Plan Review Details - Permit 15010393
Plan Review Stops For Permit 15010393
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-03-17 Cont ID  
Sent By shill Date 2015-03-17 Time 17:44 Rev Time 0.00
Received By shill Date 2015-03-17 Time 17:44 Sent To P
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-03-09 Cont ID  
Sent By shill Date 2015-03-09 Time 17:35 Rev Time 0.00
Received By shill Date 2015-03-09 Time 17:35 Sent To P
Notes
2015-03-09 17:36:02****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. DESIGNER OF RECORD TO INCORPORATE THE NEW SCOPE OF
 WORK (DEMOLITION OF SHOWER BUILT WITHOUT PERMIT) INTO
 THE PLAN, FS 471.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-02-17 Cont ID  
Sent By shill Date 2015-02-17 Time 08:06 Rev Time 0.00
Received By shill Date 2015-02-17 Time 08:00 Sent To  
Notes
2015-02-17 08:04:12****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 1-2. OK
  
 3. A CERTIFIED APPRAISAL WAS PROVIDED IN ORDER TO
 DEMONSTRATE THAT THIS IS NOT A "SUBSTANTIAL
 IMPROVEMENT." REVISE PLAN TO INCORPORATE THE BATHROOM
 INSTALLED WITHOUT PERMIT; EITHER REVISE PLAN TO INCLUDE
 OR REVISE PLAN TO INCLUDE DEMOLITION. PROVIDE A COPY OF
 THE CERTIFIED APPRAISAL AT TIME OF RESUBMITTAL FOR THE
 FILE.
  
 4. OK
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-01-20 Cont ID  
Sent By shill Date 2015-01-20 Time 11:01 Rev Time 0.00
Received By shill Date 2015-01-20 Time 11:01 Sent To  
Notes
2015-01-20 11:16:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 107, PLANS APPEAR TO BE REDUCED FROM FULL SIZE
 SHEETS. FONT IS SMALL, DETAILS DO NOT APPEAR TO MEET
 THE MINIMUM SCALE FOR PLANS. PROVIDE FULL SIZE DETAILS.
  
 2. SHEET S1, FBC 107, CLOUD ALL CHANGES SO IT IS
 APPARENT WHAT HAS BEEN REVISED. IF THIS SHEET HAS NOT
 BEEN REVISED, IT IS NOT NECESSARY TO SUBMIT.
  
 3. THIS PERMIT WAS ISSUED WITH PROVISO. A SEPARATE
 MECHANICAL PERMIT IS REQUIRED, AND FLOOD VENT PRODUCT
 APPROVALS ARE REQUIRED, AND A NEW ELEVATION CERTIFICATE
 IS REQUIRED. PLEASE SEE PROVISO AND ADDRESS AT THIS
 TIME. FOR YOUR CONVENIENCE, THE PROVISO ITEMS ARE
 BELOW.
  
 4. WHEN RESUBMITTING, REVISION FORM IS TO INCLUDE THE
 JOB ADDRESS, FBC 107. THIS HELPS OUR OFFICE LOCATE
 PLANS WHEN NEEDED. ANOTHER ADDRESS (2101 VISTA PARKWAY)
 WAS WRITTEN ON THE REVISION FORM.
  
 -------------------------------------------------------
 --------------------------------------
 ****PROVISO****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 TARGET SURVEYING JOB #165993
  
 ELEVATION CERTIFICATE PROVIDED SHOWS A GARAGE FLOOR
 ELEVATION OF 6.7', MECHANICAL EQUIPMENT IS AT 6.6'. AS
 THIS IMPROVEMENT CONSTITUTES A SUBSTANTIAL IMPROVEMENT,
 PER CONTRACTOR, FLOOD VENTS WILL BE INSTALLED IN THE
 GARAGE AND THE MECHANICAL EQUIPMENT WILL BE RAISED TO
 7.5'.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE WILL BE
 REQUIRED PRIOR TO FINAL INSPECTION. INCORPORATE THE
 FOLLOWING CORRECTIONS INTO THE ELEVATION CERTIFICATE:
  
 A1, INCLUDE OWNER'S NAME
  
 A8, FLOOD VENTS ARE TO BE INSTALLED. IF THEY ARE
 ENGINEERED FLOOD VENTS, INCLUDE THE PRODUCT APPROVAL AS
 WELL AS A PHOTOGRAPH OF THE INSTALLED VENTS.
  
 A9, CONFIRM GARAGE SQUARE FOOT AREA AS FLOOD VENTS ARE
 PROPOSED.
  
 B1, INCLUDE COMMUNITY NAME (CITY OF WEST PALM BEACH).
  
 B4, REVISE, SHOULD BE 120229 0020.
  
 COMMENTS SECTION STATES THAT ACCESS IS UNAVAILABLE TO
 THE GARAGE. AN ACCURATE GARAGE SQUARE FOOT AREA IS
 REQUIRED AFTER FLOOD VENTS ARE INSTALLED.
 COMMENTS SECTION, INCLUDE SOURCE OF LATITUDE/LONGITUDE.
 COMMENT SECTION, DESCRIBE MACHINERY IN C2E.
  
 AN ORIGINAL SIGNED AND SEALED ELEVATION CERTIFICATE
 WILL BE REQUIRED (NO DIGITAL SIGNATURE)
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-03-18 Cont ID  
Sent By tklarge Date 2015-03-18 Time 03:51 Rev Time 0.00
Received By tklarge Date 2015-03-17 Time 17:44 Sent To  
Notes
2015-03-17 17:44:31TO TL DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-03-10 Cont ID  
Sent By tklarge Date 2015-03-10 Time 03:15 Rev Time 0.00
Received By tklarge Date 2015-03-06 Time 18:47 Sent To  
Notes
2015-03-09 17:36:313/9 TO TL DESK
  
2015-03-06 18:47:44REVISION RE-SUBMITTAL SENT TO SAMANTHA HILL FOR REVIEW.
 JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-17 Cont ID  
Sent By shill Date 2015-02-17 Time 08:06 Rev Time 0.00
Received By shill Date 2015-02-03 Time 12:05 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-20 Cont ID  
Sent By shill Date 2015-01-20 Time 11:16 Rev Time 0.00
Received By shill Date 2015-01-14 Time 18:02 Sent To  
Notes
2015-01-14 18:02:17SENT TO S HILL

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-03-18 Cont ID  
Sent By tklarge Date 2015-03-18 Time 03:51 Rev Time 0.00
Received By tklarge Date 2015-03-18 Time 03:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-03-10 Cont ID  
Sent By tklarge Date 2015-03-10 Time 03:15 Rev Time 0.00
Received By tklarge Date 2015-03-10 Time 02:56 Sent To  
Notes
2015-03-10 03:15:221) SUBMIT A PLAN THAT SHOWS THE UNPERMITTED PLUMBING
 FIXTURES THAT ARE GOING TO BE REMOVED. WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 2) SUBMIT DETAILS AS TO HOW AND WHERE THE UNPERMITTED
 PIPING WILL BE REMOVED. THE WATER AND SANITARY LINES
 SHALL BE REMOVED IN THEIR ENTIRETY FROM THE POINT OF
 CONNECTION TO THE EXISTING PLUMBING SYSTEM. WPB AMEND.
 TO 2010 FBC SEC. 105.1, 110.1, 110.6.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  