF CODE COMPLIANT SANITARY
 RISER DIAGRAM FOR REVIEW AND APPROVAL PRIOR TO ROUGH
 PLUMBING INSPECTION.

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-01-24 Cont ID  
Sent By tklarge Date 2015-01-24 Time 12:13 Rev Time 0.00
Received By tklarge Date 2015-01-24 Time 11:44 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2015-02-14 Cont ID  
Sent By rmcdouga Date 2015-02-14 Time 11:19 Rev Time 0.00
Received By rmcdouga Date 2015-02-14 Time 11:19 Sent To  
Notes
2015-02-14 11:21:04OWENS CORNING ASPHALT SINGLES NOA NO.12-0309.01
 LOMANCO ROOF VENTS NOA NO. 13-0820.08

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By sgraham Date 2015-01-21 Time   Rev Time  
Received By   Date 2015-01-21 Time   Sent To  
Notes
2015-01-21 11:21:14NOTE: SEPARATE PERMIT REQUIRED FOR LANDSCAPING.