Plan Review Stops For Permit 14120915 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
5 |
Status |
P |
Date |
2016-02-12 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2016-02-12 |
Time |
16:05 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2016-02-12 |
Time |
16:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
F |
Date |
2015-11-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-11-20 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-11-20 |
Time |
13:07 |
Sent To |
|
|
Notes |
2015-11-20 13:07:20 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. PLANS REFER TO AN EXISTING CENTRAL AIR AND HEAT | | SYSTEM TO REMAIN. I WAS UNABLE TO LOCATE A PERMIT FOR | | THIS WORK. EITHER PROVIDE A PERMIT NUMBER OR SUBMIT | | APPLICATION, FBC 105. | | | | APPLICATION IS TO INCLUDE VALUE OF MECHANICAL SYSTEM. | | PLANS SHOULD STATE "PROPOSED" - IT IS NOT "EXISTING" | | UNLESS LEGALLY INSTALLED (PERMITTED AND INSPECTED). | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2015-09-12 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-09-12 |
Time |
18:10 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-09-12 |
Time |
18:10 |
Sent To |
|
|
Notes |
2015-09-12 18:11:21 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | 1. PLANS REFER TO AN EXISTING CENTRAL AIR AND HEAT | | SYSTEM TO REMAIN. I WAS UNABLE TO LOCATE A PERMIT FOR | | THIS WORK. EITHER PROVIDE A PERMIT NUMBER OR SUBMIT | | APPLICATION, FBC 105. | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2015-04-08 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-04-08 |
Time |
12:13 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-04-08 |
Time |
12:13 |
Sent To |
|
|
Notes |
2015-04-08 12:20:45 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | SEE FRONT SCREEN NOTES - OWNER HAS BEEN PREVIOUSLY | | ADVISED OF ALL REQUIREMENTS | | | | FROM PREVIOUS REVIEW: | | | | 1. FBC 109, CONTRACTOR IS TO PROVIDE A COST BREAKDOWN | | OF ALL WORK PERFORMED. | | | | 2. PROVIDE A FLOOR PLAN OF STRUCTURE. THIS SHOULD | | INCLUDE ALL FIRE RESISTANCE RATED WALLS, FBC 107 AND | | LOCATION OF PROPOSED WORK (OR WORK DONE WITHOUT | | PERMITS), FBC 107. | | | | 2ND REVIEW, NO WORK SHOWN ON PLAN, BUT THE DESCRIPTION | | INCLUDES CABINETRY AND AN ARCHWAY. TYPICAL CONSTRUCTION | | PLANS SHOW EXISTING CONDITIONS, PROPOSED CONDITIONS. | | | | 3. OK | | | | 4. THERE APPEAR TO BE TWO STRUCTURES ON THIS PARCEL. | | PROVIDE A SITE PLAN INDICATING WHICH STRUCTURE THIS | | PERMIT APPLICATION APPLIES TO. | | | | | | | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2015-01-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-01-21 |
Time |
17:04 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-01-21 |
Time |
17:04 |
Sent To |
M |
|
Notes |
2015-01-21 17:11:06 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | SEE FRONT SCREEN NOTES - OWNER HAS BEEN PREVIOUSLY | | ADVISED OF ALL REQUIREMENTS | | | | 1. FBC 109, CONTRACTOR IS TO PROVIDE A COST BREAKDOWN | | OF ALL WORK PERFORMED. | | | | 2. PROVIDE A FLOOR PLAN OF STRUCTURE. THIS SHOULD | | INCLUDE ALL FIRE RESISTANCE RATED WALLS, FBC 107 AND | | LOCATION OF PROPOSED WORK (OR WORK DONE WITHOUT | | PERMITS), FBC 107. | | | | 3. REVISE PLAN TO INCLUDE OCCUPANCY CLASSIFICATION, FBC | | 107. | | | | 4. THERE APPEAR TO BE TWO STRUCTURES ON THIS PARCEL. | | PROVIDE A SITE PLAN INDICATING WHICH STRUCTURE THIS | | PERMIT APPLICATION APPLIES TO. | | | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2015-10-08 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-10-08 |
Time |
11:35 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-10-08 |
Time |
08:25 |
Sent To |
I |
|
Notes |
2015-10-08 11:36:22 | ELECTRICAL PROVISO FOR PERMIT 14120915 | | IN ORDER TO BRING THE UNPERMITTED KITCHEN INTO | | COMPLIANCE, THE MINIMUM REQUIRED OUTLETS SHALL BE IN | | PLACE. THE DRAWING SUBMITTED FAILS TO INDICATE; | | THEREFORE CORRECTIONS ARE REQUIRED. FURTHERMORE THE | | PANEL PERMITTED OR NOT SHALL ALSO BE ACCORDING TO | | MINIMUM CODE STANDARDS; THUS REQUIRING THAT THERE BE A | | DISCONNECT AS INDICATED BY NEC 230.70(A)(1). SEE NEC | | 230.6 FOR FURTHER DETAILS. | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2015-03-31 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-03-31 |
Time |
12:16 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-03-31 |
Time |
12:16 |
Sent To |
B |
|
Notes |
2015-03-31 14:16:15 | 3/31/2015 | | PROJECT: LJUBO 827 BRIGGS ST | | PERMIT#: 14100826 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 3RD ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) REVISE THE ELECTRICAL RISER DIAGRAM TO INDICATE THE | | FOLLOWING: | | A MAIN DISCONNECTING MEANS AS REQUIRED BY NEC 230.70 | | SIZES OF MAIN DISCONNECT, SERVICE ENTRANCE, FEEDERS, | | PANEL, AND GROUNDING ELECTRODE SYSTEM. NEC 215.5, | | 250.50 | | | | 2) LOADS FOR NEW CIRCUITS OR EXTENDED CIRCUITS IN | | PREVIOUSLY WIRED DWELLING UNITS SHALL BE CALCULATED IN | | ACCORDANCE WITH EITHER 220.12 OR 220.14, AS APPLICABLE. | | NEC 220.16(2) | | | | 3) EVERY CIRCUIT AND CIRCUIT MODIFICATION SHALL BE | | LEGIBLY IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND | | SPECIFIC PURPOSE OR USE. NEC 408.4 | | | | 3) INDICATE CIRCUITS ON THE FLOORPLAN FOR CLARITY. WPB | | AMENDMENTS TO FBC 107.3.2 | | | | 4) AT LEAST ONE GFI RECEPTACLE OUTLET SHALL BE | | INSTALLED AT EACH PENINSULAR COUNTERTOP SPACE. NEC | | 210.52(C)(3) | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | SHEETS FOR COMPARATIVE REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2015-02-10 |
Time |
|
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-02-10 |
Time |
14:45 |
Sent To |
|
|
Notes |
2015-02-10 14:45:26 | 2/10/2015 | | PROJECT: | | PERMIT#: | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | ELECTRICAL PLAN REVIEW | | ACTION: | | | | 1) | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2015-01-21 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-01-21 |
Time |
15:20 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-01-21 |
Time |
15:20 |
Sent To |
|
|
Notes |
2015-01-21 15:27:02 | 1/21/2015 | | PROJECT: 827 BRIGGS | | PERMIT#: 14120915 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) THE PLAN VIEW INDICATES ELECTRICAL OUTLETS. THE | | ELEVATION VIEW DOES NOT. PLEASE MAKE THE PLANS | | CONSISTANT. | | | | 2) THERE ARE ADDITIONAL SHEETS INDICATING AN ELECTRICAL | | SERVICE AND A WATER HEATER. PROVIDE A SITE PLAN AND A | | FLOOR PLAN INDICATING THE LOCATION OF THE ELECTRICAL | | SERVICE, THE ELECTRICAL PANEL, AND THE WATER HEATER. | | | | 3) TWO COPIES OF ALL PLANS AND SPECIFICATIONS ARE | | REQUIRED FOR SUBMITTAL. WPB AMENDMENTS TO THE FBC | | 107.3.1 THERE IS ONLY ONE DRAWING SUBMITTED FOR THE | | WATER HEATER CONNECTION. | | | | 4) THE WATER HEATER CONNECTION PLAN SUBMITTED INDICATED | | THE WATER HEATER AND THE WIRING FEEDING IT ARE ALL | | OUTDOORS. PROVIDE METHODS AND MATERIALS APPROVED FOR | | THE ENVIRONMENT USED FOR THIS WORK. | | | | 5) THE RISER DIAGRAM SUBMITTED DOES NOT INCLUDE A MAIN | | DISCONNECT. A DISCONNECT IS REQUIRED TO BE INSTALLED AS | | CLOSE AS PRACTICAL TO THE SERVICE ENTRANCE. INDICATE | | THE LOCATION, TYPE AND SIZE OF MAIN DISCONNECT. NEC | | 230.70(A)(1) | | | | 6) THE RISER DIAGRAM IS UNCLEAR WITH REGARDS TO THE | | SERVICE ENTRANCE SIZE TYPE AND LOCATION. IF THIS IS | | TRUELY A DUPLEX ELECTRICAL SERVICE WITH TWO 100AMP | | ELECTRICAL SERVICES PROVIDE THE SERVICE ENTRANCE SIZE | | TYPE AND LOCATION. | | | | 7) PROVIDE A LOAD CALCULATION INDICATED THE TOTAL | | CONNECTED LOAD FOR THE SERVICE INCLUDING BOTH UNITS. | | | | 8) WHEN ALTERATIONS, REPAIRS, OR ADDITIONS REQUIRING A | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | LOCATED AS REQUIRED FOR NEW DWELLINGS. FBC-RESIDENTIAL | | 314 AND 315. PROVIDE A FLOOR PLAN OF THE UNIT(S) | | INDICATING THE LOCATION FOR THE REQUIRED SMOKE | | DETECTORS. | | | | 9) INDICATE ANY ELECTRICAL WORK, OUTLETS LIGHTS AND | | CIRCUITS THAT ARE NEW, ALTERRED, RELOCATED, OR EXISTING | | TO REMAIN ON THE NEW FLOOR PLAN. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] | | | | | | . |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2014-11-25 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-11-25 |
Time |
13:12 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2014-11-25 |
Time |
15:16 |
Sent To |
|
|
Notes |
2015-01-21 13:13:02 | REVIEW FROM 14100826: | | | | 11/25/2014 | | PROJECT: LJUBO | | PERMIT#: 14100826 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 3RD ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) ACCORDING TO CODE ENFORCEMENT REPORT CASE # CE | | 14070585, THE VIOLATION INCLUDES INTERIOR ALTERATIONS | | /EXTERIOR WORK THAT WAS DONE WITHOUT THE BENEFIT OF | | PERMITS AND INSPECTIONS. THE ELECTRICAL PERMIT CANNOT | | BE ISSUED UNTIL A FULL SET OF PROFESSIONALLY DRAWN | | PLANS DONE BY A DESIGN PROFESSIONAL LICENSED IN THE | | STATE OF FLORIDA IN ACCORDANCE WITH FL. STATUTES 471 & | | 481 ARE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW | | AND APPROVAL. THE PLANS SHALL INCLUDE ALL THE | | INFORMATION, DETAILS AND APPROVALS REQUIRED BY SEC. | | 107.3.5.3 OF THE WPB AMEND. TO 2010 FL. BLDG. CODE FOR | | PLAN REVIEW FOR THIS STRUCTURE. ELECTRICAL PLAN REVIEW. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | SHEETS FOR COMPARATIVE REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2015-11-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-11-20 |
Time |
13:08 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-10-23 |
Time |
12:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2015-10-08 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-10-08 |
Time |
11:37 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2015-08-28 |
Time |
08:55 |
Sent To |
Z |
|
Notes |
2015-10-08 11:39:17 | 10/8/15 PASSED ELECTRICAL REVIEW WITH PROVISO AS NOTED | | ON PLANS. CONTRACTOR NOTIFIED VIA EMAIL. SENT TO SMALL | | DENIED BIN "A". MA | 2015-09-12 18:04:43 | 9/12 R19 | | | | | 2015-09-09 12:43:37 | RESUB IN LIBRARY |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-04-08 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-04-08 |
Time |
12:20 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-02-10 |
Time |
14:26 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-01-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-01-21 |
Time |
18:18 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-01-21 |
Time |
12:56 |
Sent To |
|
|
Notes |
2015-01-21 12:56:24 | TO TL DESK | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2015-10-28 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2015-10-28 |
Time |
17:10 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-10-28 |
Time |
16:16 |
Sent To |
|
|
Notes |
2015-10-28 17:10:54 | APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED | | PROVISIONALLY. FAILURE TO CORRECT THE LISTED | | DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL | | RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF | | RE-INSPECTION FEE(S). | | 1) SUBMIT TWO SETS OF STRUCTURAL ANCHORING DETAILS THAT | | SHOW HOW THE ROOF TOP PACKAGE UNIT WILL BE ATTACHED TO | | THE ROOF TO RESIST THE WINDLOADS. FBCR-M1307.2.1 | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2015-10-06 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2015-10-06 |
Time |
18:49 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-10-06 |
Time |
18:29 |
Sent To |
|
|
Notes |
2015-10-06 18:31:37 | THERE ARE NO RECORDS ON FILE WITH THE CITY TO SHOW THAT | | ANY MECHANICAL WORK HAS BEEN DONE WITHIN THE LAST TEN | | YEARS. IF THERE IS NEWER HVAC EQUIPMENT, THEN IT WAS | | INSTALLED WITOUT PERMITS. MECHANICAL WORK DONE WITHOUT | | PERMITS IS REQUIRED TO BE INSPECTED FOR COMPLIANCE WITH | | THE CURRENT BUILDING CODE. NO MECHANICAL PLANS OR | | PERMIT APPLICATION WERE SUBMITTED. (REPEAT COMMENT) | | SUBMIT A MECHANICAL PERMIT APPLICATION AND TWO SETS OF | | PLANS THAT SPECIFY THE SCOPE OF MECHANICAL WORK THAT | | WAS DONE WITHOUT PERMITS AND SHOW THAT IT COMPLIES WITH | | THE 2010 FBC. SEE COMMENTS BELOW. | | | | PLAN | | REVIEW COMMENTS | | | | 3RD REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING | | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | PROVIDE EQUIPMENT SIZING CALCULATIONS. | | | | 2) FBC - 107.3.5.3 PROVIDE A MECHANICAL PLAN TO SHOW | | SUPPLY AND RETURN DUCTS PER FBC-R M16 & BATH EXHAUST | | PER FBC-R M15. | | | | 3) FBC -107.3.5.1.4 MECHANICAL MINIMUM PLAN REVIEW | | CRITERIA: SHOW, EXHAUST SYSTEMS, CLOTHES DRYER EXHAUST, | | KITCHEN EQUIPMENT EXHAUST, SPECIALTY EXHAUST SYSTEMS, | | EQUIPMENT, EQUIPMENT LOCATION, MAKE-UP AIR, | | ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS, VENTILATION, | | COMBUSTION AIR, CHIMNEYS, FIREPLACES AND VENTS, | | APPLIANCES, BOILERS, REFRIGERATION, BATHROOM | | VENTILATION, LABORATORY, DESIGN FLOOD ELEVATION. | | | | 4) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT | | BEDROOMS. | | | | 5) FBC 107.2.1 PROVIDE THE MODEL NUMBERS AND | | SPECIFICATIONS OF THE HEATING AND COOLING EQUIPMENT IN | | AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN THAT | | CORRESPONDS WITH THE EQUIPMENT SIZING CALCULATIONS. | | | | 6) PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE | | PREVIOUSLY COMPLETED WORK TO BE MADE ACCESSIBLE AND | | OPEN FOR INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION | | FOR ALL CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO | | FBC 110 & FBC 117. | | -FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A | | PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY | | THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK | | SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION | | PURPOSES UNTIL APPROVED. | | -FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR | | TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE | | TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN | | APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY. | | | | 7) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE | | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER | | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN | | ADDRESSED. | | | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2015-03-20 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2015-03-20 |
Time |
10:58 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-03-20 |
Time |
10:58 |
Sent To |
|
|
Notes |
2015-03-20 11:16:16 | MECHANICAL WORK DONE WITHOUT PERMITS. NO MECHANICAL | | PLANS OR PERMIT APPLICATION WERE SUBMITTED. (REPEAT | | COMMENT) SUBMIT A MECHANICAL PERMIT APPLICATION AND TWO | | SETS OF PLANS THAT SPECIFY THE SCOPE OF MECHANICAL WORK | | THAT WAS DONE WITHOUT PERMITS. | | | | PLAN REVIEW COMMENTS | | | | 2ND REVIEW: FBC 2010 | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY MECHANICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING | | EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS | | CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER | | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES. | | PROVIDE EQUIPMENT SIZING CALCULATIONS. | | | | 2) FBC - 107.3.5.3 PROVIDE A MECHANICAL PLAN TO SHOW | | SUPPLY AND RETURN DUCTS PER FBC-R M16 & BATH EXHAUST | | PER FBC-R M15. | | | | 3) FBC -107.3.5.1.4 MECHANICAL MINIMUM PLAN REVIEW | | CRITERIA: SHOW, EXHAUST SYSTEMS, CLOTHES DRYER EXHAUST, | | KITCHEN EQUIPMENT EXHAUST, SPECIALTY EXHAUST SYSTEMS, | | EQUIPMENT, EQUIPMENT LOCATION, MAKE-UP AIR, | | ROOF-MOUNTED EQUIPMENT, DUCT SYSTEMS, VENTILATION, | | COMBUSTION AIR, CHIMNEYS, FIREPLACES AND VENTS, | | APPLIANCES, BOILERS, REFRIGERATION, BATHROOM | | VENTILATION, LABORATORY, DESIGN FLOOD ELEVATION. | | | | 4) FBC-R - M 1602.4 PROVIDE BALANCED AIR RETURN AT | | BEDROOMS. | | | | 5) FBC 107.2.1 PROVIDE THE MODEL NUMBERS AND | | SPECIFICATIONS OF THE HEATING AND COOLING EQUIPMENT IN | | AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN THAT | | CORRESPONDS WITH THE EQUIPMENT SIZING CALCULATIONS. | | | | 6) PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE | | PREVIOUSLY COMPLETED WORK TO BE MADE ACCESSIBLE AND | | OPEN FOR INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION | | FOR ALL CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO | | FBC 110 & FBC 117. | | -FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A | | PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY | | THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK | | SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION | | PURPOSES UNTIL APPROVED. | | -FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR | | TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE | | TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN | | APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY. | | | | 7) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE | | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER | | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN | | ADDRESSED. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2015-01-21 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2015-01-21 |
Time |
17:13 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2015-01-21 |
Time |
17:13 |
Sent To |
|
|
Notes |
2015-01-21 17:14:56 | MECHANICAL WORK DONE WITHOUT PERMITS. NO MECHANICAL | | PLANS OR PERMIT APPLICATION WERE SUBMITTED. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
4 |
Status |
P |
Date |
2015-11-03 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-11-03 |
Time |
04:29 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-11-03 |
Time |
04:10 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
F |
Date |
2015-09-09 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-09-09 |
Time |
09:01 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-09-09 |
Time |
08:44 |
Sent To |
|
|
Notes |
2015-09-09 09:00:17 | THIS STRUCTURE WAS CITED FOR PLUMBING AND OTHER WORK | | (ELECTRICAL, BUILDING,MECHANICAL) DONE WITHOUT THE | | PROPER PERMITS OR INSPECTIONS.THE SUBMITTED PLANS ARE | | FOR AN "AS-BUILT" CONDITION. THIS IS NOT ACCEPTABLE FOR | | THIS APPLICATION. A SET OF PLANS SHALL BE SUBMITTED | | THAT SHOWS AN EXISTING FLOOR PLAN WITH ALL THE | | UNPERMITTED WORK THAT IS TO BE REMOVED AND THE PROPOSED | | FLOOR PLAN WITH THE UNPERMITTED WORK REMOVED. THERE IS | | NO WAY OF KNOWING IF ANY UNPERMITTED NON-COMPLIANT WORK | | IS REMAINING AND BEING CLASSIFIED AS "EXISTING" ON THE | | "AS-BUILT" PLANS. THE ENTIRE SCOPE OF WORK SHALL BE | | DONE WITH ONE SET OF PLANS. WPB AMEND. TO FBC SEC. | | 107.2.1, 107.3.5.3. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2015-01-21 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-01-21 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-01-21 |
Time |
14:03 |
Sent To |
|
|
Notes |
2015-01-21 14:06:10 | REPAIR OR REPLACE SEWER, INSTALL NEW WATER HEATER, | | REMOVE UNPERMITTED PLUMBING WHERE ADDED KITCHEN WAS | | LOCATED. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2015-01-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2014-11-26 |
Time |
13:00 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2014-11-26 |
Time |
13:01 |
Sent To |
|
|
Notes |
2015-01-21 13:00:30 | PLAN REVIEW COMMENTS FROM 14100911: | | | | 1) 1) ACCORDING TO CODE ENFORCEMENT REPORT CASE # CE | | 14070585, THE VIOLATION INCLUDES INTERIOR ALTERATIONS | | /EXTERIOR WORK THAT WAS DONE WITHOUT THE BENEFIT OF | | PERMITS AND INSPECTIONS. THE PLUMBING PERMIT CANNOT BE | | ISSUED UNTIL A FULL SET OF PROFESSIONALLY DRAWN PLANS | | DONE BY A DESIGN PROFESSIONAL LICENSED IN THE STATE OF | | FLORIDA IN ACCORDANCE WITH FL. STATUTES 471 & 481 ARE | | SUBMITTED TO THE BUILDING DIVISION FOR REVIEW AND | | APPROVAL. THE PLANS SHALL INCLUDE ALL THE INFORMATION, | | DETAILS AND APPROVALS REQUIRED BY SEC. 107.3.5.3 OF THE | | WPB AMEND. TO 2010 FL. BLDG. CODE FOR PLAN REVIEW FOR | | THIS STRUCTURE.PLUMBING PLAN REVIEW.** | | ***NOTE*** | | THE OWNER HAS BEEN TOLD NUMEROUS TIMES DURING HIS | | VISITS TO THE BUILDING DIVISION OF THE ABOVE | | REQUIREMENTS AND THAT AT A MINIMUM A RESIDENTIAL | | BUILDING CONTRACTOR SHALL SUBMIT A PERMIT APPLICATION | | AND PLANS TO REMOVE ALL THE UNPERMITTED ILLEGAL | | CONSTRUCTION ALONG WITH THE OTHER REQUIRED TRADES. THIS | | SHALL BE SUBMITTED TO THE BUILDING DIVISION AS A | | COMPLETE PACKAGE AND NOT IN A PIECE-MEAL FASHION AS HE | | IS ATTEMPTING TO DO. | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
5 |
Status |
P |
Date |
2015-11-20 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-11-20 |
Time |
13:08 |
Rev Time |
0.00 |
Received By |
shill |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2015-11-20 13:08:40 | OK PER SG | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
P |
Date |
2015-09-25 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2015-10-08 |
Time |
11:39 |
Rev Time |
0.00 |
Received By |
|
Date |
2015-09-25 |
Time |
|
Sent To |
B |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2015-09-01 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2015-09-01 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
sgraham |
Date |
2015-09-01 |
Time |
09:27 |
Sent To |
P |
|
Notes |
2015-09-01 09:31:09 | 9/1/15 ZONING FAILED | | | | 1. SUBMIT PLANS SHOWING THE WORK COMPLETED WITHOUT | | PERMITS, SHOW THE ILLEGAL CONVERSION OF THE TWO | | APARTMENTS | | 2. THE PLANS SHOULD SHOW ALL THE WORK CONVERTING THE | | BUILDING BACK TO A SINGLE FAMILY HOUSE | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2015-02-12 |
|
|
Cont ID |
|
Sent By |
sgraham |
Date |
2015-02-12 |
Time |
14:45 |
Rev Time |
0.00 |
Received By |
sgraham |
Date |
2015-02-12 |
Time |
14:45 |
Sent To |
|
|
Notes |
2015-02-12 14:55:44 | 2/12/15 ZONING FAILED. | | | | 1.PROVIDE TWO COPIES OF AN UP TO DATE SURVEY | | 2. ACCORDING TO THE ELECTRICAL CALCULATIONS, THERE IS | | 2- RANGES, A/C UNITS & DRYERS WHICH IS NOT PERMIT IN | | THE SINGLE FAMILY HOME. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2015-01-21 |
|
|
Cont ID |
|
Sent By |
shill |
Date |
2015-01-21 |
Time |
17:20 |
Rev Time |
0.00 |
Received By |
shill |
Date |
2015-01-21 |
Time |
17:20 |
Sent To |
|
|
Notes |
2015-01-21 17:20:39 | A ZONING REVIEW WILL BE DONE AFTER COMPLETE PLANS ARE | | SUBMITTED. |
|
|