Plan Review Details - Permit 15010285
Plan Review Stops For Permit 15010285
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-04-23 Cont ID  
Sent By jwitmer Date 2015-04-23 Time 12:28 Rev Time 0.00
Received By jwitmer Date 2015-04-23 Time 12:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2015-02-20 Time   Rev Time  
Received By   Date 2015-02-20 Time   Sent To  
Notes
2015-02-24 07:54:51BUILDING PLAN REVIEW
 PERMIT:15010285
 ADD: 8100 IBIS BLVD
 CONT:
 TEL: (
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
  
 IMPORTANT NOTICE: EFFECTIVE MAY 11, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: FRI. FEB. 20/2015
 ACTION: DENIED
  
 1) C-21 SHOWS 96 PARKING SPACES AND ONLY (3) ACCESSIBLE
 SPACES, THE FL ACCESS. CODE TABLE 208.2 75-99 SPACES
 REQUIES (4) ACCESSIBLE SPACES.
  
 2) THE PLANS DO NOT SHOW ACCESSIBLE PARKING DETAILS OF
 SIGNAGE, THE ACCESSIBLE PARKING DETAIL NOR THE CITY
 STANDARD FOR DOUBLE STRIPE LINES W/ DIMENSIONS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2015-05-29 Cont ID  
Sent By cranford Date 2015-05-29 Time 14:42 Rev Time 0.00
Received By cranford Date 2015-05-29 Time 14:42 Sent To  
Notes
2015-05-29 14:42:56ALSO SEE ENGINEERING APPROVAL E15050029

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2015-04-10 Cont ID  
Sent By cranford Date 2015-04-10 Time 08:04 Rev Time 0.00
Received By cranford Date 2015-04-10 Time 08:01 Sent To  
Notes
2015-04-10 08:04:22SAME COMMENTS UNDER 1ST REVIEW. APPLICANT SUBMITTED A
 TWO YEAR OLD EMAIL FROM A FORMER CITY EMPLOYEE
 (REFERENCING A PHASE OF THE PROJECT THAT DID NOT
 REQUIRE A BUILDING PERMIT) TO CONTRADICT THE STAFF'S
 DIRECTION TO OBTAIN AN ENGINEERING DEVELOPMENT
 APPROVAL.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-03-16 Cont ID  
Sent By cranford Date 2015-03-16 Time 10:39 Rev Time 0.00
Received By cranford Date 2015-03-16 Time 10:19 Sent To I
Notes
2015-03-16 10:33:59AS MENTIONED DURING THE PPRC REVIEW, A SEPARATE
 ENGINEERING DEVELOPMENT APPROVAL IS REQUIRED. THE
 ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS CAN
 BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 KELLY CRANFORD, PE
 CITY LAND DEVELOPMENT ENGINEER
 [email protected]
 561-494-1098 (OFFICE)

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-02-26 Cont ID  
Sent By wjolin Date 2015-02-26 Time 13:24 Rev Time 0.00
Received By wjolin Date 2015-02-26 Time 13:22 Sent To  
Notes
2015-02-26 13:22:308100 IBIS BOULEVARD
 PERMIT #15010285
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER SECTION 18.3.4.1 (NFPA 1), FIRE HYDRANTS SHALL BE
 PROVIDED WITH CLEARANCES OF 7'-6" TO THE FRONT AND
 SIDES AND 4'-0" TO THE BACKSIDE OF THE STEAMER CAP.
  
 PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT
 ACCESS ROADS SHALL HAVE A SURFACE DESIGNED TO
 ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 32 TONS.
 ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF NOT
 LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL
 CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES.
  
 PER SECTION 18.2.3.5.3 (NFPA 1), FIRE LANES SHALL BE
 MARKED WITH FREESTANDING SIGNS READING, "FIRE LANE - NO
 PARKING BY ORDER OF THE FIRE DEPARTMENT." SIGNS SHALL
 BE 12" X 18" WITH A WHITE BACKGROUND AND RED LETTERS
 AND SHALL BE A MAXIMUM OF SEVEN FEET IN HEIGHT TO THE
 BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN SIGHT OF THE
 TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 FEET APART.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-23 Cont ID  
Sent By   Date 2015-04-23 Time   Rev Time 0.00
Received By lmarchan Date 2015-04-06 Time 14:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-16 Cont ID  
Sent By cpuell Date 2015-03-16 Time 13:12 Rev Time 0.00
Received By cpuell Date 2015-01-28 Time 17:56 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-08-01 Cont ID  
Sent By skennedy Date 2015-08-01 Time 14:08 Rev Time 0.00
Received By skennedy Date 2015-07-24 Time 16:18 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-03-06 Cont ID  
Sent By avann Date 2015-03-06 Time 14:07 Rev Time 0.00
Received By ajones Date 2015-03-06 Time 14:07 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved