Plan Review Details - Permit 15010342
Plan Review Stops For Permit 15010342
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-01-29 Cont ID  
Sent By skennedy Date 2015-01-29 Time 15:13 Rev Time 0.00
Received By skennedy Date 2015-01-29 Time 15:13 Sent To FIRE
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-01-30 Cont ID  
Sent By pleduc Date 2015-01-30 Time   Rev Time 0.00
Received By pleduc Date 2015-01-30 Time 10:24 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-01-22 Cont ID  
Sent By pleduc Date 2015-01-22 Time   Rev Time 0.00
Received By pleduc Date 2015-01-22 Time 14:14 Sent To E
Notes
2015-01-22 14:21:05THIS PLAN WAS REVIEWED AND FAILED BY ROY LINDOW. FIRE
 INSPECTOR WITH PETER LEDUC, FIRE MARSHAL, WITH THE
 FOLLOWING COMMENTS:
  
 PROVIDE LOCATIONS OF EXISTING DEVICES TO BE REMOVED.
  
 NOT TO SCALE.
  
 INDICATE IF DEVICES ARE CEILING OR WALL MOUNT.
  
 PLAN CALLS FOR HORN SMOKES. PROVIDE JUSTIFICATION OR
 MAKE CORRECTIONS.
  
 PROVIDE VERIFICATION THAT FIRE ALARM IS CONNECTED TO
 AND PROVIDES NOTIFICATION THROUGHOUT ENTIRE (CONNECTED)
 BUILDINGS.
  
 BATTERY CALCULATIONS SHOW ONLY 5 ADDITIONAL DEVICES AND
 DOES NOT MATCH SUBMITTED DRAWINGS.
  
 PLANETARIUM DOES NOT SHOW NOTIFICATION DEVICES.
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-30 Cont ID  
Sent By pleduc Date 2015-01-30 Time   Rev Time 0.00
Received By pleduc Date 2015-01-13 Time 15:01 Sent To  
Notes
***NONE***