| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| GENERAL: ALL AREAS OPEN TO THE PUBLIC OR OCCUPIED BY |
| WORKERS WITH HEARING CHALLENGES SHALL PROVIDE FIRE |
| ALARM VISUAL NOTIFICATION AND IS SUBJECT TO INSPECTOR'S |
| FIELD VERIFICATION. |
| |
| SHEET FA-002: MISSING SYMBOL FOR MANUAL PULL STATION. |
| |
| SHEET FA-100: MISSING NOTIFICATION APPLIANCE IN POOL |
| EQUIPMENT ROOM (NOT SHOWN ON PLAN) AND UNIFORM ISSUE |
| #B010. |
| |
| SHEET FA-100: COULD NOT LOCATE ANY TAMPER SWITCHES IN |
| THE FIRE PUMP ROOM. |
| |
| SHEET FA-101A: INSUFFICIENT NOTIFICATION IN EAST |
| PORTION OF CONNECTOR #156. |
| |
| SHEET FA-101A: EXTERIOR PULL STATION AND NOTIFICATION |
| NEEDED NEAR POOL EXIT/CONNECTOR #156. |
| |
| SHEET FA101B: STROBE DEVICE IN NORTH CORRIDOR IS |
| LOCATED MORE THAN 15 FEET FROM THE END OF THE CORRIDOR. |
| |
| SHEET FA-101B: INSUFFICIENT NOTIFICATION IN BAR TERRACE |
| #105A. |
| |
| SHEET FA-101B: THE FIRST FLOOR HAS A LARGE QUANTITY OF |
| WINDOWS/NATURAL LIGHTING. RE-EVALUATE THE STROBE |
| CANDELA ESPECIALLY THE CEILING-MOUNTED DEVICES. |
| |
| SHEET FA-101C: SOUTH WALL OF BALLROOM HAS INSUFFICIENT |
| STROBE COVERAGE. |
| |
| SHEET FA-101C: SOUTHWEST AREA OF LOADING #131 HAS |
| INSUFFICIENT STROBE COVERAGE. |
| |
| SHEET FA-101C: NORTH WALL OF SECURITY #133 HAS |
| INSUFFICIENT STROBE COVERAGE. |
| |
| SHEET FA-101D: NO NOTIFICATION APPLIANCE IN LOBBY OF |
| SERVICE ELEVATOR #111 OR STAIR VESTIBULE #163. |
| |
| SHEET FA-101D: INSUFFICIENT STROBE COVERAGE IN ADMIN |
| OFFICES #112. |
| |
| SHEET FA-102A: MISSING NOTIFICATION APPLIANCE WITHIN 15 |
| FEET OF CORRIDOR DOOR IN PRE-FUNCTION CORRIDOR #221. |
| |
| NOTE: 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE |
| EMERGENCY COMMAND CENTER: |
| (1) THE FIRE DEPARTMENT COMMUNICATION UNIT |
| (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| ACCESS TO THE PUBLIC TELEPHONE SYSTEM |
| (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| FLOOR PLAN AND DETAILING THE BUILDING CORE MEANS OF |
| EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING |
| EQUIPMENT, AND FIRE DEPARTMENT ACCESS |
| (4) WORK TABLE |
| (5) IF APPLICABLE, HAZARDOUS MATERIAL MANAGEMENT PLANS |
| FOR THE BUILDING |
| |
| NOTE: 11.9.5 WHERE OTHERWISE REQUIRED, THE FOLLOWING |
| DEVICES OR FUNCTIONS SHALL BE PROVIDED WITHIN THE |
| EMERGENCY COMMAND CENTER: |
| (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM UNIT |
| (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT |
| (3) ANNUNCIATOR VISUALLY INDICATING THE LOCATION OF THE |
| ELEVATORS AND WHETHER THEY ARE OPERATIONAL |
| (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING |
| SYSTEMS |
| (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS |
| SIMULTANEOUSLY |
| (6) SPRINKLER VALVE AND WATERFLOW DETECTOR DISPLAY |
| PANELS |
| (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS |
| (8) FIRE PUMP STATUS INDICATORS |
| (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND |
| TRANSFER FEATURES |
| (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| BY OTHER SECTIONS OF THIS CODE |
| (11) CONTROLS REQUIRED FOR SMOKE CONTROL |
| |