Plan Review Details - Permit 14120915
Plan Review Stops For Permit 14120915
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2016-02-12 Cont ID  
Sent By shill Date 2016-02-12 Time 16:05 Rev Time 0.00
Received By shill Date 2016-02-12 Time 16:05 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2015-11-20 Cont ID  
Sent By shill Date 2015-11-20 Time 13:07 Rev Time 0.00
Received By shill Date 2015-11-20 Time 13:07 Sent To  
Notes
2015-11-20 13:07:20****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLANS REFER TO AN EXISTING CENTRAL AIR AND HEAT
 SYSTEM TO REMAIN. I WAS UNABLE TO LOCATE A PERMIT FOR
 THIS WORK. EITHER PROVIDE A PERMIT NUMBER OR SUBMIT
 APPLICATION, FBC 105.
  
 APPLICATION IS TO INCLUDE VALUE OF MECHANICAL SYSTEM.
 PLANS SHOULD STATE "PROPOSED" - IT IS NOT "EXISTING"
 UNLESS LEGALLY INSTALLED (PERMITTED AND INSPECTED).
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-09-12 Cont ID  
Sent By shill Date 2015-09-12 Time 18:10 Rev Time 0.00
Received By shill Date 2015-09-12 Time 18:10 Sent To  
Notes
2015-09-12 18:11:21****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PLANS REFER TO AN EXISTING CENTRAL AIR AND HEAT
 SYSTEM TO REMAIN. I WAS UNABLE TO LOCATE A PERMIT FOR
 THIS WORK. EITHER PROVIDE A PERMIT NUMBER OR SUBMIT
 APPLICATION, FBC 105.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-04-08 Cont ID  
Sent By shill Date 2015-04-08 Time 12:13 Rev Time 0.00
Received By shill Date 2015-04-08 Time 12:13 Sent To  
Notes
2015-04-08 12:20:45****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 SEE FRONT SCREEN NOTES - OWNER HAS BEEN PREVIOUSLY
 ADVISED OF ALL REQUIREMENTS
  
 FROM PREVIOUS REVIEW:
  
 1. FBC 109, CONTRACTOR IS TO PROVIDE A COST BREAKDOWN
 OF ALL WORK PERFORMED.
  
 2. PROVIDE A FLOOR PLAN OF STRUCTURE. THIS SHOULD
 INCLUDE ALL FIRE RESISTANCE RATED WALLS, FBC 107 AND
 LOCATION OF PROPOSED WORK (OR WORK DONE WITHOUT
 PERMITS), FBC 107.
  
 2ND REVIEW, NO WORK SHOWN ON PLAN, BUT THE DESCRIPTION
 INCLUDES CABINETRY AND AN ARCHWAY. TYPICAL CONSTRUCTION
 PLANS SHOW EXISTING CONDITIONS, PROPOSED CONDITIONS.
  
 3. OK
  
 4. THERE APPEAR TO BE TWO STRUCTURES ON THIS PARCEL.
 PROVIDE A SITE PLAN INDICATING WHICH STRUCTURE THIS
 PERMIT APPLICATION APPLIES TO.
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-01-21 Cont ID  
Sent By shill Date 2015-01-21 Time 17:04 Rev Time 0.00
Received By shill Date 2015-01-21 Time 17:04 Sent To M
Notes
2015-01-21 17:11:06****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 SEE FRONT SCREEN NOTES - OWNER HAS BEEN PREVIOUSLY
 ADVISED OF ALL REQUIREMENTS
  
 1. FBC 109, CONTRACTOR IS TO PROVIDE A COST BREAKDOWN
 OF ALL WORK PERFORMED.
  
 2. PROVIDE A FLOOR PLAN OF STRUCTURE. THIS SHOULD
 INCLUDE ALL FIRE RESISTANCE RATED WALLS, FBC 107 AND
 LOCATION OF PROPOSED WORK (OR WORK DONE WITHOUT
 PERMITS), FBC 107.
  
 3. REVISE PLAN TO INCLUDE OCCUPANCY CLASSIFICATION, FBC
 107.
  
 4. THERE APPEAR TO BE TWO STRUCTURES ON THIS PARCEL.
 PROVIDE A SITE PLAN INDICATING WHICH STRUCTURE THIS
 PERMIT APPLICATION APPLIES TO.
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2015-10-08 Cont ID  
Sent By albarran Date 2015-10-08 Time 11:35 Rev Time 0.00
Received By albarran Date 2015-10-08 Time 08:25 Sent To I
Notes
2015-10-08 11:36:22ELECTRICAL PROVISO FOR PERMIT 14120915
 IN ORDER TO BRING THE UNPERMITTED KITCHEN INTO
 COMPLIANCE, THE MINIMUM REQUIRED OUTLETS SHALL BE IN
 PLACE. THE DRAWING SUBMITTED FAILS TO INDICATE;
 THEREFORE CORRECTIONS ARE REQUIRED. FURTHERMORE THE
 PANEL PERMITTED OR NOT SHALL ALSO BE ACCORDING TO
 MINIMUM CODE STANDARDS; THUS REQUIRING THAT THERE BE A
 DISCONNECT AS INDICATED BY NEC 230.70(A)(1). SEE NEC
 230.6 FOR FURTHER DETAILS.
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2015-03-31 Cont ID  
Sent By shill Date 2015-03-31 Time 12:16 Rev Time 0.00
Received By dhayes Date 2015-03-31 Time 12:16 Sent To B
Notes
2015-03-31 14:16:153/31/2015
 PROJECT: LJUBO 827 BRIGGS ST
 PERMIT#: 14100826
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE THE ELECTRICAL RISER DIAGRAM TO INDICATE THE
 FOLLOWING:
 A MAIN DISCONNECTING MEANS AS REQUIRED BY NEC 230.70
 SIZES OF MAIN DISCONNECT, SERVICE ENTRANCE, FEEDERS,
 PANEL, AND GROUNDING ELECTRODE SYSTEM. NEC 215.5,
 250.50
  
 2) LOADS FOR NEW CIRCUITS OR EXTENDED CIRCUITS IN
 PREVIOUSLY WIRED DWELLING UNITS SHALL BE CALCULATED IN
 ACCORDANCE WITH EITHER 220.12 OR 220.14, AS APPLICABLE.
 NEC 220.16(2)
  
 3) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE
 LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND
 SPECIFIC PURPOSE OR USE. NEC 408.4
  
 3) INDICATE CIRCUITS ON THE FLOORPLAN FOR CLARITY. WPB
 AMENDMENTS TO FBC 107.3.2
  
 4) AT LEAST ONE GFI RECEPTACLE OUTLET SHALL BE
 INSTALLED AT EACH PENINSULAR COUNTERTOP SPACE. NEC
 210.52(C)(3)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date   Cont ID  
Sent By   Date 2015-02-10 Time   Rev Time 0.00
Received By dhayes Date 2015-02-10 Time 14:45 Sent To  
Notes
2015-02-10 14:45:262/10/2015
 PROJECT:
 PERMIT#:
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION:
  
 1)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-01-21 Cont ID  
Sent By dhayes Date 2015-01-21 Time 15:20 Rev Time 0.00
Received By dhayes Date 2015-01-21 Time 15:20 Sent To  
Notes
2015-01-21 15:27:021/21/2015
 PROJECT: 827 BRIGGS
 PERMIT#: 14120915
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE PLAN VIEW INDICATES ELECTRICAL OUTLETS. THE
 ELEVATION VIEW DOES NOT. PLEASE MAKE THE PLANS
 CONSISTANT.
  
 2) THERE ARE ADDITIONAL SHEETS INDICATING AN ELECTRICAL
 SERVICE AND A WATER HEATER. PROVIDE A SITE PLAN AND A
 FLOOR PLAN INDICATING THE LOCATION OF THE ELECTRICAL
 SERVICE, THE ELECTRICAL PANEL, AND THE WATER HEATER.
  
 3) TWO COPIES OF ALL PLANS AND SPECIFICATIONS ARE
 REQUIRED FOR SUBMITTAL. WPB AMENDMENTS TO THE FBC
 107.3.1 THERE IS ONLY ONE DRAWING SUBMITTED FOR THE
 WATER HEATER CONNECTION.
  
 4) THE WATER HEATER CONNECTION PLAN SUBMITTED INDICATED
 THE WATER HEATER AND THE WIRING FEEDING IT ARE ALL
 OUTDOORS. PROVIDE METHODS AND MATERIALS APPROVED FOR
 THE ENVIRONMENT USED FOR THIS WORK.
  
 5) THE RISER DIAGRAM SUBMITTED DOES NOT INCLUDE A MAIN
 DISCONNECT. A DISCONNECT IS REQUIRED TO BE INSTALLED AS
 CLOSE AS PRACTICAL TO THE SERVICE ENTRANCE. INDICATE
 THE LOCATION, TYPE AND SIZE OF MAIN DISCONNECT. NEC
 230.70(A)(1)
  
 6) THE RISER DIAGRAM IS UNCLEAR WITH REGARDS TO THE
 SERVICE ENTRANCE SIZE TYPE AND LOCATION. IF THIS IS
 TRUELY A DUPLEX ELECTRICAL SERVICE WITH TWO 100AMP
 ELECTRICAL SERVICES PROVIDE THE SERVICE ENTRANCE SIZE
 TYPE AND LOCATION.
  
 7) PROVIDE A LOAD CALCULATION INDICATED THE TOTAL
 CONNECTED LOAD FOR THE SERVICE INCLUDING BOTH UNITS.
  
 8) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL
 314 AND 315. PROVIDE A FLOOR PLAN OF THE UNIT(S)
 INDICATING THE LOCATION FOR THE REQUIRED SMOKE
 DETECTORS.
  
 9) INDICATE ANY ELECTRICAL WORK, OUTLETS LIGHTS AND
 CIRCUITS THAT ARE NEW, ALTERRED, RELOCATED, OR EXISTING
 TO REMAIN ON THE NEW FLOOR PLAN.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
 .

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-11-25 Cont ID  
Sent By shill Date 2014-11-25 Time 13:12 Rev Time 0.00
Received By dhayes Date 2014-11-25 Time 15:16 Sent To  
Notes
2015-01-21 13:13:02REVIEW FROM 14100826:
  
 11/25/2014
 PROJECT: LJUBO
 PERMIT#: 14100826
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) ACCORDING TO CODE ENFORCEMENT REPORT CASE # CE
 14070585, THE VIOLATION INCLUDES INTERIOR ALTERATIONS
 /EXTERIOR WORK THAT WAS DONE WITHOUT THE BENEFIT OF
 PERMITS AND INSPECTIONS. THE ELECTRICAL PERMIT CANNOT
 BE ISSUED UNTIL A FULL SET OF PROFESSIONALLY DRAWN
 PLANS DONE BY A DESIGN PROFESSIONAL LICENSED IN THE
 STATE OF FLORIDA IN ACCORDANCE WITH FL. STATUTES 471 &
 481 ARE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW
 AND APPROVAL. THE PLANS SHALL INCLUDE ALL THE
 INFORMATION, DETAILS AND APPROVALS REQUIRED BY SEC.
 107.3.5.3 OF THE WPB AMEND. TO 2010 FL. BLDG. CODE FOR
 PLAN REVIEW FOR THIS STRUCTURE. ELECTRICAL PLAN REVIEW.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-11-20 Cont ID  
Sent By shill Date 2015-11-20 Time 13:08 Rev Time 0.00
Received By shill Date 2015-10-23 Time 12:37 Sent To  
Notes
2015-10-26 12:37:37R01

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-10-08 Cont ID  
Sent By albarran Date 2015-10-08 Time 11:37 Rev Time 0.00
Received By albarran Date 2015-08-28 Time 08:55 Sent To Z
Notes
2015-10-08 11:39:1710/8/15 PASSED ELECTRICAL REVIEW WITH PROVISO AS NOTED
 ON PLANS. CONTRACTOR NOTIFIED VIA EMAIL. SENT TO SMALL
 DENIED BIN "A". MA
2015-09-12 18:04:439/12 R19
  
  
2015-09-09 12:43:37RESUB IN LIBRARY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-08 Cont ID  
Sent By dhayes Date 2015-04-08 Time 12:20 Rev Time 0.00
Received By shill Date 2015-02-10 Time 14:26 Sent To  
Notes
2015-02-10 14:25:31R24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-21 Cont ID  
Sent By shill Date 2015-01-21 Time 18:18 Rev Time 0.00
Received By shill Date 2015-01-21 Time 12:56 Sent To  
Notes
2015-01-21 12:56:24TO TL DESK
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2015-10-28 Cont ID  
Sent By rmcdouga Date 2015-10-28 Time 17:10 Rev Time 0.00
Received By rmcdouga Date 2015-10-28 Time 16:16 Sent To  
Notes
2015-10-28 17:10:54APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF
 RE-INSPECTION FEE(S).
 1) SUBMIT TWO SETS OF STRUCTURAL ANCHORING DETAILS THAT
 SHOW HOW THE ROOF TOP PACKAGE UNIT WILL BE ATTACHED TO
 THE ROOF TO RESIST THE WINDLOADS. FBCR-M1307.2.1
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-10-06 Cont ID  
Sent By rmcdouga Date 2015-10-06 Time 18:49 Rev Time 0.00
Received By rmcdouga Date 2015-10-06 Time 18:29 Sent To  
Notes
2015-10-06 18:31:37THERE ARE NO RECORDS ON FILE WITH THE CITY TO SHOW THAT
 ANY MECHANICAL WORK HAS BEEN DONE WITHIN THE LAST TEN
 YEARS. IF THERE IS NEWER HVAC EQUIPMENT, THEN IT WAS
 INSTALLED WITOUT PERMITS. MECHANICAL WORK DONE WITHOUT
 PERMITS IS REQUIRED TO BE INSPECTED FOR COMPLIANCE WITH
 THE CURRENT BUILDING CODE. NO MECHANICAL PLANS OR
 PERMIT APPLICATION WERE SUBMITTED. (REPEAT COMMENT)
 SUBMIT A MECHANICAL PERMIT APPLICATION AND TWO SETS OF
 PLANS THAT SPECIFY THE SCOPE OF MECHANICAL WORK THAT
 WAS DONE WITHOUT PERMITS AND SHOW THAT IT COMPLIES WITH
 THE 2010 FBC. SEE COMMENTS BELOW.
  
 PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  
 2) FBC - 107.3.5.3 PROVIDE A MECHANICAL PLAN TO SHOW
 SUPPLY AND RETURN DUCTS PER FBC-R M16 & BATH EXHAUST
 PER FBC-R M15.
  
 3) FBC -107.3.5.1.4 MECHANICAL MINIMUM PLAN REVIEW
 CRITERIA: SHOW, EXHAUST SYSTEMS, CLOTHES DRYER EXHAUST,
 KITCHEN EQUIPMENT EXHAUST, SPECIALTY EXHAUST SYSTEMS,
 EQUIPMENT, EQUIPMENT LOCATION, MAKE-UP AIR,
 ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS, VENTILATION,
 COMBUSTION AIR, CHIMNEYS, FIREPLACES AND VENTS,
 APPLIANCES, BOILERS, REFRIGERATION, BATHROOM
 VENTILATION, LABORATORY, DESIGN FLOOD ELEVATION.
  
 4) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT
 BEDROOMS.
  
 5) FBC 107.2.1 PROVIDE THE MODEL NUMBERS AND
 SPECIFICATIONS OF THE HEATING AND COOLING EQUIPMENT IN
 AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN THAT
 CORRESPONDS WITH THE EQUIPMENT SIZING CALCULATIONS.
  
 6) PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE
 PREVIOUSLY COMPLETED WORK TO BE MADE ACCESSIBLE AND
 OPEN FOR INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION
 FOR ALL CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO
 FBC 110 & FBC 117.
 -FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
 -FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 7) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-03-20 Cont ID  
Sent By rmcdouga Date 2015-03-20 Time 10:58 Rev Time 0.00
Received By rmcdouga Date 2015-03-20 Time 10:58 Sent To  
Notes
2015-03-20 11:16:16MECHANICAL WORK DONE WITHOUT PERMITS. NO MECHANICAL
 PLANS OR PERMIT APPLICATION WERE SUBMITTED. (REPEAT
 COMMENT) SUBMIT A MECHANICAL PERMIT APPLICATION AND TWO
 SETS OF PLANS THAT SPECIFY THE SCOPE OF MECHANICAL WORK
 THAT WAS DONE WITHOUT PERMITS.
  
 PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS.
  
 2) FBC - 107.3.5.3 PROVIDE A MECHANICAL PLAN TO SHOW
 SUPPLY AND RETURN DUCTS PER FBC-R M16 & BATH EXHAUST
 PER FBC-R M15.
  
 3) FBC -107.3.5.1.4 MECHANICAL MINIMUM PLAN REVIEW
 CRITERIA: SHOW, EXHAUST SYSTEMS, CLOTHES DRYER EXHAUST,
 KITCHEN EQUIPMENT EXHAUST, SPECIALTY EXHAUST SYSTEMS,
 EQUIPMENT, EQUIPMENT LOCATION, MAKE-UP AIR,
 ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS, VENTILATION,
 COMBUSTION AIR, CHIMNEYS, FIREPLACES AND VENTS,
 APPLIANCES, BOILERS, REFRIGERATION, BATHROOM
 VENTILATION, LABORATORY, DESIGN FLOOD ELEVATION.
  
 4) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT
 BEDROOMS.
  
 5) FBC 107.2.1 PROVIDE THE MODEL NUMBERS AND
 SPECIFICATIONS OF THE HEATING AND COOLING EQUIPMENT IN
 AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN THAT
 CORRESPONDS WITH THE EQUIPMENT SIZING CALCULATIONS.
  
 6) PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE
 PREVIOUSLY COMPLETED WORK TO BE MADE ACCESSIBLE AND
 OPEN FOR INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION
 FOR ALL CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO
 FBC 110 & FBC 117.
 -FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A
 PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY
 THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK
 SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION
 PURPOSES UNTIL APPROVED.
 -FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR
 TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE
 TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN
 APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY.
  
 7) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-01-21 Cont ID  
Sent By rmcdouga Date 2015-01-21 Time 17:13 Rev Time 0.00
Received By rmcdouga Date 2015-01-21 Time 17:13 Sent To  
Notes
2015-01-21 17:14:56MECHANICAL WORK DONE WITHOUT PERMITS. NO MECHANICAL
 PLANS OR PERMIT APPLICATION WERE SUBMITTED.

Review Stop P PLUMBING
Rev No 4 Status P Date 2015-11-03 Cont ID  
Sent By tklarge Date 2015-11-03 Time 04:29 Rev Time 0.00
Received By tklarge Date 2015-11-03 Time 04:10 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-09-09 Cont ID  
Sent By tklarge Date 2015-09-09 Time 09:01 Rev Time 0.00
Received By tklarge Date 2015-09-09 Time 08:44 Sent To  
Notes
2015-09-09 09:00:17THIS STRUCTURE WAS CITED FOR PLUMBING AND OTHER WORK
 (ELECTRICAL, BUILDING,MECHANICAL) DONE WITHOUT THE
 PROPER PERMITS OR INSPECTIONS.THE SUBMITTED PLANS ARE
 FOR AN "AS-BUILT" CONDITION. THIS IS NOT ACCEPTABLE FOR
 THIS APPLICATION. A SET OF PLANS SHALL BE SUBMITTED
 THAT SHOWS AN EXISTING FLOOR PLAN WITH ALL THE
 UNPERMITTED WORK THAT IS TO BE REMOVED AND THE PROPOSED
 FLOOR PLAN WITH THE UNPERMITTED WORK REMOVED. THERE IS
 NO WAY OF KNOWING IF ANY UNPERMITTED NON-COMPLIANT WORK
 IS REMAINING AND BEING CLASSIFIED AS "EXISTING" ON THE
 "AS-BUILT" PLANS. THE ENTIRE SCOPE OF WORK SHALL BE
 DONE WITH ONE SET OF PLANS. WPB AMEND. TO FBC SEC.
 107.2.1, 107.3.5.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-01-21 Cont ID  
Sent By tklarge Date 2015-01-21 Time 14:03 Rev Time 0.00
Received By tklarge Date 2015-01-21 Time 14:03 Sent To  
Notes
2015-01-21 14:06:10REPAIR OR REPLACE SEWER, INSTALL NEW WATER HEATER,
 REMOVE UNPERMITTED PLUMBING WHERE ADDED KITCHEN WAS
 LOCATED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-01-21 Cont ID  
Sent By shill Date 2014-11-26 Time 13:00 Rev Time 0.00
Received By tklarge Date 2014-11-26 Time 13:01 Sent To  
Notes
2015-01-21 13:00:30PLAN REVIEW COMMENTS FROM 14100911:
  
 1) 1) ACCORDING TO CODE ENFORCEMENT REPORT CASE # CE
 14070585, THE VIOLATION INCLUDES INTERIOR ALTERATIONS
 /EXTERIOR WORK THAT WAS DONE WITHOUT THE BENEFIT OF
 PERMITS AND INSPECTIONS. THE PLUMBING PERMIT CANNOT BE
 ISSUED UNTIL A FULL SET OF PROFESSIONALLY DRAWN PLANS
 DONE BY A DESIGN PROFESSIONAL LICENSED IN THE STATE OF
 FLORIDA IN ACCORDANCE WITH FL. STATUTES 471 & 481 ARE
 SUBMITTED TO THE BUILDING DIVISION FOR REVIEW AND
 APPROVAL. THE PLANS SHALL INCLUDE ALL THE INFORMATION,
 DETAILS AND APPROVALS REQUIRED BY SEC. 107.3.5.3 OF THE
 WPB AMEND. TO 2010 FL. BLDG. CODE FOR PLAN REVIEW FOR
 THIS STRUCTURE.PLUMBING PLAN REVIEW.**
 ***NOTE***
 THE OWNER HAS BEEN TOLD NUMEROUS TIMES DURING HIS
 VISITS TO THE BUILDING DIVISION OF THE ABOVE
 REQUIREMENTS AND THAT AT A MINIMUM A RESIDENTIAL
 BUILDING CONTRACTOR SHALL SUBMIT A PERMIT APPLICATION
 AND PLANS TO REMOVE ALL THE UNPERMITTED ILLEGAL
 CONSTRUCTION ALONG WITH THE OTHER REQUIRED TRADES. THIS
 SHALL BE SUBMITTED TO THE BUILDING DIVISION AS A
 COMPLETE PACKAGE AND NOT IN A PIECE-MEAL FASHION AS HE
 IS ATTEMPTING TO DO.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop Z ZONING
Rev No 5 Status P Date 2015-11-20 Cont ID  
Sent By shill Date 2015-11-20 Time 13:08 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
2015-11-20 13:08:40OK PER SG
  

Review Stop Z ZONING
Rev No 4 Status P Date 2015-09-25 Cont ID  
Sent By albarran Date 2015-10-08 Time 11:39 Rev Time 0.00
Received By   Date 2015-09-25 Time   Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2015-09-01 Cont ID  
Sent By sgraham Date 2015-09-01 Time 09:27 Rev Time 0.00
Received By sgraham Date 2015-09-01 Time 09:27 Sent To P
Notes
2015-09-01 09:31:099/1/15 ZONING FAILED
  
 1. SUBMIT PLANS SHOWING THE WORK COMPLETED WITHOUT
 PERMITS, SHOW THE ILLEGAL CONVERSION OF THE TWO
 APARTMENTS
 2. THE PLANS SHOULD SHOW ALL THE WORK CONVERTING THE
 BUILDING BACK TO A SINGLE FAMILY HOUSE
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2015-02-12 Cont ID  
Sent By sgraham Date 2015-02-12 Time 14:45 Rev Time 0.00
Received By sgraham Date 2015-02-12 Time 14:45 Sent To  
Notes
2015-02-12 14:55:442/12/15 ZONING FAILED.
  
 1.PROVIDE TWO COPIES OF AN UP TO DATE SURVEY
 2. ACCORDING TO THE ELECTRICAL CALCULATIONS, THERE IS
 2- RANGES, A/C UNITS & DRYERS WHICH IS NOT PERMIT IN
 THE SINGLE FAMILY HOME.

Review Stop Z ZONING
Rev No 1 Status F Date 2015-01-21 Cont ID  
Sent By shill Date 2015-01-21 Time 17:20 Rev Time 0.00
Received By shill Date 2015-01-21 Time 17:20 Sent To  
Notes
2015-01-21 17:20:39A ZONING REVIEW WILL BE DONE AFTER COMPLETE PLANS ARE
 SUBMITTED.