Plan Review Details - Permit 14120909
Plan Review Stops For Permit 14120909
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2015-07-29 Cont ID  
Sent By shill Date 2015-07-29 Time 18:02 Rev Time 0.00
Received By shill Date 2015-07-29 Time 18:02 Sent To  
Notes
2015-07-29 18:02:58CHANGED ADDRESS TO CORRECT PARCEL
  

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 2018-01-09 Cont ID  
Sent By shill Date 2018-01-09 Time 16:01 Rev Time 0.00
Received By shill Date 2018-01-09 Time 16:01 Sent To  
Notes
2018-01-09 16:02:09EXEMPT FROM AIPP ORDINANCE PER S.WELTER (VIA EMAIL
 1/9/18)
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date   Cont ID  
Sent By   Date 2016-02-16 Time   Rev Time 0.00
Received By kconrad Date 2016-02-11 Time 10:35 Sent To  
Notes
2016-02-16 11:03:44REVIEWED THE UNI-SPAN PARTIAL SHORING PLANS FOR THE 2ND
 LEVEL DECK (POUR #1) SHEETS S-1, S-2,S-3, AND LEVELS
 3-8 (GRIDLINES #3 THRU #16) FROM LINES H.2 TO R-LINE,
 SHEETS S-4 AND S-5.
  
  
 1) REQUIRE THE SUBMITTAL OF THE SHORING DESIGN
 CALCULATIONS PURSUANT TO THE FBC, SECTION 107.1/1603.1.
  
 2) PROVIDE DETAILS/CALCULATIONS FOR GUARD RAIL SYSTEM
 PER THE FBC, SECTION 1607.8.
  
 3) PLEASE SUBMIT RE-SHORING PLANS FOR REVIEW AND ENSURE
 THAT THE SAME IS REVIEWED BY THE ENGINEER OF RECORD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-08-27 Cont ID  
Sent By shill Date 2015-08-17 Time 18:27 Rev Time 0.00
Received By shill Date 2015-08-06 Time 08:36 Sent To  
Notes
2015-08-10 07:21:462010 FLORIDA BUILDING CODE
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
 REVISION REQUIRED PRIOR TO COMMENCEMENT
  
 ****PROVISOS****
 ISSUED AT CONTRACTOR'S RISK
 THE FOLLOWING ITEMS ARE PROVISO ITEMS, REVISION
 REQUIRED PRIOR TO FIRST INSPECTION
 ITEMS ABOVE ARE TO BE DONE PRIOR TO PERMIT ISSUANCE
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 2010 FLORIDA BUILDING CODE
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 THE FOLLOWING COMMENTS ARE TO BE ADDRESSED IF PLANS ARE
 RESUBMITTED FOR OTHER TRADES. IF PLANS ARE NOT
 RESUBMITTED, THE FOLLOWING ITEMS WILL BE PROVISO ITEMS,
 REVISION REQUIRED PRIOR TO COMMENCEMENT.
  
 PLEASE BE ADVISED THAT COMMENTS HAVE BEEN REARRANGED
 AND RENUMBERED FOR CLARITY. COMMENTS WHICH ARE TO BE
 ADDRESSED AT THIS TIME (AS OTHER TRADES FAILED AND A
 RESUBMITTAL IS REQUIRED) ARE BELOW. THE ITEMS WHICH ARE
 TO BE ADDRESSED AT A FUTURE DATE, OR ARE INFORMATIONAL
 ONLY, ARE NOW ALL AT THE END OF THE COMMENT LIST.
  
 1. ARCHITECT?S RESPONSE INCLUDED BUILDING REVIEWS 1 AND
 2. IF RESUBMITTING, ONLY CURRENT ITEMS ARE TO BE
 ADDRESSED.
  
 2. FBC 107, AN OVERALL INDEX WAS PROVIDED (SHEET G000C)
 BUT THE INDEX IS NOT IN THE SAME ORDER AS THE
 PROJECTDOX FILES AND MANY SHEETS ARE STILL OUT OF
 ORDER. THIS HAS RESULTED IN ADDITIONAL PLAN REVIEW TIME
 FOR ALL REVIEWERS TO ATTEMPT TO LOCATE PAGES AND SERIES
 OF PLANS WITHIN THE FILE. A REVIEW OF PLAN ORDER WILL
 BE DONE PRIOR TO THE NEXT PLAN REVIEW.
  
 SOME ITEMS MAY HAVE NOT BEEN REVIEWED DUE TO THIS
 ISSUE. SOME OF THE PROJECTDOX ISSUES ARE:
  
 PHASE ONE/VOLUMEN ONE, EVERYTHING AFTER A625 (INCLUDING
 A626-644, INTERIORS, FOOD SERVICE) IS MISSING (FILES DO
 NOT FOLLOW SHEET A625 AS INDEX STATES, BUT ARE
 SCATTERED THROUGHOUT THE PLAN). THERE ARE A TOTAL OF AT
 LEAST 17 SHEETS WHICH ARE OUT OF ORDER. REPEAT COMMENT.
  
 IN101A BELONGS IN PHASE I, IS OUT OF ORDER AND IN PHASE
 2. THIS COMMENT APPLIES TO ALL OF THE IN SHEETS (OUT OF
 ORDER, PAGES ARE SCATTERED THROUGHOUT THE PLAN). REPEAT
 COMMENT.
  
 THE ORDER OF THE PHASE / VOLUMEN IS NOT CONSISTENT WITH
 THE ORDERING OF THE PHASE / VOLUMEN IN THE PROJECTDOX
 FILE
  
 PHASE 2 IRRIGATION SHEETS ARE NOT INCLUDED ON EITHER
 INDEX (G000C OR PHASE TWO VOLUMEN TWO INDEX)
  
 2110 - G000B DOESN'T INCLUDE FS (FOOD SERVICE) SHEETS,
 BUT THERE ARE FS SHEETS WHICH FOLLOW THE T (TECHNOLOGY)
 SHEETS. FS SHEETS ARE SHOWN ON G000C, BUT NOT IN THE
 ORDER SHOWN.
  
 REGARDING NAMING OF SHEETS, PAGES HAVE BEEN DIFFICULT
 TO LOCATE DUE TO INCONSISTENT INDEX AND NAMING
 CONVENTION WHICH IS NOT TYPICAL. SP WAS USED FOR SITE
 POOL, BUT IS USUALLY SITE PLAN. FS WAS USED FOR FOOD
 SERVICE, BUT THIS NAME IS USUALLY ASSIGNED TO FIRE
 SPRINKLER PAGES. K IS THE LETTER TYPICALLY USED FOR
 KITCHEN EQUIPMENT PLANS. OTHER REVIEWERS ARE STILL
 UNABLE TO LOCATE PAGES WHICH REQUIRE REVIEW. A DETAILED
 EXPLANATION OF PLAN ORDER ISSUES IS AVAILABLE VIA EMAIL
 UPON REQUEST.
  
 SEE PREVIOUS LIST REGARDING THE ORDER OF THE SERIES
 WITHIN THE PROJECTDOX FILE. THIS WAS NOT FIXED FOR THIS
 SUBMITTAL.
  
 ARCHITECT PROVIDED A RESPONSE NARRATIVE FOR AN
 EXPLANATION OF THE FILE ORDER. THIS IS NOT CONSISTENT
 WITH THE NAMING CONVENTION USED FOR THE FILES WHICH
 WERE UPLOADED, SO THE NARRATIVE IS NOT CONSISTENT WITH
 THE PROJECTDOX DOCUMENT. IN A 602 PAGE PLAN, IT IS VERY
 TIME CONSUMING TO SPECTULATE AS TO LOCATION OF
 INFORMATION.
  
 3. APPENDIX C INCLUDES INFORMATION NOT INCLUDED IN THE
 SUMMARY PAGE PREPARED BY ARCHITECT. PER ARCHITECT?S
 COVER LETTER FOR THE APPENDIX DOCUMENT, APPENDIX C
 SHOULD INCLUDE ONLY FIRESTOP SYSTEMS AND DOOR HARDWARE
 INFORMATION.
  
 SOME PAGES INCLUDE INFORMATION REVIEWED BY OTHER TRADES
 (ELECTRICAL WIRING SPECS, COMMERCIAL KITCHEN EQUIPMENT
 SPECS, ETC.).
  
 THE SPEC BOOK SHEETS SUBMITTED HAVE NOT BEEN REVIEWED.
 SPEC BOOKS SHOULD NOT BE A PART OF THE PERMIT FILE AS
 THE PLANS ARE TO SHOW CODE COMPLIANCE. REMOVE THE SPEC
 SHEETS AND ALL OTHER SHEETS NOT INCLUDED ON THE
 APPENDIX SUMMARY FROM THE FILE. THEY SHOULD BE UPLOADED
 AS A SEPARATE FILE.
  
 IT WOULD HELPFUL IF THE COVER PAGE SUMMARY (WHICH
 SERVES AS AN INDEX) WOULD INCLUDE PAGE NUMBERS. THE
 DOCUMENT IS 191 PAGES. ANY LARGE DOCUMENT SHOULD BE
 PAGINATED, FBC 107. OR, SPLIT THE DOCUMENT INTO SEVERAL
 DOCUMENT.
  
 4. A101 DOES NOT MATCH THE LIFE SAFETY PLAN AND OTHER
 SHEETS, PLEASE CORRELATE. IT IS DIFFICULT TO PERFORM A
 LIFE SAFETY REVIEW WITH THE MULTIPLE GRAPHICS ON THE
 LIFE SAFETY PAGE, OVERALL FLOOR PLAN WHICH IS CLEAN IS
 AN OLD VERSION, AND THE ENLARGED FLOOR PLAN HAS
 CONSTRUCTION DETAILS (WAS NOT INTENDED TO USE FOR LIFE
 SAFETY). THE GRAPHICS ON THE LIFE SAFETY PLAN OBSCURES
 WALLS AND DOORS. SHEET A101 IS REQUIRED FOR A COMPLETE
 LIFE SAFETY REVIEW.
  
 5. G101 HAS A NOTE, TRAVEL DISTANCE TO GATE 48FT 10IN,
 APPEARS TO LEAD TO A DOOR, NOT A GATE, PLEASE REVISE.
 THIS IS THE SAME EXIT ACCESS WHICH GRAPHICALLY DEPICTS
 A WALL BLOCKING MEANS OF EGRESS, FBC 107.
  
 6. DINING SHOW A DOUBLE DOOR OPENING INTO POOL AREA
 WITH TRAVEL DISTANCE TO GATE 107FT 3IN, BUT NO EXIT
 SIGN. EXIT STRATEGY NOT CLEAR.
  
 7. FBC 1005.1, THE LOSS OF ONE MEANS OF EGRESS SHALL
 NOT REDUCE THE CAPACITY TO LESS THAN 50 PERCENT, SEE
 POOL AREA. ONE EXIT SIGN IS ADJACENT TO TWO GATES
 (DOUBLE AND SINGLE), OCCUPANT LOADS LISTED FOR BOTH, AS
 WELL AS OCCUPANT LOAD STATED FOR THE EXIT TO THE SOUTH,
 NO EXIT SIGNS FROM BUILDING TO POOL AREA, NOT CLEAR
 WHICH 452 OCCUPANTS ARE EXITING THROUGH THIS AREA (59,
 117, 276 LABELED FOR POOL GATES).
  
 8. OK OR MOVED TO END OF COMMENT LIST (INFORMATIONAL OR
 FUTURE PROVISO ITEMS, NOT REQUIRED TO BE ADDRESSED WITH
 THE REVISION)
  
 9. G101, CORRIDOR 187 IS NOT A RATED CORRIDOR BUT
 SERVES THE RESIDENTIAL UNITS AS THERE IS AN EXIT SIGN
 FROM CORRIDOR 188 TO CORRIDOR 187, FBC TABLE 1018.1.
 THERE IS A NOTE WHICH STATES THAT TRAVEL DISTANCE IS
 134FT, BUT IT IS NOT CLEAR WHERE THIS IS APPLICABLE.
  
 SEE OTHER COMMENT REGARDING EXIT ENCLOSURE DEFINITION;
 REVISE PLAN TO CLARIFY MEANS OF EGRESS COMPONENTS AND
 EXIT STRATEGY.
  
 10. A101A AND G101, 47 FIXED SEATS SHOWN INCLUDING ONE
 COMPANION SEAT (TWO ARE REQUIRED BUT CAN BE MOVABLE IF
 COMPARABLE TO FIXED SEATING), TWO WHEELCHAIR SPACES
 APPEAR TO BE SHOWN (NOT MARKED, BUT RECTANGLES ARE
 SHOWN) BUT AN OCCUPANT LOAD OF 46 STATED AND NO
 OCCUPANT LOAD STATED FOR THE THEATER VESTIBULE. PLEASE
 CLARIFY THE MATH AND OCCUPANT LOAD. ALSO INCORPORATE A
 STATEMENT THAT ANY STAFF MEMBERS ENTERING THIS ROOM
 WILL BE USING ONE OF THE SEATS OR ADD A REASONABLE
 NUMBER OF STAFF MEMBERS TO THE OCCUPANT LOAD.
  
 REVISE PLAN TO LABEL THE TWO WHEELCHAIR SPACES AS SUCH.
  
 11. PROVISO, G101 AND A213, THE DOORS FOR THE MULTI
 PURPOSE ROOM INCLUDE SIDELIGHTS WHICH APPEAR TO BE
 IDENTICAL TO THE DOORS BUT DO NOT OPERATE. SEE FBC
 1008.1, REVISE PLAN TO SHOW HOW THE DOORS WILL BE
 EASILY DISTINGUISHABLE FROM THE INOPERABLE SIDELITES.
  
 SIGNAGE IS NOT ACCEPTABLE DUE TO THE LARGE NUMBER OF
 OCCUPANTS ATTEMPTING TO EXIT. ALSO SIGNAGE WOULD BE
 CONFUSING; SIGN STATES THIS IS NOT AN EXIT, BUT IT IS
 AN EXIT; UNLESS THE SIGN IS POSTED ON THE SIDELITE,
 SIGNAGE IS NOT CLEAR AS TO WHAT IS NOT AN EXIT.
  
 THIS ISSUE WILL BE A PROVISO ITEM. THE SIDELITES ARE
 GRAPHICALLY SHOWN AS IDENTICAL TO THE DOORS.
  
 THIS APPLIES TO BOTH DOORS 126 AND 124 (AND ANY OTHER
 DOORS AS APPLICABLE).
  
 12. FROM PREVIOUS LISTS, G101, AEROBICS 146 AND FITNESS
 143 APPEAR TO HAVE AN OCCUPANT LOAD OVER 50, BUT SECOND
 EXIT ACCESS NOT CLEAR. AEROBICS ROOM HAS TWO DOORS BUT
 BOTH LEAD TO SAME CORRIDOR (COMMON PATH). FITNESS ROOM
 HAS ONLY ONE EXIT ACCESS. TWO MEANS OF EGRESS REQUIRED
 FROM SPACES WITH AN OCCUPANT LOAD OVER 50, TWO EXITS
 REQUIRED FOR THE AREA.
  
 2ND REVIEW, COMMENT NOT ADDRESSED. ARCHITECT RESPONSE
 IS THAT THE ROOMS INDIVIDUALLY HAVE AN OCCUPANT LOAD
 LESS THAN 50.
  
 AEROBICS AND FITNESS ROOMS EACH SEPARATELY HAVE AN
 OCCUPANT LOAD LESS THAN 50 BUT TOGETHER HAVE AN
 OCCUPANT LOAD OVER 50 WITH THE PARTITION OPEN. TO TREAT
 EACH AREA SEPARATELY, REPLACE THE MOVABLE PARTITION
 WITH A WALL. OCCUPANCY CLASSIFICATION IS STATED AS
 BUSINESS. THIS SHOULD BE ASSEMBLY, SEE DEFINITION.
 REGARDLESS OF OCCUPANCY CLASSIFICATION, THE DOORS ARE
 TO SWING IN THE DIRECTION OF TRAVEL (146 AND 146A),
 1008.1.2 AS OCCUPANT LOAD EXCEEDS 50 WITH THE PARTITION
 OPEN.
  
 TRAVEL DISTANCE IS MEASURED TO THE GALLERY WHICH IS
 CALLED AN EXIT ENCLOSURE. SEE OTHER COMMENTS REGARDING
 THE DEFINITION OF EXIT ENCLOSURE. NOTE THAT AS
 DESIGNED, ALL OCCPANTS OF THIS AREA ARE FORCED TO GO
 THROUGH THE GALLERY WHICH IS OPEN TO TWO ELEVATORS.
  
 CONSIDER THE SCENARIO THAT SHOULD THERE BE AN ISSUE
 (FIRE OR SMOKE) IN THE ELEVATOR SHAFT, OCCUPANTS FOR
 THIS AREA ARE FORCED TO GO THROUGH A SMOKE FILLED EXIT
 ENCLOSURE. RATIONALE OF INCLUDING TWO ELEVATORS, TOILET
 ROOMS, LOW VOLTAGE SERVER ROOM, HOUSEKEEPING ROOM, OPEN
 LIVING ROOM LIBRARY, WORK ROOM IN AN ?EXIT ENCLOSURE?
 IS NOT CLEAR.
  
 SEE ALSO IBC CODE AND COMMENTARY 2009 (THE BASE CODE
 FOR FBC 2010), PAGE 7-62 (SECTION 708.14.1) WHERE
 ELEVATOR LOBBIES AND EXCEPTIONS ARE DISCUSSED AT
 LENGTH, WHICH SPECIFICALLY STATES:
  
 OF COURSE, THE ELEVATOR HOISTWAY DOORS CAN NEVER OPEN
 INTO AN EXIT ENCLOSURE.
  
 REVISE PLAN SO THAT THE EXIT ENCLOSURE INCLUDES ONLY
 ITEMS WHICH DO NOT POSE A HAZARD TO THE EXIT ENCLOSURE.
 THE LIVING ROOM WILL CONTAIN FURNITURE AND OTHER
 COMBUSTIBLES (HAZARD). THE ELEVATORS THEMSELVES POSE A
 HAZARD (EVEN WITH PRESSURIZATION). THE OTHER ROOMS
 CURRENTLY SHOWN WITHIN THE EXIT ENCLOSURE SHOULD ALSO
 BE SEPARATED FROM THE EXIT ENCLOSURE.
  
 REVISE PLAN SO THAT EXIT STRATEGY ADDRESSES THESE
 CONCERNS.
  
 13. AN ADDITIONAL DOOR WAS PROVIDED TO ADDRESS THE DEAD
 END BUT SEE OTHER COMMENTS REGARDING TWO EXITS REQUIRED
 AND USE OF THE GALLERY AS AN EXIT ENCLOSURE. PRIOR TO
 RESUBMITTAL, ENSURE THAT NO NEW DEAD ENDS ARE CREATED.
  
 14. G101, REVISE PLAN TO INCLUDE OCCUPANT LOAD AND AREA
 FOR THE FITNESS ROOM AND AEROBICS ROOM (SEPARATELY AS
 THE LARGER AREA CAN BE COMBINED TO TWO SMALLER AREAS).
 AS IT APPEARS THAT THE AEROBICS AND FITNESS AREA
 OCCUPANT LOAD WILL BE OVER 50, DOORS ARE TO SWING IN
 THE DIRECTION OF TRAVEL, FBC 1008.1.2.
  
 NOT ADDRESSED. CHANGE DOOR SWING OR ADD A WALL AT THE
 LOCATION OF THE FOLDING PARTITION. OCCUPANT FOR THE
 ROOM WITH THE PARTITION IS OVER 50 (PER BUILDING
 OFFICIAL).
  
 15. THE AEROBICS AND FITNESS AREA OCCUPANT LOAD IS OVER
 50, FIRE EXIT HARDWARE OR PANIC HARDWARE REQUIRED FOR
 THOSE DOORS AND ALL OTHER DOORS IN THE MEANS OF EGRESS,
 FBC 1008.1.10, 1004.9.
  
 NOT ADDRESED.
  
 16. EGRESS GATE IS REQUIRED TO HAVE EITHER FIRE EXIT
 HARDWARE OR PANIC HARDWARE, FBC 1008.1.10, 1008.2.
 REVISE PLAN TO INCLUDE THE REQUIREMENT OR DETAIL.
  
 RESPONSE LETTER STATES TO SEE AS102. INDEX SHOWS THE AS
 SERIES BEFORE A SHEETS. UNABLE TO LOCATE SHEET (NOT IN
 THIS LOCATION). COMMENT NOT ADDRESSED.
  
 17. DOOR SCHEDULE HAS A COLUMN FOR ?ELECTRIC? BUT THAT
 COLUMN IS BLANK. IT APPEARS THAT THIS SHOULD BE
 APPLICABLE FOR SLIDING DOORS IN THE REQUIRED MEANS OF
 EGRESS AND EXIT. EXIT DOOR 122 (DOOR TYPE G1) SHOULD
 ALSO COMPLY WITH FBC 1008.1.4.2, 1008.1.4.3.
  
 18. A601 AND G101, DOORS IN FIRE BARRIERS REQUIRE A 45
 MINUTE FIRE RATING, FBC TABLE 715.4. IT IS NOT CLEAR
 WHICH DOORS ARE BEING CONSIDERED IN A CORRIDOR RATHER
 THAN AN OCCUPANCY SEPARATION. SEE DOORS 173C, 182, 172,
 183.
  
 DOOR 173C IS A 20 MINUTE DOOR, BUT THE CORRIDOR 184
 RATING IS NOT CONTINUOUS AS IT APPEARS TO TRANSITION
 INTO THE GALLERY. USE OF CORRIDORS, INCIDENTAL AND
 ACCESSORY USES FBC 508 ARE NOT ENTIRELY CLEAR. IF ANY 1
 HOUR RATINGS ON THE PLAN ARE REMOVED WHEN RESUBMITTING,
 PLEASE ALSO NOTE ALSO SMOKE AND PROTECTION REQUIREMENT
 IN 508.2.5.2.
  
 19. SEE G102 AND OTHER FLOORS, THERE IS AN UNIDENTIFIED
 1 HOUR RECTANGLE ADJACENT TO THE ELEVATOR 2-2. THIS
 AREA IS NOT IDENTIFIED ON A102, A102A. FBC 107, USE OF
 THIS SPACE AND REQUIRED FIRE RESISTANCE RATING NOT
 CLEAR.
  
 20. THE MCKEON DOOR SPECIFIED DOES NOT MEET THE MINIMUM
 REQUIREMENTS OF FBC 715.4. THE DOOR SPEC SHEET STATES
 THAT IT MEETS UL 10B FOR 20 MINUTES. SEE G101, 45
 MINUTE AND 60 MINUTE ARE REQUIRED.
  
 21. PLANS IN MANY LOCATIONS USE THE LANGUAGE "UNDER
 SEPARATE PERMIT" (FOR INSTANCE, SHEET 036 - S6.2). IF
 ALL WORK TO BE INCLUDED IN THIS PERMIT, REVISE
 LANGUAGE.
  
 PLANS STILL REFER TO SEPARATE PERMIT FOR PHASE I AND
 PHASE II. PHASE ONE PLANS REFER TO PHASE TWO AS A
 SEPARATE PERMIT. PHASE TWO REFERS TO PHASE ONE AS A
 SEPARATE PERMIT. SEE OTHER COMMENT REGARDING
 CONSIDERING PUTTING THE TWO PHASES INTO TWO SEPARATE
 PERMITS. IF ALL WORK TO REMAIN UNDER ONE PERMIT, PLEASE
 REVISE LANGUAGE AS IT IS CONFUSING. SEE FBC 107, PLANS
 SHOULD BE CLEAR AS TO SCOPE AND NATURE OF WORK.
  
 22. INCORPORATE FIRE RATING REQUIREMENTS AND DETAILS
 FOR THE FLOOR, STRUCTURAL ELEMENTS FBC TABLE 601.
  
 NOT ADDRESSED. DETAILS SHOWING THE TESTED ASSEMBLY OR
 CALCULATED FIRE RESISTANCE REQUIRED, SEE FBC 703. A
 STATEMENT IN A RESPONSE LETTER THAT EVERYTHING COMPLIES
 IS NOT ADEQUATE TO DEMONSTRATE CODE COMPLIANCE FOR THIS
 HIGH RISE BUILDING.
  
 NOTE THAT THE LIFE SAFETY PLAN, WHICH SHOWS OTHER FIRE
 RESISTANCE RATINGS, IS LACKING INFORMATION REGARDING
 EXTERIOR WALLS AND STRUCTURAL FRAME. PROPOSED FIRE
 RATING FOR THE STRUCTURAL ELEMENTS IS NOT CLEAR. IT IS
 NOT CLEAR WHETHER FBC TABLE 601 OR 602 WILL DETERMINE
 THE EXTERIOR WALL RATINGS.
  
 NEW COMMENTS DUE TO NEW INFORMATION:
  
 23. CLOUDS INDICATING CHANGES FROM REVISION 0 TO
 REVISION 4 HAVE BEEN REMOVED. FOUR VERSIONS OF G101
 HAVE BEEN UPLOADED TO PROJECT DOX. ONE SET WAS NOT
 REVIEWED (VERSION 2) AND IT APPEARS THAT VERSION 3 HAS
 BEEN UPLOADED TWICE.
  
 PLEASE RETAIN ALL CLOUDS FOR CHANGES NOT REVIEWED
 (FUTURE REVISIONS).
  
 24. G101, AREA SCHEDULE (GROSS BUILDING) IS LACKING THE
 TOTAL AND ALSO LACKS THIRD THROUGH SEVENTH FLOOR, FBC
 107, FBC 107.
  
 25. G101, AT 3 HOUR FIRE WALL, PLAN STATES THAT 1 HOUR
 FIRE PROTECTION IS REQUIRED (EXTENDED 4 FT FROM FIRE
 WALL). SEE FBC TABLE 601 AND 602; BASED ON OTHER MORE
 STRINGENT REQUIREMENTS, 1 HOUR DOES NOT APPEAR TO BE
 SUFFICIENT. BEARING WALLS ARE TO BE 3 HOURS. SEE OTHER
 COMMENT REGARDING FIRE RATING DETAILS.
  
 26. A352, PT WOOD AND EXT PLYWOOD IS SHOWN. SEE FBC
 603, 717.5, 718.3, IT APPEARS THAT THERE IS AN
 EXCESSIVE AMOUNT OF COMBUSTIBLE, NON FRT LUMBER
 INSTALLED AT 130 FT. EITHER REVISE TO NON COMBUSTIBLE
 MATERIALS OR PROVIDE RATIONALE OR EXCEPTION.
  
 27. G101, ROOM TO THE NORTH OF AIR HANDLER ROOM 180 IS
 NOT LABELED.
  
 28. G101, THE DINING ROOM EGRESS (SOUTH EAST CORNER OF
 DISPLAY KITCHEN DINING B) PATH TO WOUTH EXIT GOES
 THROUGH A WALL, SEE THE L SHAPE AREA BETWEEN NORTH
 WALLS OF OFFICE 163C AND DRY STORAGE 166. REVISE OR
 CLARIFY.
  
 29. SP AND WF SHEETS, NEW POOL AND WALL FOUNTAIN PLANS
 WERE SUBMITTED. THEY HAVE NOT BEEN REVIEWED AT THIS
 TIME AND REQUIRE SEPARATE PERMITS. HOWEVER, IN TAKING A
 CURSORY GLANCE AT THE PLANS, IT APPEARS THAT THE POOL
 WAS DESIGNED TO FBC 2010 RESIDENTIAL DUE TO THE FBC
 2010 RESIDENTIAL REFERENCES ON THE PLANS.
  
 30. ENERGY CALCS WERE SUBMITTED. INCLUDED ON THE ENERGY
 CALCS IS A GAS HOT WATER BOILER, BETWEEN 300,000 AND
 2.5 MILLION BTUS. SEE FBC 1015.3 REGARDING EXITING
 REQUIREMENTS FOR BOILER ROOMS. WHERE IS THIS BOILER
 LOCATED? IT IS NOT SHOWN ON THE LIFE SAFETY PLAN, FBC
 107. REVISE OR CLARIFY.
  
 31. REVISED SHEET G101 SHOWS TRAVEL DISTANCE AS 130FT
 FROM THE FITNESS LOUNGE TO THE EXIT ENCLOSURE. SEE THE
 DEFINITION OF CORRIDOR, FBC 1002, AN ENCLOSED EXIT
 ACCESS COMPONENT THAT DEFINES AND PROVIDES A PATH OF
 EGRESS TRAVEL TO AN EXIT.
  
 SEE ALSO DEFINITION OF EXIT ENCLOSURE, AN EXIT
 COMPONENT THAT IS SEPARATED FROM OTHER INTERIOR SPACES
 OF A BUILDING OR STRUCTURE BY FIRE RESISTANCE RATED
 CONSTRUCTION AND OPENING PROTECTIVES. MANY ROOMS ARE
 INCLUDED IN THE GALLERY (HOUSEKEEPING, LIVING ROOM,
 ELEVATOR LOBBIES, TOILET ROOMS, ETC.). DEFINITION
 STATES THAT AN EXIT ENCLOSURE IS TO BE SEPARATED FROM
 OTHER INTERIOR SPACES.
  
 THIS COMMENT ALSO APPLIES TO THE RESIDENTIAL AREA
 EXITING. RESIDENTIAL CORRIDOR TAKES THE OCCUPANT
 THROUGH THE 1 HOUR RATED CORRIDOR THROUGH THIS GALLERY
 AREA, NOW CALLED AN EXIT ENCLOSURE, BUT THE GALLERY AS
 SHOWN ON G101 DOES NOT MEET THE DEFINITION OF AN EXIT
 ENCLOSURE. AN EXIT ENCLOSURE IS TO BE SEPARATED FROM
 OTHER INTERIOR SPACES. ONCE AN OCCUPANT ENTERS THE
 EXIT, THE EXIT IS TO BE CONTINUOUS UNTIL THE EXIT
 DISCHARGE.
  
 32. CHANGES TO THE PROPERTY LINE (REPLAT) REQUIRE THAT
 COMPLIANCE WITH FBC TABLE 705.8 (MAXIMUM AREA OF
 EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION
 DISTANCE) AND FBC TABLE 602 (FIRE RESISTANCE RATING
 REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE
 SEPARATION DISTANCE) BE SHOWN. A REVISION WILL BE
 REQUIRED PRIOR TO CERTIFICATE OF COMPLETION.
  
 33. REVISE SHEET G001, REQUIRED FIRE RESISTIVE RATINGS.
 DISTANCE TO PROPERTY LINE IS FOR GREATER THAN 30FT
 SEPARATION. AS THERE IS A PROPERTY LINE BETWEEN THE TWO
 BUILDINGS, THIS IS NOT ACCURATE. DUE TO THE EXCEPTION
 FOR ONE STORY (1 HOUR REDUCTION FBC TABLE 601 FOOTNOTE
 A), DISTANCE TO PROPERTY LINE (FBC TABLE 602) APPEARS
 TO BE MORE RESTRICTIVE (2 HOUR REEQUIRED FROM 5 FEET TO
 UNDER 20 FEET).
  
 34. THRESHOLD PLAN STATEMENT REQUIRED BY FS 553.79 TO
 BE CORRECTED ON STRUCTURAL DRAWINGS. EVIDENCE THAT THIS
 HAS BEEN CORRECTED IS TO BE SENT TO ME VIA EMAIL PRIOR
 TO PERMIT ISSUANCE. PLANS ARE TO BE SUBMITTED AS A
 REVISION PRIOR TO COMMENCEMENT IF PERMIT IS ISSUED THIS
 REVIEW CYCLE. IF PERMIT IS NOT ISSUED IN THIS REVIEW
 CYCLE, REVISED DRAWINGS TO BE RESUBMITTED. (EMAIL
 RECEIVED FROM STRUCTURAL ENGINEER ON 8/18/15)
  
 35. AS ALL STRUCTURAL SHEETS ARE REQUIRED TO BE
 REVISED, SEE PREVIOUS LIST REGARDING THE ADDRESS ON THE
 PLAN AND REVISE. STRUCTURAL SHEETS STILL HAVE INCORRECT
 ADDRESS OF 4920 LORING DRIVE.
  
 36. UNIT 1A, SHOW CLEAR FLOOR SPACE CENTERED ON SINK,
 SHEET A 401A.
  
 37. AS 109, POOL BAR AREA, CLARIFY PURPOSE THIS AREA;
 IS THIS FOR STAFF ONLY (WORK AREA), OR FOR USE BY
 RESIDENTS AND THEIR GUESTS? THERE IS A STATEMENT ON THE
 PLAN WHICH STATES THAT AMENITY SPACES AND COMMON AREAS
 ARE ONLY USED BY RESIDENTS AND THEIR GUEST. THERE ARE
 OFFICES, SPA, LARGE RESTAURANT STYLE DINING AREA, BUT
 THE PLAN DOES NOT INDICATE WHICH AREAS ARE FOR USE BY
 EMPLOYEES.
  
 IT IS NOT CLEAR WHETHER ACCESSIBILITY OR FAIR HOUSING
 APPLIES. MORE INFORMATION REQUIRED; NO CLEAR FLOOR
 SPACE SHOWN FOR FIXTURES, SINK AND COUNTER ARE AT 40
 INCHES. WILL FOOD OR DRINKS BE SOLD AT THIS LOCATION?
 SEE FBC 2010 ACCESSIBILITY 804, 902, 904, 606, CFR
 100.205(C)(1).
  
 38. BREAK ROOM APPEARS TO BE FOR EMPLOYEE USE. SINK TO
 COMPLY WITH FBC 2010 ACCESSIBILITY 606.
  
 39. SEE PLUMBING COMMENTS REGARDING OTHER ACCESSIBILITY
 AND FAIR HOUSING AND REVISE PLAN TO SHOW APPLICABLE
 DIMENSIONS.
  
 40. SEE FIRE REPEAT COMMENT REGARDING FBC 403.3.2,
 SHEET 402, FIRE PUMP SHALL BE SUPPLIED BY A MINIMUM OF
 TWO WATER MAINS LOCATED IN DIFFERENT STREETS. AS WITH
 THE STRUCTURAL SHEETS, REVISE AND PROVIDE EVIDENCE VIA
 EMAIL THAT THIS ITEM HAS BEEN ADDRESSED.
 *****************************
 PROVISOS
 ISSUED AT CONTRACTOR'S RISK
  
 1. AS PER OWNER?S AGREEMENT, A REPLAT WILL BE FILED
 WITHIN 45 DAYS OF PERMIT ISSUANCE. FINAL PLAT REQUIRED
 PRIOR TO C.O. A NEW SITE PLAN SHOWING DISTANCE TO THE
 NEW PROPERTY LINE TO BE SUBMITTED FOR REVIEW AS A
 REVISION.
  
 2. ADVISORY ONLY, SEPARATE PERMITS (PLANS, APPLICATION,
 REVIEWS, AND FEES) REQUIRED FOR PARKING LOT, SIGNAGE,
 AWNINGS, FENCING, POOL, TRELLIS, SITE WALL, SEPARATE
 BUILDINGS (INCLUDING GENERATOR BUILDING), FBC 107.
  
 3. THE FOLLOWING SHEETS HAVE BEEN VOIDED AND WERE NOT
 REVIEWED: SP101, SP102, SP103, SP104, SP105, SP106,
 WF101, WF102, AND WF103. SUBMIT THESE PAGES UNDER
 SEPARATE PERMIT APPLICATION.
  
 4. ADVISORY ONLY, THE ART IN PUBLIC PLACES WAS SENT VIA
 EMAIL, CITY OF WEST PALM BEACH CODE OF ORDINANCES
 78-123, 78-126.
  
 THIS PERMIT WILL BE ISSUED WITH THE PROVISO THAT,
 WITHIN 90 DAYS OF ISSUANCE, THE APPROVAL WILL BE
 PROVIDED. PLEASE SEND A COPY OF THE APPROVAL WHEN
 AVAILABLE VIA EMAIL TO [email protected] IN ORDER TO
 DOCUMENT THE PERMIT FILE.
  
 5. ADVISORY ONLY, FS 553.79(7)(C) ALL SHORING AND
 RESHORING PROCEDURES, PLANS, AND DETAILS BE SUBMITTED
 TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING.
 SHORING/RESHORE ENGINEERING TO BE SUBMITTED AT EACH
 LIFT. FAILURE TO SUBMIT SHORING/RESHORE PLANS TO THE
 BUILDING DIVISION FOR PLAN REVIEW AT THE TIME OF EACH
 LIFT MAY RESULT IN A STOP WORK ORDER. AS THIS ISSUE HAS
 BEEN PROBLEMATIC IN THE PAST, IT IS RECOMMENDED THAT A
 NOTE BE INCORPORATED INTO THE PLAN.
  
 6. ADVISORY ONLY, PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED FOR REVIEW PRIOR
 TO INSTALLATION, FBC 107, FBC 1609 (SUBMITTAL, NO FEE).
 COMPONENTS AND CLADDING TO COMPLY WITH WALL PRESSURES
 SHOWN ON SHEET S8.5:
  
 ZONE 4 + 52.0 / - 52.2
 ZONE 5 + 52.0 / -95.7
  
 FOR ROOF COVERING, SEE ROOF PLAN REVIEW STOP OR SHEET
 S8.5 FOR PRESSURES.
  
 8. PROVISO, FBC 911.1.4, LAYOUT OF FIRE COMMAND CENTER
 AND ALL FEATURES REQUIRED BY 911.1.5 TO BE SUBMITTED
 AND APPROVED PRIOR TO INSTALLATION.
  
 9. PROVISO, G101 AND A213, THE DOORS FOR THE MULTI
 PURPOSE ROOM INCLUDE SIDELIGHTS WHICH APPEAR TO BE
 IDENTICAL TO THE DOORS BUT DO NOT OPERATE. SEE FBC
 1008.1, DOORS TO BE EASILY DISTINGUISHABLE FROM THE
 INOPERABLE SIDELITES.
  
 10. PROVISO, THE FOLLOWING TEST REPORTS FOR THE
 FLOORING UNDERLAYMENT WILL BE REQUIRED PRIOR TO
 INSTALLATION (INFORMATIONAL NOTE: PER S2.4, S3.1 FLOOR
 SLABS ARE 8IN, SO STC AND IIC TESTS ON AN 8IN SLAB OR
 LESS ARE ACCEPTABLE): STC (FBC 1207.2), IIC (FBC
 1207.3), ASTM E 84 (FBC 603.1).
  
 11. PROVISO, FBC 2010 ACCESSIBILITY 703, SIGNS TO
 COMPLY WITH THIS SECTION.
  
 12. PROVISO, DETAILS FOR UL ASSEMBLIES REFERENCED ON
 THE PLANS ARE TO BE SUBMITTED WITH OPTIONS NOTED PRIOR
 TO INSTALLATION. IF NOT PREPARED BY DESIGNER OF RECORD,
 SHOP DRAWING REVIEW REQUIRED PRIOR TO SUBMITTAL.
  
 AS THE EXTERIOR WALLS ARE FIRE RATED, DETAILS FOR
 STRUCTURE AND EXTERIOR WALLS REQUIRED PRIOR TO
 COMMENCEMENT.
  
 13. PROVISO, REVISED PLANS TO INCLUDE TOTAL SQUARE FOOT
 AREA, PER FLOOR, PER OCCUPANCY CLASSIFICATION, TO
 INCLUDE BOTH PHASE I AND PHASE II, FBC 107, FBC 109.
 VALUE (ADJUSTED PER ICC TABLE AND COTLEUR & HEARING
 SITE PLAN) WILL BE CONFIRMED AND MAY BE INCREASED.
 ISSUED AT CONTRACTOR'S RISK.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-05-18 Cont ID  
Sent By S. Hill Date 2015-05-18 Time 14:50 Rev Time 0.00
Received By shill Date 2015-05-04 Time 14:11 Sent To  
Notes
2015-05-18 14:50:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 2010 FLORIDA BUILDING CODE
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
  
 1. FOR ALL THRESHOLD JOBS, FS 553.79(7)(D) ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO BE SIGNED AND
 SEALED BY THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A
 STATEMENT THAT, TO THE BEST OF THE ARCHITECT?S OR
 ENGINEER?S KNOWLEDGE, THE PLANS AND SPECIFICATIONS
 COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND
 THE APPLICABLE FIRESAFETY STANDARDS AS DETERMINED BY
 THE LOCAL AUTHORITY IN ACCORDANCE WITH THIS CHAPTER AND
 CHAPTER 633.
  
 PLEASE INCORPORATE THIS STATEMENT INTO THE PLANS. IT IS
 TYPICAL FOR THIS STATEMENT TO BE ON EACH SHEET. IF
 DESIGNER OBJECTS TO INCLUDING THIS STATEMENT ON EACH
 SHEET AND WOULD LIKE THE STATEMENT ON ONE SHEET ONLY,
 PLEASE ADVISE AND THIS OPTION WILL BE INVESTIGATED WITH
 THE APPROPRIATE BOARD.
  
 2. IT IS NOT CLEAR WHETHER THE NEW BUILDING WILL BE
 CONSIDERED AN ADDITION TO THE EXISTING BUILDING, ON THE
 SAME PARCEL, CONNECTED BY A WALKWAY, OR IF WILL BE
 TREATED AS A NEW BUILDING, SEPARATE PARCEL, OR NEW
 BUILDING, SAME PARCEL (WITH UNITY OF TITLE, SEE OTHER
 COMMENTS).
  
 IF THE TWO TOWERS ARE DESIGNED AS ONE BUILDING,
 DESIGNER TO REFERENCE FBC 2010 EXISTING BUILDING
 CHAPTER 10 (ADDITIONS) AS WELL AS METHOD OF COMPLIANCE
 FOR THE EXISTING BUILDING (SEE FBC 2010 EXISTING
 BUILDING 101.5). THIS IS REQUIRED IN ORDER TO ADDRESS
 ISSUES AS THEY ARISE EITHER IN THE FIELD OR IN PLAN.
  
 3. CHIEF BUILDING INSPECTOR AGREES THAT, IF ALL PARTIES
 FOR THE TWO PROJECTS (DINING ROOM EXPANSION AND PHASE
 I, 14120908 AND 14120909) ARE THE SAME, ONE SET OF
 THRESHOLD DOCUMENTS (RESUMES, AGREEMENTS) IS
 ACCEPTABLE. IF THIS IS NOT ACCEPTABLE TO ANY OF THE
 PARTIES, PLEASE CONTACT ME TO DISCUSS.
  
 THRESHOLD DOCUMENTS REQUIRED:
  
 SPECIAL INSPECTOR AGREEMENT
 RESUME AND COPIES OF LICENSES FOR SPECIAL INSPECTOR AND
 ALL ON SITE INSPECTORS
 RESUME AND COPIES OF LICENSES FOR CONTRACTOR, JOB
 SUPERINTENDENT AND/OR PROJECT MANAGER
  
 4. THE BUSINESS LICENSE NUMBER, NAME AND ADDRESS SHOWN
 ON THE PLAN (PERKINS EASTMAN, FS95000000559,
 PITTSBURGH, PA) ARE NOT CONSISTENT WITH DBPR RECORDS
 (PERKINS EASTMAN ARCHITECTS, D.P.C., INC, AA26000763,
 NEW YORK, NY). SINCE THE ADDRESS, NAME, AND LICENSE
 NUMBER ARE DIFFERENT FROM DBPR RECORDS, IT IS NOT
 POSSIBLE TO DETERMINE THE ARCHITECT (COMPANY) TAKING
 RESPONSIBILITY FOR THE DESIGN.
  
 SEE FS 481.219, CERTIFICATE OF AUTHORIZATION REQUIRED
 AND THE NUMBER IS TO BE ON ALL FINAL CONSTRUCTION
 DOCUMENTS.
  
 HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/PRO/ARCH/STATUTES.
 HTML
  
 5. PAPA RECORDS SHOW A PROPERTY LINE WHICH IS NOT SHOWN
 ON THE PLANS SUBMITTED. WILL THE TWO PROPERTIES REMAIN
 SEPARATE PARCELS, HAVE THEY ALREADY BEEN COMBINED WITH
 A UNITY OF TITLE, OR WILL THEY BE COMBINED WITH A UNITY
 OF TITLE? IF THEY ARE TO REMAIN SEPARATE PARCELS, SEE
 FBC TABLE 602, TABLE 705.8 AND REVISE PLAN TO SHOW
 COMPLIANCE (DISTANCE TO PROPERTY LINE, RATED WALLS AS
 APPLICABLE, PROTECTED OPENINGS IF PERMITTED).
  
 IT APPEARS THAT THE PROPERTY LINE BETWEEN 4920 LORING
 DRIVE AND 4850 LORING DRIVE DIVIDES THE NEW BUILDING
 KNOWN AS TRADITIONS II PHASE ONE.
  
 THE DISTANCE OF PROPOSED BUILDING TO THE ACTUAL
 PROPERTY LINE (AS PER PAPA, NOT SHOWN ON PLANS) IS
 UNCLEAR.
  
 IF YOU HAVE NOT ALREADY SUBMITTED APPLICATION FOR UNITY
 OF TITLE AND WISH TO DO SO, THE APPLICATION IS
 AVAILABLE ONLINE:
  
 HTTP://WPB.ORG/WP-CONTENT/UPLOADS/SITES/7/2012/05/2011-
 11-14-16-09-54-APPLICATIONFORUNITYOFTITLE.PDF
  
 6. THE ADDRESS ASSIGNED TO THIS BUILDING IS 4850 LORING
 DRIVE; PLEASE REVISE PLANS AS APPLICABLE.
  
 7. FS553, AS PERMITS 14120908 AND 14120909 WERE
 INITIALLY FOUNDATION PERMITS, PLEASE PROVIDE NEW
 APPLICATIONS WITH THE NEW SCOPE OF WORK AND VALUE,
 SIGNED BY THE QUALIFIER AND THE OWNER. ALSO PLEASE NOTE
 THAT IT APPEARS THAT THE NEW BUILDING (TRADITIONS II
 PHASE ONE) IS LOCATED PRIMARILY ON A PARCEL WITH AN
 ADDRESS OF 4850 LORING DRIVE, LOCATED ON TRACT C,
 PARCEL ID 74-42-43-12-26-003-0000.
  
 8. SEPARATE PERMITS (PLANS, APPLICATION, REVIEWS, AND
 FEES) REQUIRED FOR PARKING LOT, SIGNAGE, FENCING, POOL,
 TRELLIS, FBC 107.
  
 9. ADVISORY ONLY, THE ART IN PUBLIC PLACES WAS SENT VIA
 EMAIL, CITY OF WEST PALM BEACH CODE OF ORDINANCES
 78-123, 78-126.
  
 THIS PERMIT WILL BE ISSUED WITH THE PROVISO THAT,
 WITHIN 90 DAYS OF ISSUANCE, THE APPROVAL WILL BE
 PROVIDED. PLEASE SEND A COPY OF THE APPROVAL WHEN
 AVAILABLE VIA EMAIL TO [email protected] IN ORDER TO
 DOCUMENT THE PERMIT FILE.
  
 10. ADVISORY ONLY, FS 553.79(7)(C) ALL SHORING AND
 RESHORING PROCEDURES, PLANS, AND DETAILS BE SUBMITTED
 TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING.
 SHORING/RESHORE ENGINEERING TO BE SUBMITTED AT EACH
 LIFT. FAILURE TO SUBMIT SHORING/RESHORE PLANS TO THE
 BUILDING DIVISION FOR PLAN REVIEW AT THE TIME OF EACH
 LIFT MAY RESULT IN A STOP WORK ORDER. AS THIS ISSUE HAS
 BEEN PROBLEMATIC IN THE PAST, IT IS RECOMMENDED THAT A
 NOTE BE INCORPORATED INTO THE PLAN.
  
 11. ADVISORY ONLY, PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED FOR REVIEW PRIOR
 TO INSTALLATION IF NOT SUBMITTED AT THIS TIME, FBC 107,
 FBC 1609 (SUBMITTAL, NO FEE).
  
 12. ADVISORY ONLY, POOL DETAILS NOT REVIEWED AT THIS
 TIME. POOL WILL BE REVIEWED UNDER A SEPARATE PERMIT,
 FBC 107.
  
 13. FOR TRACKING PURPOSES, A SEPARATE PERMIT IS
 REQUIRED FOR THE DETACHED GENERATOR BUILDING, FBC 107.
  
 14. ADVISORY ONLY, AT THIS TIME, THE "R" (ROOFING) STOP
 HAS A REVIEW STATUS OF "N". PRODUCT APPROVALS AND
 ENGINEERING, IF APPLICABLE, WILL BE REQUIRED AT TIME OF
 ROOF SUB PERMIT APPLICATION IF NOT SUBMITTED DURING THE
 PLAN REVIEW PROCESS FOR THE ADDITION.
  
 15. ADVISORY ONLY; PARKING LOT STRIPING, AWNINGS, SIGNS
 AND OTHER INDEPENDENT STRUCTURAL ELEMENTS REQUIRE
 SEPARATE PERMITS WHICH WOULD INCLUDE FEES, BUILDING
 PERMIT APPLICATIONS, PLANS AND REVIEWS.
  
 16. FBC 107, AN INDEX LOCATED AT THE BEGINNING OF THE
 DIGITAL ROLL OF PLANS WOULD BE HELPFUL. THE PLANS ARE
 ORDERED IN THIS MANNER:
  
 INDEX FOR PHASE I FOR ARCH/STRUCTURAL ONLY
 PHASE I PAGES FOR LIFE SAFETY, CIVIL, LANDSCAPE,
 STRUCTURAL, DEMO, SITE, ARCH
 INDEX FOR PHASE II FOR ARCH/STRUCTURAL ONLY
 PHASE I PAGES FOR LIFE SAFETY, CIVIL, LANDSCAPE,
 STRUCTURAL, DEMO, SITE, ARCH
 FMEP INDEX FOR PHASE II
 FMEP SHEETS
 FMEP INDEX FOR PHASE I
 FMEP INDEX
  
 SINCE THERE ARE 577 PLAN PAGES FOR THIS PROJECT, PLEASE
 PROVIDE AN INDEX AT THE BEGINNING OF THE DIGITAL ROLL.
 ALTHOUGH A COMPLETE SHEET INDEX IS NOT REQUIRED, AN
 INDEX WHICH SHOWS THE SERIES ORDER WOULD BE HELPFUL,
 ESPECIALLY AS PHASE II FMEP PAGES ARE LOCATED BEFORE
 PHASE I FMEP.
  
 17. FBC 107, SHEET WHICH IS LABELED 201 - A626.PDF IS
 IN THE MIDDLE OF THE CIVIL SHEETS FOR PHASE II. PLEASE
 COORDINATE TO HAVE THIS PAGE RELOCATED SO IT IS IN
 NUMERICAL ORDER, ARCHITECTURAL SHEETS.
  
 THIS ALSO APPLIES TO SHEETS:
 202 ? A630 (BETWEEN L AND S SHEETS, PHASE II)
 204 - A642
 206 - A644
 209 - IN101C
 210 - IN101D
 2-110 ? G000B
  
 THIS MAY NOT BE A COMPLETE LIST. CHECK ALL PRIOR TO
 RESUBMITTAL. DUE TO NAMING CONVENTION, THE SERIES OF
 SHEETS DO NOT APPEAR IN THE ORDER ON THE DRAWING
 SCHEDULE, AND FMEP ARE NOT INCLUDED (HAVE THEIR OWN
 INDEXES). DUE TO THE SIZE OF THIS PLAN, WHILE NOT
 REQUIRED TO BE IN ORDER OF THE INDEX (ALTHOUGH THAT
 WOULD BE HELPFUL), THE SERIES SHOULD BE TOGETHER AND IN
 THE ORDER ON THE INDEX FOR THAT SERIES.
  
 18. FBC ENERGY CONSERVATION 103.2.1.2, ENERGY CALCS
 REQUIRED.
  
 19. G001, IT APPEARS THAT THE PROPOSED BUILDING WILL BE
 USED AS EITHER ASSISTED LIVING OR INDEPENDENT LIVING
 WHICH ARE REGULATED BY FAIR HOUSING ACT, FBC 2010
 ACCESSIBILITY. SHEET G001 HAS A LINE WHICH STATES THAT
 PER 11 9.1.4, NINE UNITS ARE REQUIRED TO BE ACCESSIBLE.
 PLEASE REVISE THIS INFORMATION TO CLARIFY. IF THIS IS
 EITHER ASSISTED LIVING OR INDEPENDENT LIVING,
 ACCESSIBILITY DOES NOT APPLY TO THE RESIDENTIAL PORTION
 OF THE BUILDING, BUT APPLIES TO PORTIONS OF THE AMENITY
 AND BUSINESS AREAS. ALSO, THIS REFERENCE APPEARS TO BE
 FROM FBC 2007; THIS SPECIFIC SECTION IS FOR TRANSIENT
 LODGING. PER FAIR HOUSING, ALL UNITS ARE TO CONSIDERED
 COVERED UNITS AND ARE TO COMPLY WITH THE REQUIREMENTS
 IN SECTION 3, 100.205 C.
  
 IF THE UNITS ARE NOT EITHER INDEPENDENT OR ASSISTED
 LIVING UNITS, PLEASE REVISE PLAN TO CLARIFY.
  
 20. UNIT PLANS HAVE NOT BEEN REVIEWED AS ALL
 INFORMATION PROVIDED INDICATES THAT THEY ARE SUBJECT TO
 FAIR HOUSING, BUT NO INFORMATION REGARDING WAS PROVIDED
 ON THE UNIT PLANS, AND ACCESSIBLE UNITS ARE SHOWN. A
 REVIEW CANNOT BE DONE WITHOUT MORE INFORMATION, FBC
 107.
  
 21. PHASE II SHEET A101, CLARIFY USE OF GUEST ROOM 105
 (REVISE PLAN TO INCLUDE INTENDED USE). IF THIS IS A
 ROOM AVAILABLE FOR RENT, IT APPEARS THAT THIS UNIT
 WOULD BE SUBJECT TO ALL REQUIREMENTS OF FBC 2010
 ACCESSIBILITY. ALSO, ONE PUBLIC ACCOMODATION ROOM MAY
 CAUSE OTHER AREAS (SUCH AS THE POOL) TO BE SUBJECT TO
 ACCESSIBILITY (IN PARTICULAR, SEE FBC 2010
 ACCESSIBILITY 1004, 1009).
  
 22. G001, REQUIREMENTS ARE STATED BUT SOME THINGS ARE
 NOT CLEAR AS TO JOB SPECIFIC APPLICABLILITY. WILL THIS
 BUILDING BE CONSIDERED AN ADDITION TO THE EXISTING
 RESIDENTIAL TOWER (TRADITION 1), OR IS IT DESIGNED AS A
 SEPARATE BUILDING? SHOW COMPLIANCE WITH FBC 2010 TABLE
 503. NO INFORMATION PROVIDED REGARDING THE EXISTING
 BUILDING.
  
 EITHER THIS IS ONE LARGE BUILDING (PROVIDE INFORMATION
 REGARDING THE EXISTING BUILDING) OR TWO SEPARATE
 BUILDINGS WITH AN ASSUMED PROPERTY LINE (SHOW
 COMPLIANCE FBC 705.3. REVISE PLAN TO CLARIFY.
  
 23. G101, IF TRADITION 1 AND TRADITION II ARE SEPARATE
 BUILDINGS, A 2 HOUR FIRE WALL IS SHOWN, 3 HOURS
 REQUIRED PER FBC TABLE 706.4.
  
 24. G101, IF TRADITION 1 AND TRADITION II ARE SEPARATE
 BUILDINGS, THE FIRE WALL IS TO COMPLY WITH THE
 REQUIREMENT OF 706.2, STRUCTURAL INTEGRITY.
  
 25. G101, CLARIFY THE EXIT STRATEGY FOR THE CONNECTING
 DOOR BETWEEN TRADITION I AND II. IF THIS IS AN EXIT FOR
 BOTH SIDES, HOW WILL THE DOOR SWING IN BOTH DIRECTIONS,
 AND HOW WOULD YOU CONTROL CONFLICTS SUCH AS OCCUPANTS
 TRAVELING IN OPPOSITE DIRECTIONS? IT IS NOT CLEAR HOW
 THE FIRE WALL WILL ALLOW OCCUPANTS TO PASS THROUGH. IF
 THIS IS TO BE A MCKEON DOOR, IT IS NOT CLEAR HOW THIS
 WILL MEET THE STRUCTURAL INTEGRITY REQUIREMENT.
  
 REVISE PLAN TO INCLUDE A DETAIL FOR THE PROPOSED FIRE
 WALL AND CLARIFY THE ABOVE CONCERNS, FBC 107.
  
 26. G101, CORRIDOR 187 IS NOT A RATED CORRIDOR BUT
 SERVES THE RESIDENTIAL UNITS AS THERE IS AN EXIT SIGN
 FROM CORRIDOR 188 TO CORRIDOR 187, FBC TABLE 1018.1.
 THERE IS A NOTE WHICH STATES THAT TRAVEL DISTANCE IS
 134FT, BUT IT IS NOT CLEAR WHERE THIS IS APPLICABLE.
  
 27. A101, FBC 1022.4, STAIR 1, OPENINGS INTO THE STAIR
 ARE LIMITED TO THOSE REQUIRED FOR EXITING. THE
 RATIONALE FOR HAVING AN EXIT FOR THE CHILLERS GO
 THROUGH THE EXIT FOR THE RESIDENTIAL IS NOT CLEAR; IF
 TWO EXITS ARE REQUIRED FROM THIS SPACE, IT APPEARS THAT
 THERE IS ENOUGH ROOM TO ADD A DOOR IN ANOTHER LOCATION.
  
 28. SOME MECHANICAL SHEETS DO NOT SHOW THE REQUIRED
 FIRE RATING (FBC708) FOR THE ADJACENT SHAFT FOR THE
 PRESSURIZED STAIRS (FOR INSTANCE, 305 M202A), PLEASE
 CORRELATE.
  
 29. G001 MAKES REFERENCE TO THE EXCEPTION FOR A 1 HOUR
 SHAFT RATING PER FBC 403.2.1.2. INCORPORATE THIS
 REQUIREMENT INTO THE FIRE PROTECTION SHEETS. A BUILDING
 REVIEW WILL BE DONE IN ADDITION TO FIRE AND MECHANICAL
 REVIEWS WHEN THE FIRE SPRINKLER PERMIT APPLICATION AND
 PLANS ARE SUBMITTED. NOTE THAT FLOOR PLANS SHOW A 2
 HOUR SHAFT RATING. CLARIFY WHERE THIS EXCEPTION WILL
 APPLY. IF THIS EXCEPTION DOES NOT APPLY, REMOVE FROM
 PLAN AND ADVISE.
  
 30. G101 AND OTHER PAGES, REVISE LIFE SAFETY PLAN TO
 SHOW EXIT DISCHARGE TO THE PUBLIC WAY FOR ALL EXITS.
  
 EXIT DISCHARGE NOT CLEAR FOR THE EXITS WHICH OPEN TO
 THE POOL AREA AND FOR THE EXITING FROM CORRIDOR THROUGH
 THE DINING ROOM EXTENSION, FBC 1027. EXIT STRATEGY IS
 NOT CLEAR. SEE FIRE COMMENTS. SEE ALSO 1004.8 (OUTDOOR
 AREAS), 1006.1.1 (ILLUMINATION). TWO REQUIRED EXITS
 FROM DINING ROOM OPEN INTO THE POOL AREA. THE POOL AREA
 ITSELF HAS A HIGH OCCUPANT LOAD. IT IS NOT CLEAR HOW
 HUNDREDS OF OCCUPANTS WILL TRAVEL FROM THE POOL AREA TO
 THE PUBLIC WAY; ONLY A SMALL GATE IS SHOWN AND THE
 OCCUPANTS WILL HAVE TO CROSS AN AREA MARKED FOR THE
 FIRE TRUCK.
  
 OTHER EXITS SHOW SIDEWALKS BUT ACCESS TO THE PUBLIC WAY
 (OR OTHER APPROVED AREA) IS NOT CLEAR. FOR INSTANCE,
 FP001 SHOWS A SIDEWALK FOR EXIT STAIRS 3 AND 4 WHICH
 LEADS BACK INTO THE BUILDING.
  
 31. G101, STAIR 4, FBC 1022.6, IN ORDER TO FACILITATE
 PHASE II, THE EXTERIOR WALL IS TO BE FIRE RESISTANCE
 RATED (LESS THAN 180DEGREES WHEN PHASE II IS BUILT).
  
 32. G101, THEATER VESTIBULE AND MULTIPURPOSE ROOM (ALSO
 REFERRED TO AS THEATER ON SHEET G001, USE GROUP
 CLASSIFICATION) IS SHOWN AS GROUP A1. SHEET G001 ALSO
 REFERS TO MULTIPURPOSE AS A3.
  
 33. A101, SHOW 18IN MANEUVERING CLEARANCE PULL SIDE,
 FOR THE FOLLOWING DOORS PER FBC 2010 ACCESSIBILITY
 404.2.4:
  
 AEROBICS ROOM 146
 ACCESSIBLE CHANGING ROOM 149
  
 34. A101A, WHEN RESUBMITTING, INCLUDE SEATING PLAN FOR
 THE MULTIPURPOSE ROOM.
  
 NOTE: SEATING REVIEWED IN PLANGRID, A101A. FORTY SEVEN
 FIXED SEATS SHOWN, OCCUPANT LOAD IS 51.
  
 REVISE PLAN TO INCLUDE INFORMATION REGARDING THE USE OF
 THIS SPACE. WILL THIS BE ONLY FOR RESIDENTS AND THEIR
 GUESTS (FAIR HOUSING), OR WILL TICKETS EVER BE SOLD TO
 THE GENERAL PUBLIC (ACCESSIBILITY)?
  
 NO ACCESSIBLE SEATING IS SHOWN. SEE FBC 2010
 ACCESSIBILITY 802 REGARDING WHEELCHAIR SPACES, SIGHT
 LINES, AND COMPANION SPACES REQUIRED. REVISE PLAN TO
 CLARIFY COMPLIANCE FOR ACCESSIBILITY OR FAIR HOUSING
 (REQUIREMENT THAT ALL PUBLIC AND COMMON USE AREAS ARE
 READILY ACCESSIBLE TO AND USABLE BY DISABLED PERSONS)
 AS APPLICABLE.
  
 35. EXERCISE AREAS, MULTIPURPOSE ROOM (SEE OTHER
 COMMENT), SALON, SPA, POOL, DINING, GUEST ROOM, ALL
 COMMON AREAS, REVISE PLAN TO INDICATE WHETHER THESE
 AREAS ARE FOR RESIDENTS AND THEIR GUESTS ONLY (SUBJECT
 TO FAIR HOUSING ONLY) OR IF THE PORTION OF THE FACILITY
 IS OPEN TO NON RESIDENTS FOR A FEE, OR AVAILABLE FOR
 EMPLOYEE USE (SUBJECT TO ACCESSIBILITY AS WELL AS FAIR
 HOUSING).
  
 36. G101 AND A213, THE DOORS FOR THE MULTI PURPOSE ROOM
 INCLUDE SIDELIGHTS WHICH APPEAR TO BE IDENTICAL TO THE
 DOORS BUT DO NOT OPERATE. SEE FBC 1008.1, REVISE PLAN
 TO SHOW HOW THE DOORS WILL BE EASILY DISTINGUISHABLE
 FROM THE INOPERABLE SIDELITES.
  
 37. G101 OR RELATED A SHEET, REVISE PLAN TO INCLUDE
 INFORMATION REGARDING WHAT WILL BE STORED IN THE
 CHEMICAL ROOM 137A (ASSOCIATED WITH SALON), FBC 107,
 FBC 307. PLAN SHOULD INCLUDE A BRIEF DESCRIPTION OF
 CHEMICALS TO BE STORED AND, IF ANY CHEMICALS ARE THOSE
 LISTED IN FBC307, INCLUDE CHEMICAL AND AMOUNT TO SHOW
 THAT IT IS BELOW THE ALLOWABLE LIMIT.
  
 38. G101, AEROBICS 146 AND FITNESS 143 APPEAR TO HAVE
 AN OCCUPANT LOAD OVER 50, BUT SECOND EXIT ACCESS NOT
 CLEAR. AEROBICS ROOM HAS TWO DOORS BUT BOTH LEAD TO
 SAME CORRIDOR (COMMON PATH). FITNESS ROOM HAS ONLY ONE
 EXIT ACCESS. TWO MEANS OF EGRESS REQUIRED FROM SPACES
 WITH AN OCCUPANT LOAD OVER 50, TWO EXITS REQUIRED FOR
 THE AREA.
  
 39. G101, CORRIDOR 146A APPEARS TO EXCEED DEAD END
 CORRIDOR LIMIT, FBC 1018.4. REVISE PLAN TO ADDRESS.
  
 40. G101, FBC 303, FITNESS LOUNGE, FITNESS, AEROBICS,
 BREAK ROOM, CONFERENCE ROOM, LIBRARY ARE ASSEMBLY
 OCCUPANCY, FBC 303. PROVIDE OCCUPANT LOAD (TABLE
 1004.1.1, EXERCISE ROOMS) AND SEPARATION BETWEEN
 ASSEMBLY AND BUSINESS UNLESS EXCEPTION APPLIES. IF
 COVERED UNDER AN EXCEPTION, INCORPORATE INTO PLAN (FBC
 508.1, 508.2 AND COMMENTARY).
  
 41. LIVING ROOM LIBRARY IS SHOWN AS A CIRCULATION AREA
 WITH OCCUPANT LOAD BASED ON 200 SF PER PERSON. FBC
 TABLE 1004, READING ROOMS ARE TO HAVE AN OCCUPANT LOAD
 OF 50 SF PER PERSON. REVISE PLAN TO CLARIFY THE USE AND
 OCCUPANT LOAD FOR THIS AREA.
  
 42. G101, REVISE PLAN TO INCLUDE OCCUPANT LOAD AND AREA
 FOR THE FITNESS ROOM AND AEROBICS ROOM (SEPARATELY AS
 THE LARGER AREA CAN BE COMBINED TO TWO SMALLER AREAS).
 AS IT APPEARS THAT THE AEROBICS AND FITNESS AREA
 OCCUPANT LOAD WILL BE OVER 50, DOORS ARE TO SWING IN
 THE DIRECTION OF TRAVEL, FBC 1008.1.2.
  
 43. AS IT APPEARS THAT THE AEROBICS AND FITNESS AREA
 OCCUPANT LOAD WILL BE OVER 50, FIRE EXIT HARDWARE OR
 PANIC HARDWARE REQUIRED FOR THOSE DOORS AND ALL OTHER
 DOORS IN THE MEANS OF EGRESS, FBC 1008.1.10, 1004.9.
  
 44. EGRESS GATE IS REQUIRED TO HAVE EITHER FIRE EXIT
 HARDWARE OR PANIC HARDWARE, FBC 1008.1.10, 1008.2.
 REVISE PLAN TO INCLUDE THE REQUIREMENT OR DETAIL.
  
 45. G101, FBC 911.1.1, FIRE COMMAND CENTER ROOM SHALL
 BE A MINIMUM OF 200 SF AND A MINIMUM DIMENSION OF 10FT;
 REVISE PLAN TO SHOW COMPLIANCE WITH SIZE REQUIREMENT.
  
 46. G101, FBC 911.1.2, FIRE COMMAND CENTER ROOM
 REQUIRES A 1 HOUR FIRE BARRIER; THIS IS SHOWN AT THE
 CORRIDOR BUT NOT BETWEEN FIRE COMMAND CENTER AND
 CHILLERS RM 182.
  
 47. G101, PROVIDE OCCUPANT LOAD FOR DINING F. IF THE
 OCCUPANT LOAD IS OVER 50, TWO EXITS REQUIRED. REQUIRED
 MEANS OF EGRESS DOORS ARE TO BE SIDE SWINGING; A
 SLIDING DOOR IS SHOWN AS SECOND MEANS OF EGRESS, FBC
 1008.1.2.
  
 48. FBC 911.1.4, LAYOUT OF FIRE COMMAND CENTER AND ALL
 FEATURES REQUIRED BY 911.1.5 TO BE SUBMITTED AND
 APPROVED PRIOR TO INSTALLATION.
  
 49. TK G102, RATING BETWEEN STAIR 2, STAIR 4 IS SHOWN
 BETWEEN ADJACENT SHAFTS FOR PRESSURIZATION ON SHEET
 M202A, G102 SHOWS THE RATING OUTSIDE THE SHAFT (BETWEEN
 SHAFT AND CORRIDOR).
  
 50. G102 AND OTHER FLOORS, PROVIDE OCCUPANT LOAD AND
 OCCUPANCY CLASSIFICATION FOR THE COMMUNITY ROOM AND
 CONCIERGE 936, FBC 107, SEE ALSO FBC 508.2.
  
 NOTE THAT IF OCCUPANT LOAD IS 50 OR MORE, TWO EXITS ARE
 REQUIRED.
  
 51. A610, REVISE DOOR NOTE (GENERAL GLAZING
 REQUIREMENTS) TO UPDATE CODE REFERENCE (FBC 2007).
  
 52. DOOR SCHEDULE HAS A COLUMN FOR ?ELECTRIC? BUT THAT
 COLUMN IS BLANK. IT APPEARS THAT THIS SHOULD BE
 APPLICABLE FOR SLIDING DOORS IN THE REQUIRED MEANS OF
 EGRESS AND EXIT. EXIT DOOR 122 (DOOR TYPE G1) SHOULD
 ALSO COMPLY WITH FBC 1008.1.4.2, 1008.1.4.3.
  
 53. A601 AND G101, DOORS IN FIRE BARRIERS REQUIRE A 45
 MINUTE FIRE RATING, FBC TABLE 715.4. IT IS NOT CLEAR
 WHICH DOORS ARE BEING CONSIDERED IN A CORRIDOR RATHER
 THAN AN OCCUPANCY SEPARATION. SEE DOORS 173C, 182, 172,
 183.
  
 DOOR 173C IS A 20 MINUTE DOOR, BUT THE CORRIDOR 184
 RATING IS NOT CONTINUOUS AS IT APPEARS TO TRANSITION
 INTO THE GALLERY. USE OF CORRIDORS, INCIDENTAL AND
 ACCESSORY USES FBC 508 ARE NOT ENTIRELY CLEAR. IF ANY 1
 HOUR RATINGS ON THE PLAN ARE REMOVED WHEN RESUBMITTING,
 PLEASE ALSO NOTE ALSO SMOKE AND PROTECTION REQUIREMENT
 IN 508.2.5.2.
  
 54. S8.1 AND G000 PHASE I AND II, MAP FOR IMPORTANCE
 FACTOR III & IV IS INCLUDED, BUT SHEET S8.1 STATES
 DESIGN CRITERIA AS RISK CATEGORY II; PLEASE CORRELATE.
  
 IN ORDER TO ESTABLISH RISK CATEGORY, PROVIDE TOTAL
 BUILDING OCCUPANT LOAD. AT THIS POINT IT IS NOT CLEAR
 WHETHER THE TOTAL OCCUPANT LOAD SHOULD INCLUDE
 TRADITION I AND TRADITION II, OR IF THE TWO WILL BE
 DESIGNED AS SEPARATE BUILDINGS.
  
 55. S8.1, SOME STANDARD REFERENCES REFER TO "LATEST
 EDITION." PLEASE REVISE TO BE THE VERSION SPECIFIED IN
 FBC CHAPTER 35.
  
 56. S9.1, SECTION 9 AND OTHER PLACES, PLYWOOD
 SPECIFIED. FBC 603.1, PLEASE REVISE TO FRT.
  
 57. AN ENCLOSED ELEVATOR LOBBY IS NOT SHOWN. FBC
 708.14.1, PLEASE ADVISE AS TO WHICH EXCEPTION IS BEING
 USED IN THIS DESIGN AND WHERE THIS INFORMATION CAN BE
 LOCATED ON THE PLAN.
  
 58. A002 AND OTHER SHEETS REFER TO UL ASSEMBLIES.
 INCORPORATE DETAILS WITH SPECIFIC OPTIONS INTO THE PLAN
 OR THIS PERMIT WILL BE ISSUED WITH PROVISO THAT THE
 DETAILS BE SUBMITTED PRIOR TO INSTALLATION, AFTER
 REVIEW BY DESIGNER OF RECORD.
  
 59. A101, A "W" SHAPE APPEARS IN FRONT OF DOORS AT 186
 ELEVATOR LOBBY AND 118 WOMEN WHICH DOES NOT APPEAR ON
 OTHER SHEETS, CLARIFY, FBC 107.
  
 60. FBC 1207, PROVIDE THE FOLLOWING TEST REPORTS FOR
 THE FLOORING UNDERLAYMENT WILL BE REQUIRED AS
 APPLICABLE (INFORMATIONAL NOTE: PER S2.4, S3.1 FLOOR
 SLABS ARE 8IN, SO STC AND IIC TESTS ON AN 8IN SLAB OR
 LESS ARE ACCEPTABLE):
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 IF THIS INFORMATION IS NOT PROVIDED PRIOR TO PERMIT
 ISSUANCE, PERMIT WILL BE ISSUED WITH PROVISO THAT THIS
 BE SUBMITTED PRIOR TO INSTALLATION. REVIEW BY DESIGNER
 OF RECORD REQUIRED PRIOR TO SUBMITTAL, FBC 107.3.4.1.
  
 61. PROVIDE THE GEOTECHNICAL REPORT FOR THIS PROJECT,
 FBC 1803. THE SOILS REPORT IS TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
 62. FBC 107, PROVIDE THE SURVEY FOR THIS PROPERTY.
  
 63. THE PLANS INDICATE THERE WILL BE A POOL BUILT VERY
 CLOSE TO THIS BUILDING PLEASE PROVIDE HOW THE
 FOUNDATION /FOOTING WILL BE PRESERVED WHILE THE POOL IS
 BEING EXCAVATED? 1808.7.
  
 64. 2010 FBC-B 1816.1 TERMITE PROTECTION. TERMITE
 PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL-APPLIED PESTICIDES,
 BAITING SYSTEMS AND PESTICIDES APPLIED TO WOOD, OR
 OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED
 FOR USE AS A PREVENTATIVE TREATMENT TO NEW
 CONSTRUCTION. SEE SECTION 202, REGISTERED TERMITICIDE.
 UPON COMPLETION OF THE APPLICATION OF THE TERMITE
 PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL
 BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED
 PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING
 STATEMENT: "THE BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES.
 TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE
 AND CONSUMER SERVICES."
  
 65. BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 66. PLEASE PROVIDE DOCUMENTATION HOW THE JOBSITE WILL
 COMPLY WITH :
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 110.7 IMPACT OF
 CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO
 ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT GRANTED BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS OR CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES, BUT IS NOT LIMITED TO, THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFFS, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL
 NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS,
 POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON
 EXISTING PROPERTIES RESULTING IN A SIGNIFICANT DECREASE
 OF PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE
 DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 2ND REVIEW; A STATEMENT IT TYPICALLY INCORPORATED INTO
 THE PLAN.
  
 67. G101, REVISE LIFE SAFETY PLAN TO INCLUDE WORST CASE
 WITH TRAVEL DISTANCE FOR EACH AREA (NOT NECESSARY FOR
 EACH ROOM). PATH OF TRAVEL IS TO BE SHOWN ACROSS THE
 DIAGONAL OF THE ROOMS. FBC 1016.1, THIS SHOULD BE SHOWN
 ALONG THE NATURAL UNOBSTRUTED PATH OF TRAVEL. AS
 FURNITURE WILL BE PLACED IN THE CENTER OF THE ROOM, THE
 PATH SHOULD BE MEASURED ALONG THE ROOM PERIMETER.
  
 68. SEE OTHER COMMENTS, SHAFT RATING PROPOSED NOT
 CLEAR. PLEASE CLARIFY SHAFT RATING FOR ELEVATOR 2 PHASE
 I, A 1 HOUR SHAFT IS SHOWN, BUT A 2 HOUR SHAFT IS SHOWN
 FOR ELEVATOR 1
  
 69. S2.1 APPEARS TO HAVE A TYPO, TOP RIGHT, NOTE
 (STATES "PER ACI 18.12.4"); PLEASE CORRECT OR CLARIFY
 AS APPLICABLE. PLEASE ALSO REVISE OTHER AFFECTED
 SHEETS.
  
 70. SECTION 1 S4.1, ALSO SECTION 5 AND OTHER PLACES,
 PLYWOOD SHEATHING SHOWN. FBC 602.1, REVISE TO INCLUDE
 REQUIREMENT FOR FRT (ALSO TO CORRELATE WITH A101 AND
 OTHER SHEETS), FBC 603.1.1.1.3.
  
 71. PROVIDE INFORMATION FOR THE MCKEON DOOR (SPEC
 SHEETS AND TEST REPORT), INSTALLATION INSTRUCTIONS.
 ALSO DISCUSSED IN THE MEETING WAS THE PRACTICALITY FOR
 ACCESS FOR MAINTENANCE, FBC 107.
  
 72. 50. FBC 2010 ACCESSIBILITY 703, SIGNS TO COMPLY
 WITH THIS SECTION.
  
 73. PLANS IN MANY LOCATIONS USE THE LANGUAGE "UNDER
 SEPARATE PERMIT" (FOR INSTANCE, SHEET 036 - S6.2). IF
 ALL WORK TO BE INCLUDED IN THIS PERMIT, REVISE
 LANGUAGE. IF THIS IS PROVIDED FOR INFORMATION ONLY,
 PLEASE ADVISE.
  
 74. INCORPORATE FIRE RATING REQUIREMENTS AND DETAILS
 FOR THE FLOOR, STRUCTURAL ELEMENTS FBC TABLE 601.
  
 75. PLEASE IDENTIFY THE RECTANGLE ADJACENT TO THE SINK
 IN THE GUEST ROOM, S1.2 AND OTHER PAGES.
  
 76. PROVIDE A DETAIL FOR THE OVERFLOW SCUPPER, FBC 107
 (OR ADVISE AS TO WHERE THIS CAN BE LOCATED).
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-01-10 Cont ID  
Sent By jwitmer Date 2015-01-10 Time 13:15 Rev Time 0.00
Received By shill Date 2015-01-10 Time 10:28 Sent To  
Notes
2015-01-07 17:15:45 
 BUILDING PLAN REVIEW
 PERMIT: 14120909
 ADD: 4920 LORING DR.
 CONT: THE WHITING TURNER CO.
 CONTACT: RYAN TEMPONE
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW- FOUNDATION PERMIT
 DATE: SAT. JAN. 10/ 2015
 ACTION: DENIED
  
 NOTE: FOUNDATION PERMIT/ PHASED PERMITING. 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION
 105.13 PHASED PERMIT APPROVAL. AFTER SUBMITTAL OF THE
 APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION
 OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED
 AT THE HOLDER?S OWN RISK WITH THE BUILDING OPERATION
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  
 1) MISSING INFORMATION EVEN FOR A FOUNDATION PERMIT:
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION
  
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS:
 1.1) SITE PLAN SHOWING LOCATION OF THE NEW BUILDING AND
 THE RELATIONSHIP OF OTHER BUILDINGS, PROVIDE DISTANCES
 BETWEEN.
 1.2) SURVEY WITH FLOOD ZONE DESIGNATION
 1.3) SOILS REPORT WITH THE MINIMUM BEARING VALUE FOR
 THIS BUILDING
 1.4) A ARCHITECTURAL SHEET SHOWING THE 1ST FLOOR OR
 BOTTOM FLOOR, WITH FINISH FLOOR ELEVATIONS.
 1.5) OCCUPANCY TYPE
 1.6) MINIMUM BUILDING TYPE/ NUMBER OF STORIES
  
 2) SINCE THE TRADITION TOWER WILL BE ASSUMED THE 10
 STORY THERE HAS BEEN DISCUSSION ABOUT, THIS BUILDING
 WOULD BE CLASSIFIED AS A THRESHOLD BUILDING BY
 DEFINITION AND NEED TO MEET THE STATE REQUIREMENTS FOR
 SUCH A BUILDING. NOTE SHEET S-1.1 DRAWING INDEX
 INDICATES 10 FLOOR FRAMING PLAN.
  
 NOTE :THRESHOLD FORMS WERE E-MAILED TO RYAN TEMPONE
 1/10/2015 01:05 PM.
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2A) SHEET S-8.10THRESHOLD INSPECTION NOTES NOT INCLUDED
 IN THIS SUBMITTAL. 109.3.6.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM STRUCTURAL
 INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A
 (WRITTEN/ TYPED) STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE INSPECTION COMPANY &
 THRESHOLD INSPECTOR WILL NEED TO FILL OUT THE SPECIAL
 INSPECTOR AGREEMENT FORMS AND RESUBMIT TO THE CITY FOR
 REVIEW. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 2C) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 2F) NOTE THIS IS A DIGITAL PLAN, AFTER PERMIT ISSUANCE,
 THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLLOR, (1)
 FOR THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 2G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 3) PLEASE PROVIDE DOCUMENTATION HOW THE JOBSITE WILL
 COMPLY WITH :
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 110.7 IMPACT OF
 CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO
 ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 GRANTED BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS
 OR CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES, BUT IS NOT LIMITED TO, THE
 CONTROL OF DUST, NOISE, WATER OR DRAINAGE RUN-OFFS,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW
 CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL
 HISTORIC SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL
 NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS,
 POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON
 EXISTING PROPERTIES RESULTING IN A SIGNIFICANT DECREASE
 OF PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE
 DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 4) 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 5) THE (4) FOUNDATION SHEETS SUBMIITED DOES NOT HAVE
 ENOUGH INFORMATION ON THESE SHEETS WITH DIMENSIONS, NOR
 STEEL LAYOUT FOR THE VERTICAL COLUMNS, NOR COLUMN
 SIZES. THE DETAIL SHEETS AND SECTIONS FOR ELEVATOR PITS
 ARE ALSO MISSING FROM THIS SUBMITTAL, THE MINIMUM
 BEARING VALUE NOT PROVIDED, MINIMUM CONCRETE DESIN MIX,
 THERE IS NOT ENOUGH INFORMATION PROVIDED TO DO A
 THROGOUGH REVIEW.
  
 6) THE PLANS INDICATE THERE WILL BE A POOL BUILT VERY
 CLOSE TO THIS BUILDING PLEASE PROVIDE HOW THE
 FOUNDATION /FOOTING WILL BE PRESERVED WHILE THE POOL IS
 BEING EXCAVATED? 1808.7.
  
 7) 2010 FBC-B 1816.1 TERMITE PROTECTION. TERMITE
 PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL-APPLIED PESTICIDES,
 BAITING SYSTEMS AND PESTICIDES APPLIED TO WOOD, OR
 OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED
 FOR USE AS A PREVENTATIVE TREATMENT TO NEW
 CONSTRUCTION. SEE SECTION 202, REGISTERED TERMITICIDE.
 UPON COMPLETION OF THE APPLICATION OF THE TERMITE
 PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL
 BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED
 PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING
 STATEMENT: "THE BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES.
 TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE
 AND CONSUMER SERVICES."
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-08-27 Cont ID  
Sent By dharvey Date 2015-08-27 Time 10:24 Rev Time 0.00
Received By dharvey Date 2015-08-27 Time 10:19 Sent To  
Notes
2015-08-27 10:24:11NOTES ADDED TO PLANS FOR FIELD EVALUATION AND
 COMPLIANCE WITH GOVERNING CODES
 ENTIRE INSTALLATION SUBJECT TO FIELD INSPECTION AND
 REQUIREMENTS OF THE GOVERNING CODES.
 PLANS ARE BEING NOTED FOR COMPLIANCE AND AS-BUILT MAY
 BE REQUIRED IF DEVIATIONS ARE REQUIRED FOR COMPLIANCE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-06-23 Cont ID  
Sent By dhayes Date 2015-06-23 Time 15:16 Rev Time 0.00
Received By dhayes Date 2015-06-11 Time 10:32 Sent To  
Notes
2015-06-23 15:12:326/12/2015
 PROJECT: MORSE SENIOR CENTER PHASE
 PERMIT#: 14120909
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) CLARIFICATION IS REQUIRED. THE APPLICATION SUBMITTED
 WITH THESE PLANS STATE "FOUNDATION ONLY" HOWEVER THE
 PLANS ARE A FULL SET FOR CONSTRUCTION OF A HIGH RISE.
  
 2) G001
 UNDER APPLICABLE CODES LIST TOP LEFT OF THE PAGE ADD
 THE 2008 EDITION OF THE NATIONAL ELECTRICAL CODE
  
 3) E000
 UNDER CODES AND STANDARDS LIST TOP RIGHT OF THE PAGE.
 CHANGE THE 2011 EDITION OF THE NATIONAL ELECTRICAL CODE
 TO THE 2008 EDITION OF THE NATIONAL ELECTRICAL CODE.
  
 4) E001
 SUBMIT MANUFACTURER DOCUMENTATION ON FIRE PUMP MOTOR
 AND CONTROLLER/ATS. INDICATE HP RATING LOAD AND VOLTAGE
 OF FIRE PUMP MOTOR.
 4A) PROVIDE VERIFICATION ON THE PLANS THAT THE FIRE
 PUMP FEEDERS, CIRCUIT CONDUCTORS, GENERATOR CONTROL
 WIRING AND PUMP WIRING ARE APPROPRIATELY FIRE
 PROTECTED. INDICATE THE FIRE RATING AND MATERIAL
 REQUIRED. NEC 695.6, 695.14
  
 5) VERIFY THE FIRE PUMP FEEDERS ARE SIZED WITH A RATING
 NOT LESS THAN 125% OF THE SUM OF THE FIRE PUMP MOTOR,
 PRESSURE MAINTENANCE MOTORS AND 100 PERCENT OF THE
 ACCESSORIES.
 5A) VERIFY THE MAXIMUM VOLTAGE DROP IS NOT MORE THAN 15
 % BELOW NORMAL STARTING AND 5% BELOW WHEN THE MOTOR IS
 OPERATING AT 115% OF THE FULL LOAD CURRENT RATING. NEC
 695.6, 695.7
  
 6) CLARIFY THE NEED FOR EMERGENCY POWER AND THEREFORE
 THE NEED FOR LEGALLY REQUIRED EMERGENCY GENERATOR OR
 SIMPLY A STANDBY STAND BY GENERATOR.
  
 7) INDICATE THAT ALL WIRING FOR EMERGENCY LOADS WILL BE
 IDENTIFIED WITH PERMANENT MARKINGS AND KEPT ENTIRELY
 INDEPENDENT OF ALL OTHER WIRING AND EQUIPMENT. NEC
 700.9
  
 8) PROVIDE PROPER SIGNAGE INDICATING THE TYPE AND
 LOCATION OF THE ON SITE EMERGENCY POWER SOURCE. NEC
 700.8
 8A) PERMANENT PLAQUES OR DIRECTORIES SHALL BE INSTALLED
 AT EACH SERVICE DISCONNECT
 DENOTING ALL OTHER SERVICE LOCATION. NEC 230.2(E)
  
 9) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16.
  
 10) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN
 SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 11) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 12) INDICATE COMPLIANCE WITH FBC-ENERGY. ELECTRICAL
 POWER AND LIGHTING SYSTEMS. (MANDATORY) FBC SECTION 505
 12A) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN
 SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.3
  
 13) NEC 230.9(C) GROUND FAULT PERFORMANCE TESTING. THE
 GROUND-FAULT PROTECTION SYSTEM SHALL BE PERFORMANCE
 TESTED WHEN FIRST INSTALLED ON SITE.
  
 14) PROVIDE A LAYOUT OF ALL ELECTRICAL ROOMS INDICATING
 COMPLIANCE WITH NEC 110.26 FOR ABOUT ALL ELECTRICAL
 EQUIPMENT.
  
 15) E605 INDICATE THE LOAD CALCULATION FOR PANEL
 NLGP1A. THE LOAD CALCULATION IS CUT OFF BY PANEL
 NLGP1B.
  
 16) CORRECT THE NAMING CONVENTION FOR THE ELECTRICAL
 SHEETS. THE ELECTRICAL SHEETS ARE NOT ALL TOGETHER.
  
 17) CORRECT THE NAME OF PANEL RDPB. ON PAGE E005 IT IS
 NAMED RDPB BUT ON PG E001 IT IS NAMED RMDPB
  
 18) E200A
 PROVIDE THE NOTES REFERENCED ON THE ENLARGED FLOOR PLAN
 UNITS E1 AND D2. THERE ARE PLAN NOTES SYMBOLS ON THE
 FLOOR PLANS BUT NO NOTES ANYWHERE ON THAT PAGE TO
 REFERENCE FOR CLARIFICATION.
 18A) POWER PLAN NOTE 6. CALLS FOR A 20AMP CIRCUIT FOR
 DRYER BOOSTER FANS.
 BOOSTER FANS ARE NOT APPROVED FOR USE IN WPB PER THE
 WPB FIRE DEPT LOCAL CODES AND AMENDMENTS.
  
 19) E200B
 PROVIDE THE NOTES REFERENCED ON THE ENLARGED FLOOR PLAN
 UNITS E1 AND D2. THERE ARE PLAN NOTES SYMBOLS ON THE
 FLOOR PLANS BUT NO NOTES ANYWHERE ON THAT PAGE TO
 REFERENCE FOR CLARIFICATION.
  
 20) E200C
 CORRECT PLAN NOTE 1 TO PROVIDE AFCI CIRCUIT BREAKER ON
 ALL CIRCUITS WITHIN SLEEPING AREA TO READ ?ALL
 120-VOLT, SINGLE PHASE, 15- AND 20-AMPERE BRANCH
 CIRCUITS SUPPLYING OUTLETS INSTALLED IN DWELLING UNIT
 FAMILY ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS,
 LIBRARIES, DENS, BEDROOMS, SUNROOMS, RECREATION ROOMS,
 CLOSETS, HALLWAYS, OR SIMILAR ROOMS OR AREAS SHALL BE
 PROTECTED BY A LISTED ARC-FAULT CIRCUIT INTERRUPTER,
 COMBINATION-TYPE, INSTALLED TO PROVIDE PROTECTION OF
 THE BRANCH CIRCUIT.? PER NEC 210.12(B)
 20A) ANYWHERE RECEPTACLES ARE INSTALLED WITHIN 6 FT OF
 THE SINK SHALL BE GFI PROTECTED. NEC 210.8(B)(5)
  
 21) E202CPROVIDE A GFI WITHIN SIGHT OF MECHANICAL
 EQUIPMENT. NEC 210.63 SEE ALSO 210.8(A)(3).
  
 22) E301A
 INDICATE HOW LIGHTING IS TO BE CONTROLLED THROUGHOUT.
 FBC 505.2
  
 23) E301B
 PROVIDE EMERGENCY AND EXIT LIGHTING AT STAIRS.
 INDICATE HOW LIGHTING IS TO BE CONTROLLED THROUGHOUT.
 FBC 505.2
  
 24) E310B
 PROVIDE EMERGENCY AND EXIT LIGHTING AT STAIRS.
 INDICATE HOW LIGHTING IS TO BE CONTROLLED THROUGHOUT.
 FBC 505.2
  
 25) E601
 REVISE PANEL SCHEDULE AND LOAD CALCULATION. PANEL C2
 INDICATES A 27KVA DEMAND LOAD AT ONLY 75AMPS. THIS
 SHOULD BE CLOSER TO 130AMPS.
 23A) APPLY PANEL NOTE ?A? AT ALL CIRCUIT LOCATIONS
 REQUIRED.
  
 26) E602
 APPLY PANEL NOTE ?A? AT ALL CIRCUIT LOCATIONS REQUIRED
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SWIMMING POOL, SITE LIGHTING,
 LIGHTNING PROTECTION, GENERATORS. HOOD EXHAUST, FIRE
 ALARM, ACCESS CONTROL SYSTEM, SECURITY, CCTV,
 AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2015-08-07 Cont ID  
Sent By cranford Date 2015-08-07 Time 15:35 Rev Time 0.00
Received By cranford Date 2015-08-07 Time 13:56 Sent To  
Notes
2015-08-07 15:28:18PLEASE SEE ENGINEERING DEVELOPMENT APPLICATION
 E15080021 FOR COMMENTS FROM THE CITY?S PUBLIC WORKS
 DEPARTMENT (WORK WITHIN THE CITY?S RIGHT-OF-WAYS AND
 EASEMENTS, POTABLE WATER SYSTEM, SANITARY SEWER SYSTEM,
 STORMWATER SYSTEM, SOLID WASTE COLLECTION, OR
 PEDESTRIAN AND VEHICULAR TRAFFIC).
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2015-07-16 Cont ID  
Sent By cranford Date 2015-07-16 Time 14:14 Rev Time 0.00
Received By cranford Date 2015-07-16 Time 14:00 Sent To  
Notes
2015-07-16 14:02:11PUBLIC WORKS DEPT.
  
 1. AS MENTIONED DURING PPRC REVIEW, ENGINEERING
 DEVELOPMENT APPROVAL IS REQUIRED FOR THIS PROJECT.
 ENGINEERING DEVELOPMENT APPROVAL FROM THE CITY?S PUBLIC
 WORKS DEPARTMENT IS REQUIRED FOR ALL PROJECTS INVOLVING
 OR AFFECTING THE CITY?S STREET RIGHT-OF-WAYS,
 EASEMENTS, POTABLE WATER SYSTEM, SANITARY SEWER SYSTEM,
 STORMWATER SYSTEM, SOLID WASTE COLLECTION, OR
 PEDESTRIAN AND VEHICULAR TRAFFIC. THIS INCLUDES ANY
 WORK THAT INCREASES IMPERVIOUS AREAS; CHANGES THE
 DIRECTION, VELOCITY, OR TIMING OF STORMWATER DISCHARGE;
 OR CREATES A CONDITION OF ENVIRONMENTAL CONCERN. THE
 ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS CAN
 BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 PLEASE SUBMIT AN APPLICATION FOR ENGINEERING
 DEVELOPMENT APPROVAL AND MAKE A NOTE ON THE CIVIL PLANS
 INCLUDED IN THE BUILDING APPLICATION SUBMITTAL THAT
 THEY ARE FOR REFERENCE ONLY.
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-04-15 Cont ID  
Sent By cranford Date 2015-04-15 Time 09:57 Rev Time 0.00
Received By cranford Date 2015-04-15 Time 08:47 Sent To  
Notes
2015-04-15 09:57:20PUBLIC WORKS DEPT.
  
 1. AS MENTIONED DURING PPRC REVIEW, ENGINEERING
 DEVELOPMENT APPROVAL IS REQUIRED FOR THIS PROJECT.
 ENGINEERING DEVELOPMENT APPROVAL FROM THE CITY?S PUBLIC
 WORKS DEPARTMENT IS REQUIRED FOR ALL PROJECTS INVOLVING
 OR AFFECTING THE CITY?S STREET RIGHT-OF-WAYS,
 EASEMENTS, POTABLE WATER SYSTEM, SANITARY SEWER SYSTEM,
 STORMWATER SYSTEM, SOLID WASTE COLLECTION, OR
 PEDESTRIAN AND VEHICULAR TRAFFIC. THIS INCLUDES ANY
 WORK THAT INCREASES IMPERVIOUS AREAS; CHANGES THE
 DIRECTION, VELOCITY, OR TIMING OF STORMWATER DISCHARGE;
 OR CREATES A CONDITION OF ENVIRONMENTAL CONCERN. THE
 ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS CAN
 BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 PLEASE SUBMIT AN APPLICATION FOR ENGINEERING
 DEVELOPMENT APPROVAL AND MAKE A NOTE ON THE CIVIL PLANS
 INCLUDED IN THE BUILDING APPLICATION SUBMITTAL THAT
 THEY ARE FOR REFERENCE ONLY.
  
  
 2. PLEASE SUBMIT A COPY OF THE APPROVED SITE PLAN
 (Z14120012). WHEN SITE PLAN REVIEW IS REQUIRED, REVIEW
 AND APPROVAL ARE NECESSARY PRIOR TO ISSUANCE OF A
 BUILDING PERMIT. [SECTION 94-35(G) OF THE CITY'S CODE
 OF ORDINANCES]
  
 KELLY CRANFORD, P.E.
 LAND DEVELOPMENT ENGINEER
 PUBLIC WORKS DEPARTMENT
 CITY OF WEST PALM BEACH
 [email protected]
 561-494-1098 (OFFICE)
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-09-09 Cont ID  
Sent By wjolin Date 2015-09-09 Time 11:13 Rev Time 0.00
Received By wjolin Date 2015-09-09 Time 11:06 Sent To  
Notes
2015-09-09 11:13:064920 LORING DRIVE
 PERMIT #14120909
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
 ****APPROVED WITH PROVISIONS****
  
  
 2ND REVIEW
 SHEET G101: NO EXIT SIGNAGE PROVIDED FOR CORRIDOR
 ADJACENT TO CONFERENCE #112.
  
 SHEET G101: PROVIDE ADDITIONAL EXIT SIGN AT EAST END OF
 CORRIDOR #146A. ALSO DOOR APPEARS TO SERVE 51 PERSONS
 SO THE SWING WOULD NEED TO BE WITH THE FLOW OF TRAFFIC
 AND BE EQUIPPED WITH PANIC HARDWARE.
  
 REPEAT COMMENT -SHEET G001: UPDATE THE CODE LIST TO
 REFERENCE THE 5TH EDITION OF THE FLORIDA FIRE
 PREVENTION CODE WHICH CONTAINS THE 2012 EDITION OF BOTH
 NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 SHEET A101 DOES NOT APPEAR TO BE UPDATED TO MATCH THE
 LIFE SAFETY PLAN.
  
 NOTE: THE COOKING GRILL LOCATED ON THE POOL DECK SHALL
 COMPLY WITH NFPA 96 OR SHALL BE LOCATED AT LEAST 10
 FEET FROM ANY BUILDING, STRUCTURE, OR COMBUSTIBLES PER
 NFPA 1 SECTION 10.11.6.1. IF THE GRILL WILL BE USED
 UNDER A ROOF STRUCTURE, THE DESIGN SHALL COMPLY WITH
 NFPA 96.
  
  
  
 PHASE 2 - FIRE DEPARTMENT REVIEW
  
 REPEAT COMMENT - SHEET G001: UPDATE THE CODE LIST TO
 REFERENCE THE 5TH EDITION OF THE FLORIDA FIRE
 PREVENTION CODE WHICH CONTAINS THE 2012 EDITION OF BOTH
 NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. PER
 SECTION 6.1.14.1.2, WHERE EXIT ACCESS FROM AN OCCUPANCY
 TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE OCCUPANCY
 SHALL BE TREATED AS A MIXED OCCUPANCY.
  
  
 DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2015-08-26 Cont ID  
Sent By wjolin Date 2015-08-26 Time 14:47 Rev Time 0.00
Received By wjolin Date 2015-08-07 Time 12:03 Sent To  
Notes
2015-08-07 12:04:184920 LORING DRIVE
 PERMIT #14120909
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
  
 2ND REVIEW
 SHEET G101: NO EXIT SIGNAGE PROVIDED FOR CORRIDOR
 ADJACENT TO CONFERENCE #112.
  
 SHEET G101: PROVIDE ADDITIONAL EXIT SIGN AT EAST END OF
 CORRIDOR #146A. ALSO DOOR APPEARS TO SERVE 51 PERSONS
 SO THE SWING WOULD NEED TO BE WITH THE FLOW OF TRAFFIC
 AND BE EQUIPPED WITH PANIC HARDWARE.
  
 REPEAT COMMENT -SHEET G001: UPDATE THE CODE LIST TO
 REFERENCE THE 5TH EDITION OF THE FLORIDA FIRE
 PREVENTION CODE WHICH CONTAINS THE 2012 EDITION OF BOTH
 NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 SHEET A101 DOES NOT APPEAR TO BE UPDATED TO MATCH THE
 LIFE SAFETY PLAN.
  
 NOTE: THE COOKING GRILL LOCATED ON THE POOL DECK SHALL
 COMPLY WITH NFPA 96 OR SHALL BE LOCATED AT LEAST 10
 FEET FROM ANY BUILDING, STRUCTURE, OR COMBUSTIBLES PER
 NFPA 1 SECTION 10.11.6.1. IF THE GRILL WILL BE USED
 UNDER A ROOF STRUCTURE, THE DESIGN SHALL COMPLY WITH
 NFPA 96.
  
 REPEAT COMMENT - SHEET FP402: FIRE PUMP SCHEDULE DOES
 NOT INDICATE A RATED PRESSURE OR HORSEPOWER RATING. THE
 ENGINEERING DOCUMENTS WILL BE REQUIRED TO DETERMINE IF
 PRESSURE REDUCING VALVES ARE NEEDED ON THE STANDPIPES
 AND SPRINKLER SYSTEMS. PRESSURE REDUCING VALVES WILL
 ALSO REQUIRE A 3-INCH DRAIN RISER IN LIEU OF A 2-INCH
 DRAIN RISER AS SHOWN ON THE PLANS.
  
 REPEAT COMMENT - SHEET FP402: PER FBC SECTION403.3.2
 WATER SUPPLY TO REQUIRED FIRE PUMPS - REQUIRED FIRE
 PUMPS SHALL BE SUPPLIED BY CONNECTIONS TO A MINIMUM OF
 TWO WATER MAINS LOCATED IN DIFFERENT STREETS. SEPARATE
 SUPPLY PIPING SHALL BE PROVIDED BETWEEN EACH CONNECTION
 TO THE WATER MAIN AND THE PUMPS. EACH CONNECTION AND
 THE SUPPLY PIPING BETWEEN THE CONNECTION AND THE PUMPS
 SHALL BE SIZED TO SUPPLY THE FLOW AND PRESSURE REQUIRED
 FOR THE PUMPS TO OPERATE.
  
  
 PHASE 2 - FIRE DEPARTMENT REVIEW
  
 REPEAT COMMENT - SHEET G001: UPDATE THE CODE LIST TO
 REFERENCE THE 5TH EDITION OF THE FLORIDA FIRE
 PREVENTION CODE WHICH CONTAINS THE 2012 EDITION OF BOTH
 NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS. PER
 SECTION 6.1.14.1.2, WHERE EXIT ACCESS FROM AN OCCUPANCY
 TRAVERSES ANOTHER OCCUPANCY, THE MULTIPLE OCCUPANCY
 SHALL BE TREATED AS A MIXED OCCUPANCY.
  
  
 DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-04-01 Cont ID  
Sent By wjolin Date 2015-04-01 Time 14:54 Rev Time 0.00
Received By wjolin Date 2015-03-13 Time 13:41 Sent To  
Notes
2015-03-13 13:52:384920 LORING DRIVE
 PERMIT #14120909
 REVIEW COMMENTS - FIRE DEPARTMENT
 NOTE: UNLESS NOTED OTHERWISE, ALL FIRE/LIFE SAFETY
 REVIEW COMMENTS REFERENCE NFPA 101-THE LIFE SAFETY CODE
 (2012 EDITION WITH FLORIDA AMENDMENTS.)
  
 GENERAL: INDICATE THE LOCATION AND SIZES OF ANY
 PROPOSED CONSTRUCTION TRAILERS/MODULAR BUILDINGS. PER
 NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION,
 ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2:
 TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF
 COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE
 CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS,
 TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1.
 PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET
 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 50 FEET
 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE
 SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET
 **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL
 BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC
 SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE.
 PER NFPA 241 SECTION 4.2.2: DETACHMENT BETWEEN
 TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED FIRE
 PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL BE
 PROVIDED AS REQUIRED BY THE AUTHORITY HAVING
 JURISDICTION.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 SHEET G001: UPDATE THE CODE LIST TO REFERENCE THE 5TH
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2012 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS. PER SECTION 6.1.14.1.2, WHERE
 EXIT ACCESS FROM AN OCCUPANCY TRAVERSES ANOTHER
 OCCUPANCY, THE MULTIPLE OCCUPANCY SHALL BE TREATED AS A
 MIXED OCCUPANCY.
  
 SHEET G101: FIRE COMMAND CENTER (#182B) SHALL BE AT
 LEAST 200 SQUARE FEET AND HAVE A MINIMUM DIMENSION OF
 10 FEET (FBC 911.1.3). PER NFPA 1 SECTION 11.9.2 THE
 EMERGENCY COMMAND CENTER SHALL BE SEPARATED FROM THE
 REMAINDER OF THE BUILDING BY A FIRE BARRIER HAVING A
 FIRE RESISTANCE RATING OF NOT LESS THAN 1 HOUR.
 PER NFPA 1 SECTION 11.9.4 THE FOLLOWING SHALL BE
 PROVIDED IN THE EMERGENCY COMMAND CENTER:
 (1) THE FIRE DEPARTMENT COMMUNICATION UNIT
 (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
 (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT, AND FIRE DEPARTMENT ACCESS
 (4) WORK TABLE
 (5) IF APPLICABLE, HAZARDOUS MATERIAL MANAGEMENT PLANS
 FOR THE BUILDING
  
 PER NFPA 1 SECTION 11.9.5 WHERE OTHERWISE REQUIRED, THE
 FOLLOWING DEVICES OR FUNCTIONS SHALL BE PROVIDED WITHIN
 THE EMERGENCY COMMAND CENTER:
 (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM UNIT
 (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT
 (3) ANNUNCIATOR VISUALLY INDICATING THE LOCATION OF THE
 ELEVATORS AND WHETHER THEY ARE OPERATIONAL
 (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING
 SYSTEMS
 (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY
 (6) SPRINKLER VALVE AND WATERFLOW DETECTOR DISPLAY
 PANELS
 (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS
 (8) FIRE PUMP STATUS INDICATORS
 (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES
 (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE
 (11) CONTROLS REQUIRED FOR SMOKE CONTROL
  
 11.9.6 EMERGENCY COMMAND CENTER ACCEPTANCE TESTING.
 DEVICES, EQUIPMENT, COMPONENTS, AND SEQUENCES SHALL BE
 INDIVIDUALLY TESTED IN ACCORDANCE WITH APPROPRIATE
 STANDARDS AND MANUFACTURERS? DOCUMENTED INSTRUCTIONS.
  
 SHEET G101: PER TABLE 7.3.1.2, KITCHEN SPACES SHALL
 HAVE AN OCCUPANT LOAD FACTOR OF 100 SQUARE FEET PER
 PERSON IN LIEU OF THE 200 SQ.FT. INDICATED.
  
 SHEET G101: PROVIDE AN OCCUPANT LOAD FOR BREAKROOM
 #167.
  
 SHEET G101: LIBRARY #121, FITNESS #143, AEROBICS #145
 AND CONFERENCE #112 ARE TREATED AS ASSEMBLY USE SPACES
 IN THE FIRE CODE AND NEED AN OCCUPANT LOAD BASED UPON
 THE OCCUPANT LOAD FACTORS FOUND IN TABLE 7.3.1.2.
  
 ***SHEET G101: SEVERAL EXITS APPEAR TO ROUTE AND MERGE
 EXITING OCCUPANTS AT THE POOL DECK AREA. THERE DOES NOT
 APPEAR EXTERIOR EXIT SIGNAGE, EMERGENCY LIGHTING OR
 SUFFICIENT EXIT WIDTH (1 EGRESS GATE) TO HANDLE THE
 OCCUPANT LOAD. WHERE IS THE PUBLIC WAY? HOW WILL THE
 POOL DECK EGRESS ROUTES BE MAINTAINED UNOBSTRUCTED FOR
 THE LIFE OF THE BUILDING?
  
 SHEET G101: CORRIDOR #146A CREATES A DEAD-END THAT
 EXCEEDS 20 FEET. PER SECTION12.2.5.1.3 DEAD-END
 CORRIDORS SHALL NOT EXCEED 20 FEET.
  
 SHEET C103 &C106: SOUTH ACCESS ROAD INDICATES A 20 FOOT
 WIDE FIRE LANE AT THE POOL GATE; HOWEVER, THE SOUTHWEST
 AREA INDICATES EXISTING ROADS THAT DO NOT APPEAR TO BE
 20 FEET WIDE AND MARKED AS A FIRE LANE. PER SECTION
 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT ACCESS ROADS
 SHALL HAVE A SURFACE DESIGNED TO ACCOMMODATE FIRE
 APPARATUS WEIGHING AT LEAST 36 TONS. ACCESS ROADS SHALL
 HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND
 AN UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13
 FEET 6 INCHES. PER SECTION 18.2.3.5.3 (NFPA 1), FIRE
 LANES SHALL BE MARKED WITH FREESTANDING SIGNS READING,
 "FIRE LANE - NO PARKING BY ORDER OF THE FIRE
 DEPARTMENT." SIGNS SHALL BE 12" X 18" WITH A WHITE
 BACKGROUND AND RED LETTERS AND SHALL BE A MAXIMUM OF
 SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS
 SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW AND BE SPACED
 A MAXIMUM OF 60 FEET APART.
  
 SHEET C107: FIRE HYDRANTS SHALL BE INSTALLED,
 INSPECTED, TESTED AND APPROVED BY THE FIRE DEPARTMENT
 PRIOR TO VERTICAL CONSTRUCTION.PER SECTION 18.3.4.1
 (NFPA 1), FIRE HYDRANTS SHALL BE PROVIDED WITH
 CLEARANCES OF 7'-6" TO THE FRONT AND SIDES AND 4'-0" TO
 THE BACKSIDE OF THE STEAMER CAP.
  
 SHEET C107: NORTHWEST PIV - PER NFPA 24 SECTION 6.2.1,
 ALL CONNECTIONS TO PRIVATE FIRE SERVICE MAINS FOR FIRE
 PROTECTION SYSTEMS SHALL BE ARRANGED IN ACCORDANCE WITH
 ONE OF THE FOLLOWING SO THAT THEY CAN BE ISOLATED:
 (1)A POST INDICATOR VALVE INSTALLED NOT LESS THAN 40
 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A POST
 INDICATOR VALVE SHALL BE PERMITTED TO BE INSTALLED
 CLOSER THAN 40 FEET BUT AT LEAST AS FAR FROM THE
 BUILDING AS THE HEIGHT OF THE WALL FACING THE POST
 INDICATOR VALVE.
 (2) A WALL POST INDICATOR VALVE
 (3) AN INDICATING VALVE IN A PIT, INSTALLED IN
 ACCORDANCE WITH SECTION 6.4
 (4) A BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING
 VALVE NOT LESS THAN 40 FEET FROM THE BUILDING.
 (A) FOR BUILDINGS LESS THAN 40 FEET IN HEIGHT, A
 BACKFLOW PREVENTER WITH AT LEAST ONE INDICATING VALVE
 SHALL BE PERMITTED TO BE INSTALLED CLOSER THAN 40 FEET
 BUT AT LEAST AS FAR FROM THE BUILDING AS THE HEIGHT OF
 THE WALL FACING THE BACKFLOW PREVENTER.
 (5) CONTROL VALVES INSTALLED IN A FIRE-RATED ROOM
 ACCESSIBLE FROM THE EXTERIOR
 (6) CONTROL VALVES IN A FIRE-RATED STAIR ENCLOSURE
 ACCESSIBLE FROM THE EXTERIOR AS PERMITTED BY THE
 AUTHORITY HAVING JURISDICTION
  
 SHEET C107: PER FBC SECTION403.3.2 WATER SUPPLY TO
 REQUIRED FIRE PUMPS - REQUIRED FIRE PUMPS SHALL BE
 SUPPLIED BY CONNECTIONS TO A MINIMUM OF TWO WATER MAINS
 LOCATED IN DIFFERENT STREETS. SEPARATE SUPPLY PIPING
 SHALL BE PROVIDED BETWEEN EACH CONNECTION TO THE WATER
 MAIN AND THE PUMPS. EACH CONNECTION AND THE SUPPLY
 PIPING BETWEEN THE CONNECTION AND THE PUMPS SHALL BE
 SIZED TO SUPPLY THE FLOW AND PRESSURE REQUIRED FOR THE
 PUMPS TO OPERATE.
  
 SHEET A101: CHILLER #182 HAS A DOOR LEADING INTO THE
 FIRE RATED STAIR ENCLOSURE. PER SECTION 7.1.3.2.1 DOORS
 INTO EXIT ENCLOSURES ARE ONLY PERMITTED FOR NORMALLY
 OCCUPIED ROOMS.
  
 SHEET A101C: THE COOKING GRILL LOCATED ON THE POOL DECK
 SHALL COMPLY WITH NFPA 96 OR SHALL BE LOCATED AT LEAST
 10 FEET FROM ANY BUILDING, STRUCTURE, OR COMBUSTIBLES
 PER NFPA 1 SECTION 10.11.6.1. IF THE GRILL WILL BE USED
 UNDER A ROOF STRUCTURE, THE DESIGN SHALL COMPLY WITH
 NFPA 96.
  
 SHEET A101D: PLANS SHOW OCCUPANTS USING CORRIDOR #185
 AS A MEANS OF EXIT ACCESS; HOWEVER, BOTH SIDES OF THE
 DOOR APPEAR TO BE ACCOMODATING MORE THAN 50 PERSONS AND
 WOULD NEED TO SWING IN BOTH DIRECTIONS OF EGRESS.
  
 SHEET A102B: TRASH ROOM #205C WALL ADJACENT TO
 RESIDENTIAL ROOM DOES NOT APPEAR TO BE FIRE RATED.
 TYPICAL ALL LEVELS.
  
 SHEET A490: PER SECTION 7.2.2.5.4 - STAIRWAY
 IDENTIFICATION: NEW ENCLOSED STAIRS SERVING THREE OR
 MORE STORIES AND EXISTING ENCLOSED STAIRS SERVING FIVE
 OR MORE STORIES SHALL COMPLY WITH (A) THROUGH (L).
 (A) THE STAIRS SHALL BE PROVIDED WITH SPECIAL SIGNAGE
 WITHIN THE ENCLOSURE AT EACH FLOOR LANDING.
 (B) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL.
 (C) THE SIGNAGE SHALL INDICATE THE TERMINUS OF THE TOP
 AND BOTTOM OF THE STAIR ENCLOSURE.
 (D) THE SIGNAGE SHALL INDICATE THE IDENTIFICATION OF
 THE STAIR ENCLOSURE.
 (E) THE SIGNAGE SHALL INDICATE THE FLOOR LEVEL OF, AND
 THE DIRECTION TO, EXIT DISCHARGE.
 (F) THE SIGNAGE SHALL BE LOCATED INSIDE THE ENCLOSURE
 APPROXIMATELY 60-INCHES ABOVE THE FLOOR LANDING IN A
 POSITION THAT IS VISIBLE WHEN THE DOOR IS IN THE OPEN
 OR CLOSED POSITION.
 (G) THE FLOOR LEVEL DESIGNATION SHALL ALSO BE TACTILE.
 (H) THE SIGNAGE SHALL BE PAINTED OR STENCILED ON THE
 WALL OR ON A SEPARATE SIGN SECURELY ATTACHED TO THE
 WALL.
 (I) THE STAIRWAY IDENTIFICATION LETTER SHALL BE LOCATED
 AT THE TOP OF THE SIGN IN MINIMUM 1-INCH HIGH
 LETTERING.
 (J) SIGNAGE THAT READS "NO ROOF ACCESS" AND IS LOCATED
 UNDER THE STAIRWAY IDENTIFICATION LETTER SHALL
 DESIGNATE STAIRWAYS THAT DO NOT PROVIDE ROOF ACCESS.
 LETTERING SHALL BE A MINIMUM OF 1-INCH HIGH.
 (K) THE FLOOR LEVEL NUMBER SHALL BE LOCATED IN THE
 MIDDLE OF THE SIGN IN MINIMUM 5-INCH HIGH NUMBERS.
 MEZZANINE LEVELS SHALL HAVE THE LETTER "M" OR OTHER
 APPROPRIATE IDENTIFICATION LETTER PRECEDING THE FLOOR
 NUMBER, WHILE BASEMENT LEVELS SHALL HAVE THE LETTER "B"
 OR OTHER APPROPRIATE IDENTIFICATION LETTER PRECEDING
 THE FLOOR LEVEL NUMBER.
 (L) IDENTIFICATION OF THE LOWER AND UPPER TERMINUS OF
 THE STAIRWAY SHALL BE LOCATED AT THE BOTTOM OF THE SIGN
 IN MINIMUM 1-INCH HIGH LETTERS OR NUMBERS.
  
 SHEET FP001: ALL NFPA STANDARDS REFERENCES SHALL BE
 UPDATED TO REFLECT THOSE ADOPTED IN THE 5TH EDITION OF
 FLORIDA FIRE PREVENTION CODE EFFECTIVE DECEMBER 31,
 2014. FOR EXAMPLE. THE SPRINKLER AND STANDPIPE DESIGNS
 SHALL CONFORM TO THE 2010 EDITION OF NFPA 13 AND NFPA
 14 RESPECTIVELY.
  
 STANDPIPE DESIGN: PROVIDE 2-1/2" OUTLETS ONLY. REMOVE
 THE 1-1/2" REDUCING COUPLINGS ON ALL FIRE DEPARTMENT
 VALVES.
  
 SHEET FP201B: TRASH ROOM #105C IS MISSING THE
 DESIGNATION FOR ORDINARY HAZARD SPRINKLER PROTECTION.
 TYPICAL ALL FLOORS.
  
 SHEET FP402: ENGINEERING DOCUMENTS ARE REQUIRED TO
 INDICATE THE WATER SUPPLY RESULTS FROM A CURRENT
 HYDRANT FLOW TEST. FIRE PUMP SCHEDULE DOES NOT INDICATE
 A RATED PRESSURE OR HORSEPOWER RATING. THE ENGINEERING
 DOCUMENTS WILL BE REQUIRED TO DETERMINE IF PRESSURE
 REDUCING VALVES ARE NEEDED ON THE STANDPIPES AND
 SPRINKLER SYSTEMS. PRESSURE REDUCING VALVES WILL ALSO
 REQUIRE A 3-INCH DRAIN RISER IN LIEU OF A 2-INCH DRAIN
 RISER AS SHOWN ON THE PLANS.
  
 SHEET FP402: PER FBC SECTION403.3.2 WATER SUPPLY TO
 REQUIRED FIRE PUMPS - REQUIRED FIRE PUMPS SHALL BE
 SUPPLIED BY CONNECTIONS TO A MINIMUM OF TWO WATER MAINS
 LOCATED IN DIFFERENT STREETS. SEPARATE SUPPLY PIPING
 SHALL BE PROVIDED BETWEEN EACH CONNECTION TO THE WATER
 MAIN AND THE PUMPS. EACH CONNECTION AND THE SUPPLY
 PIPING BETWEEN THE CONNECTION AND THE PUMPS SHALL BE
 SIZED TO SUPPLY THE FLOW AND PRESSURE REQUIRED FOR THE
 PUMPS TO OPERATE.
  
  
 SHEET M201B: ALL HVAC KEY NOTES APPEAR TO BE MISLABLED.
  
  
  
  
  
  
 PHASE 2 - FIRE DEPARTMENT REVIEW
  
 SHEET G001: UPDATE THE CODE LIST TO REFERENCE THE 5TH
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2012 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS. PER SECTION 6.1.14.1.2, WHERE
 EXIT ACCESS FROM AN OCCUPANCY TRAVERSES ANOTHER
 OCCUPANCY, THE MULTIPLE OCCUPANCY SHALL BE TREATED AS A
 MIXED OCCUPANCY.
  
 SHEET G101: THE FIRE RATING FOR STAIR #4 DOES NOT
 CONTINUE TO THE EXTERIOR WALLS OR DOORS. PER SECTION
 7.2.2.5.2.1 WHERE NONRATED WALLS OR UNPROTECTED
 OPENINGS ENCLOSE THE EXTERIOR OF A STAIRWAY AND THE
 WALLS OR OPENINGS ARE EXPOSED BY OTHER PARTS OF THE
 BUILDING AT AN ANGLE OF LESS THAN 180 DEGREES, THE
 BUILDING ENCLOSURE WALLS WITHIN 10 FEET HORIZONTALLY OF
 THE NONRATED WALL OR UNPROTECTED OPENING SHALL BE
 CONSTRUCTED AS REQUIRED FOR STAIRWAY ENCLOSURES,
 INCLUDING OPENING PROTECTIVES. PER SECTION 7.2.2.5.2.2
 CONSTRUCTION SHALL EXTEND VERTICALLY FROM THE FINISHED
 GROUND LEVEL TO A POINT 10 FEET ABOVE THE TOPMOST
 LANDING OF THE STAIRS OR TO THE ROOFLINE, WHICHEVER IS
 LOWER.
  
 SHEET L101: SOUTH ACCESS ROAD INDICATES A 20 FOOT WIDE
 FIRE LANE AT THE POOL GATE; HOWEVER, THE SOUTHWEST AREA
 INDICATES EXISTING ROADS THAT DO NOT APPEAR TO BE 20
 FEET WIDE AND MARKED AS A FIRE LANE. PER SECTION
 18.2.3.4.1.1 (NFPA 1), FIRE DEPARTMENT ACCESS ROADS
 SHALL HAVE A SURFACE DESIGNED TO ACCOMMODATE FIRE
 APPARATUS WEIGHING AT LEAST 36 TONS. ACCESS ROADS SHALL
 HAVE AN UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND
 AN UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 13
 FEET 6 INCHES. PER SECTION 18.2.3.5.3 (NFPA 1), FIRE
 LANES SHALL BE MARKED WITH FREESTANDING SIGNS READING,
 "FIRE LANE - NO PARKING BY ORDER OF THE FIRE
 DEPARTMENT." SIGNS SHALL BE 12" X 18" WITH A WHITE
 BACKGROUND AND RED LETTERS AND SHALL BE A MAXIMUM OF
 SEVEN FEET IN HEIGHT TO THE BOTTOM OF THE SIGN. SIGNS
 SHALL BE WITHIN SIGHT OF THE TRAFFIC FLOW AND BE SPACED
 A MAXIMUM OF 60 FEET APART.
  
  
  
 DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2016-03-17 Cont ID  
Sent By tklarge Date 2015-09-03 Time 10:04 Rev Time 0.00
Received By tklarge Date 2015-09-03 Time 10:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-09-09 Cont ID  
Sent By lmarchan Date 2015-09-09 Time 13:48 Rev Time 0.00
Received By lmarchan Date 2015-09-08 Time 14:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-09-02 Cont ID  
Sent By hmoser Date 2015-09-02 Time 14:50 Rev Time 0.00
Received By hmoser Date 2015-07-14 Time 11:02 Sent To  
Notes
2015-07-28 16:27:15CLOSED DUE TO MORE PLANS BEING UPLOADED

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-23 Cont ID  
Sent By lmarchan Date 2015-06-23 Time 15:20 Rev Time 0.00
Received By lmarchan Date 2015-03-06 Time 14:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-28 Cont ID  
Sent By skennedy Date 2015-01-28 Time 10:31 Rev Time 0.00
Received By skennedy Date 2015-01-05 Time 14:29 Sent To  
Notes
2015-08-03 09:55:041/28/15 APPLICANT HAS CHOSEN TO END THE REVIEW CYCLE
 AND RESUBMIT FULL PLANS AND CHANGE PERMIT TYPE, PERMIT
 DESCRIPTION, AND PAY ADDITIONAL FEES UPON RE-SUBMITTAL.
 SAK

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-07-29 Cont ID  
Sent By shill Date 2015-07-29 Time 18:03 Rev Time 0.00
Received By shill Date 2015-07-29 Time 18:03 Sent To  
Notes
2015-07-29 18:03:47IMPACT FEES FOR PHASE I & II
  
 MU 2015 016915 0000
 MU 2015 016916 0000

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-05-05 Cont ID  
Sent By shill Date 2015-05-05 Time 16:47 Rev Time 0.00
Received By shill Date 2015-05-05 Time 16:47 Sent To  
Notes
2015-05-05 16:47:52BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 THIS CAN BE DONE AT ANY TIME DURING THE PLAN REVIEW
 PROCESS BUT MUST BE COMPLETED AND SUBMITTED FOR REVIEW
 PRIOR TO PERMIT ISSUANCE.
  
 SAMANTHA HILL
 561-805-6724
 [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-01-10 Cont ID  
Sent By jwitmer Date 2015-01-10 Time 13:06 Rev Time 0.00
Received By jwitmer Date 2015-01-10 Time 13:05 Sent To  
Notes
2015-01-10 13:06:39BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-09-02 Cont ID  
Sent By hmoser Date 2015-09-02 Time 14:50 Rev Time 0.00
Received By hmoser Date 2015-08-28 Time 09:10 Sent To  
Notes
2015-09-02 14:50:11PASS REVISION REQUIRED
 1) PROVIDE ACCESS FOR VAV 2-7, 2-8 AND 2-9 ON PAGE
 M201.B
 2) PUT ALL MECHANICAL PLANS TOGETHER TO MAKE PLAN
 REVIEW LESS CONFUSING
 3) COULD NOT FIND ENERGY CALCULATIONS,COME TO FIND
 SUPPORTING DOCS HAD OVER
 300 PAGES. PLEASE INDEX SUPPORTING DOCS.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-06-01 Cont ID  
Sent By hmoser Date 2015-06-01 Time 09:51 Rev Time 0.00
Received By hmoser Date 2015-05-26 Time 11:30 Sent To  
Notes
2015-06-01 09:51:37PLAN DENIED
 1) PROVIDE ENERGY CALCULATIONS WITH THE
 PLANS. PER SECTION 503.2.1 CALCULATIONS
 OF HEATING AND COOLING LOADS. 2010
 FLORIDA ENERGY CODE.
 2) PROVIDE FRESH AIR CALCULATIONS ON PLAN
 PER TABLE 403.3 FBC (M) 2010
 3) DRYER BOOSTER FANS ARE NOT PERMITTED
 IN THE CITY OF WEST PALM BEACH PER WPB.
 FIRE DEPARTMENT.
 4) MISSING FIRE DAMPERS ON 1ST FLOOR
 REFER TO SECTION 607 FBC (M) 2010
 5) PROVIDE NOA ON ALL OUTSIDE GRILLS
 PER SECTION 107.3.4.1 GENERAL 2010 FBC.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2015-09-03 Cont ID  
Sent By tklarge Date 2015-09-03 Time 11:46 Rev Time 0.00
Received By tklarge Date 2015-09-03 Time 11:46 Sent To  
Notes
2015-09-03 11:49:30PLUMBING PASSED WITH PROVISOS. SEE PLAN REVIEW COMMENTS
 DATED 8/17/15. ALL PLUMBING PLAN REVIEW CORRECTIONS
 SHALL BE SUBMITTED WITHIN 60 DAYS OF IISUANCE OF MAIN
 PERMIT. T. LARGE.

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-08-17 Cont ID  
Sent By tklarge Date 2015-08-17 Time 06:45 Rev Time 0.00
Received By tklarge Date 2015-08-08 Time 06:41 Sent To  
Notes
2015-08-12 06:42:501) SHT.063-AS109 - DETAIL #1 - THE MAXIMUM HEIGHT OF
 THE SINK CABINET SHALL BE 36 INCHES PER THE FAIR
 HOUSING ACT CFR 100.205 (C) (1).ONE OF THE SINKS SHALL
 HAVE A 30 INCH WIDE BY 48 INCH LONG CLEAR FLOOR SPACE
 CENTERED ON THE FIXTURE. SHOW THE REQUIRED CLEAR FLOOR
 SPACE ON THE PLAN. THE RESPONSE NARRATIVE WHICH REFERS
 TO FBC-A SEC. 233.3.1 EXCEPTION IS NOT APPLICABLE.
 (COMMENT # 6).
 2) SHT. 262-P.003 - THE PLAN STILL SHOWS A GENERATOR
 BUT THE RESPONSE NARRATIVE STATES THE GENERATOR HAS
 BEEN REMOVED FROM THE PERMIT SET. CLARIFY.(SEE PREVIOUS
 REVIEW COMMENT #9).
 3) SHT.074-A101 - THE SINK IN THE ART STUDIO #124 AND
 BREAK ROOM (#167) SHALL COMPLY WITH THE FAIR HOUSING
 ACT CFR 100.205 (C) (1).THE SINKS SHALL HAVE A MAXIMUM
 HEIGHT OF 36 INCHES AND SHALL HAVE A CLEAR FLOOR SPACE
 OF 30" X 48" CENTERED ON THE FIXTURE. SHOW THE REQUIRED
 CLEAR FLOOR SPACES ON THE PLAN. THE RESPONSE NARRATIVE
 WHICH REFERS TO FBC-A SEC. 233.3.1 EXCEPTION IS NOT
 APPLICABLE. (COMMENT#10) .
 4) SHT. 146- A400 - SHOW THE MINIMUM AND MAXIMUM HEIGHT
 DIMENSIONS FOR THE LOCATION OF THE REINFORCEMENT FOR
 THE GRAB BARS. 2ND REQUEST. COMPLY WITH CFR 100.205 (6)
 & ANSI A117.1. (SEE PREVIOUS REVIEW COMMENT #11).
 5) CLARIFY THE RESPONSE NARRATIVE TO MY PREVIOUS REVIEW
 COMMENT #14. THIS PROJECT CLEARLY FALLS UNDER THE FAIR
 HOUSING ACT YET THE RESPONSE FROM PERKINS EASTMAN
 STATES THE A OR B DESIGN SPECIFICATION IS NOT REQUIRED
 SINCE THE PROJECT MEETS FBC-A 233.3.1, EXCEPTION.
 6) SHT. 168-A451 - DETAIL # 10-MEN'S & WOMEN'S
 RESTROOMS - BOTH OF THE AMBULATORY STALLS SHALL HAVE
 GRAB BARS ON NOTH SIDES OF THE STALL PER 2010
 FBC-ACCESS. SEC.604.8.2.3.
 7) SHT. 169-A452 -DETAIL # 020 - THERE ARE NO DETAILS
 FOR THE SEAT IN THE SHOWER IN THE ACCESSIBLE CHANGING
 ROOM. THE SEAT SHALL COMPLY WITH ANSI A117.1 -1986
 SEC.4.24.
 8) SHT. 185-A510 - DETAIL # 2 - SHOW THE REQUIRE KNEE &
 TOE CLEARANCES FOR THE SINK PER ANSI A117.1 - 1986.
 9) SHT. 153-403(A) -DETAIL #2 - SHOW THE REQUIRED 30
 INCHES BY 48 INCHES CLEAR FLOOR SPACE REQUIRED FOR THE
 SHOWER PER THE FHA GUDELINES AND CFR 100.205.
 10) SHOW THE DEPTH OF THE TYPICAL LAVATORY IN THE
 LIVING UNITS. THE LAVATORIES SHALL NOT EXCEED 24 INCHES
 IN DEPTH PER THE FHA GUIDELINES.
 11) SHT. 148-A401B - DETAIL # 1A - SHOW THE DISTANCE
 BETWEEN THE CABINETS . COMPLY WITH THE FHA GUIDELINES
 REQUIREMENT #7 AND CFR 100.205.ALSO, SEE DETAIL #1.
 12) SHT.144-A352 - DETAIL # 9 - CLEARLY IDENTIFY THE
 SCUPPER ON THE DETAIL AND SHOW THE SCUPPER OPENING.
 SCUPPERS SHALL NOT HAVE AN OPENING DIMENSION LESS THAN
 4 INCHES PER 2010 FBC-SEC.1107.3.
 13) PLAN REVIEW COMMENT #24 - THE RESPONSE NARRATIVE
 REFERS TO DRAWINGS # FS-2E & FS-3E. THERE ARE NO SUCH
 DRAWINGS IN THIS PLAN SET. CLARIFY.
 14) WHY ARE PLANS FOR "EDWARD'S PAVILLION" INCLUDED
 WITH THESE PLANS?
 15) SHT. 2075 -A407 IS NUMBERED AS A PHASE II DRAWING
 IN THE NAMING CONVENTION BUT THE PLAN IS LISTED AS
 BEING IN PHASE I ON THE PLAN ITSELF. CLARIFY.REFER TO
 LOWER RIGHT HAND CORNING OF DRAWING. SHT. 2129-P4.02
 WHICH ARE THE RISERS FOR THIS AREA IS NOTED AS PHASE
 II. WHICH IS IT?
 16) SHT.2128-P4.01 - ONE OF THE RISERS IS MISSING ITS
 IDENTIFYING NUMBER.
 17) PLAN REVIEW COMMENT # 35 - SHT. 2126-P201B & 2130-
 P403 - IDENTIFY THE OTHER TWO WATER MAINS AND PROVIDE
 THE PAGE NUMBER FOR THE CONTINUATION POINT.WPB AMEND.
 TO FBC SEC. 107.2.1. THE RESPONSE NARRATIVE REFERS TO
 REVISED SHEETS P001 & P403. THESE SHEETS HAVE NOT BEEN
 REVISED & P003 IS A PLUMBING SITE PLAN. CLARIFY. 2ND
 REQUEST.
 18) PLAN REVIEW COMMENT # 37 - EXPLAIN HOW HALF OF UNIT
 A1C CAN BE LOCATED IN PHASE I AND THE OTHER HALF IN
 PHASE II. THE RESPONSE NARRATIVE NOTES THAT THE ROOM
 NAME HAS BEEN CHANGED TO "STORAGE". THIS HAS NOT BEEN
 DONE. IT IS STILL A LIVING UNIT. CLARIFY.
 19) PLAN REVIEW COMMENT # 39 - SHT.2135-P501 - SHOW THE
 SIZE OF THE COPPER DWV LINE FROM THE WASHING MACHINE.
 THE MINIMUM SIZE SHALL BE 2". THE RESPONSE NARRATIVE
 NOTES THAT THE DETAIL HAS BEEN REMOVED FROM THE SHEET
 BUT IN FACT IT HAS NOT. NOTHING HAS BEEN DONE TO THE
 SHEET IN THE SET. CLARIFY.
 20) PLAN REVIEW COMMENT # 2131-P404 - THE SIZE OF THE
 WATER RISERS DO NOT MATCH FROM THE 9TH TO THE 10TH
 FLOOR. I ASSUME THE LINES ARE BEING REDUCED BECAUSE OF
 THE NUMBER OF FIXTURES AT THE 10TH FLOOR. THE RESPONSE
 NARRATIVE REFERS TO REVISED SHT.P404 BUT THERE IS NO
 REVISED SHEET IN THE SET. REFER TO RISERS #
 24,26,27,29,30 & 31. ALSO , THERE ARE NO PIPE SIZES ON
 THE RISERS ON WATER RISER #24 AT THE TENTH FLOOR
 LEVEL.CLARIFY.
 21) PLAN REVIEW COMMENT # 41 - SHT. 2131-P404 - WATER
 RISER #28 IS NOT SHOWN ON THE PLAN.THE RESPONSE
 NARRATIVE NOTES " SEE REVISED SHEET P404. THERE IS NO
 REVISED SHEET P404 IN THE SET. CLARIFY.
 22) PLAN REVIEW COMMENT # 53 - SHT.261-P002 - SUBMIT
 MANUFACTURER'S SPECIFICATION SHEETS FOR THE ELEVATOR
 SUMP PUMP. COMPLY WITH 2010 FBC-PLUMBING SEC.1003.4 -
 EXCEPTION. THE RESPONSE NARRATIVE NOTES "SEE REVISED
 SHEET P002. THERE IS NO REVISED SHEET P002. CLARIFY.
 23) PLAN REVIEW COMMENT # 55 - SHT.262-P003 - PLUMBING
 KEYNOTE #3 STATES THAT THE COOLING TOWER WATER TO
 DISCHARGE TO THE SANITARY. COOLING WATER CANNOT
 DISCARGE TO THE SANITARY PER CWPB ORD. SECTION 90-126
 (5). COOLING TOWER WATER SHALL NOT DRAIN TO THE
 STORMWATER SYSTEM PER CITY ORD. SEC.90-203. THE NOTE IS
 STILL ON THE PLAN. CLARIFY.
 24) PLAN REVIEW COMMENT # 56 - SHT. 299- P501 SHOW THE
 SIZE OF THE INTERCEPTORS AS 1500 GALS. THE MAXIMUM SIZE
 OF AN INDIVIDUAL GREASE INTERCEPTOR CHAMBER SHALL BE
 1250 GALS. PER 2010 FBC-PLUMBING SEC.1003.5.1.WHEN THE
 CAPACITY IS GREATER THAN 1250 GALLONS, MULTI-CHAMBERED
 GREASE INTERCEPTORS OR GREASE INTERCEPTORS IS SERIES
 SHALL BE REQUIRED.
 25) PLAN REVIEW COMMENT #69 - INDICATE ON THE STORM
 RISER PLANS OR ON SHEETS 275-P105 & 276-P106 THAT THE
 DESIGN OF THE STORM DRAINAGE SYSTEM INCLUDES 1/2 THE
 AREA OF ANY VERTICAL WALLS THAT DIVERTS RAINWATER TO
 THE ROOF. THE DESIGN SHALL ALSO INCLUDE THE SQUARE
 FOOTAGE OF ANY SLOPED ROOF THAT DIVERTS RAINWATER TO
 THE FLAT ROOFS.2010 FBC-PLUMBING SEC.1106.4.
 26) SHT. 268-P101C - THE NOTES AT THE GREASE TRAP ARE
 DIFFICULT TO READ. THERE IS OTHER TEXT OVER TOP OF
 IT.PLEASE CORRECT, WPB AMEND. TO FBC SEC. 107.2.1.
 27) SHT.299-P501 - SHOW THE PIPE SIZES OF ALL SECTIONS
 OF PIPE FOR THE DOMESTIC BOOSTER WATER PUMP,WATER
 SOFTENER AND PRESSURE REDUCING STATION. WPB AMEND. TO
 FBC SEC. 107.2.1.
 28) SHT. 280-P301 - THE SANITARY AND WATER RISERS FOR
 UNIT A1C ARE MISSING THE IDENTIFYING NUMBERS.
 29) SHT.297-P412 - SHOW THE DISTANCE IN DEVELOPED
 LENGTH FROM EACH LINE PRESSURE REGULATOR TO THE MOST
 REMOTE OUTLET AND THE LOAD OF THE SECTION.SHOW THE
 LENGTHS OF EACH SECTION OF PIPE FOR THE 2 PSI SYSTEM
 AND THE LESS THAN 2 PSI SYSTEM. 2010 FBC-FUEL GAS SEC.
 402.4.1, NFPA 54 SEC.6.1.3.
 30) SHT.297-P412 - THE GAS RISER IS SHOWING 4,996 CFH
 ON A 1 1/4" LINE AT 2 PSI. THE SIZING TABLE REFERENCED
 ON THE DRAWING ALLOWS A MAXIMUM OF 1,470 CFH AT 2 PSI
 ON AN 1 1/4" LINE. IT APPEARS THE LINE IS SEVERELY
 UNDERSIZED.THE MINIMUM SIZE SHALL BE 2 1/2 INCHES.
 31) SHT. 297-P412 - THE BTU LOAD AT POINT D ON THE
 DRAWING DOES NOT EQUAL THE SUM OF THE BTU'S OF THE
 LISTED FIXTURES. CLARIFY.
 32) SHOW THE BRANCH LINES TO THE POOL AND KITCHEN AREA
 ON THE GAS RISER DIAGRAM AND SIZE THE LINE AND SUPPLY
 THE BTU LOAD FOR THE BRANCH LINES.WPB AMEND. TO FBC
 SEC. 107.3.5.1.
 33) THE SIZE OF THE GAS LINE TO THE FIREPLACE MAY
 BEREQUIRED TO BE A MINIMUM OF 3/4" PER TABLE 6.2 (A) OF
 NFPA 54.
 34) THE CFH AT THE METER SHOW 5020.3 CFH BUT THE CFH ON
 THE 1 1/4" LINE DOWNSTREAM OF THE METER SHOWS 4,996
 CFH, WHERE DID THE ADDITIONAL LOAD AT THE METER COME
 FROM? CLARIFY.
 35) PLEASE EXPLAIN THE NOTATION OF "8 OZ." ON THE GAS
 DRAWING.
 36) THE PRV 'S SHALL COMPLY WITH THE FBC- FUEL GAS
 SEC.410.2 (4),(5), (6),& 410.3.
 37)THE LINE FROM THE METER TO POINT "B" SHALL BE A
 MINIMUM OF 2 1/2 INCHES PER NFPA 54 TABLE 6.2 (C).
 38) LIST THE CORRECT APPLICABLE GAS SIZING TABLES FOR
 EACH TYPE OF MATERIAL BEING USED . WPB AMEND. TO FBC
 SEC. 107.3.5.1.3.
 39) THE BTU LOAD DOWNSTREAM OF OF POINT "D" APPEARS
 INCORRECT. ADDING THE 1,996 CFH FROM THE POOL AND
 KITCHEN AREA TO THE BTU LOAD COMES TO 3,310.3. RE-CHECK
 YOUR CALCULATIONS.(SEE AREA AT 2020.3 CFH). CHECK THE
 ENTIRE SYSTEM FOR CORRECT SIZING.
 40 ) THE BTU LOAD UPSTREAM OF POINT "D" SHOULD BE
 6310.3.I CALCULATE THE ENTIRE BTU LOAD ON THE SYSTEM AS
 7610.3 CFH. CLARIFY.
 41) PVC IS NOT PERRMITED TO BE USED TO VENT REGULATORS
 INDOORS PER FBC-FUEL GAS SEC.403.6.3.
 42.) SHT. 297-P412 - SHOWS THE GAS PIPING BEING
 INSTALLED UNDER THE SLAB. THIS METHOD IS PERMITTTED IF
 THERE IS NO OTHER METHOD TO INSTALL THE PIPING. IF THE
 PIPING CAN BE RUN OVERHEAD THAT IT HOW IT SHALL BE
 INSTALLED. IF THERE IS NO OTHER METHOD, THE
 INSTALLATION SHALL COMPLY WITH 2010 FBC-FUEL GAS
 SEC.404.12.1 OR 404.12.2. THE VENT TO THE ROOF IS NOT
 AN ACCEPTED METHOD.
 43) THE PLAN SHOWS PE PIPE IN THE CONDUIT. PLASTIC PIPE
 SHALL BE INSTALLED OUTDOORS UNDERGROUND ONLY PER
 FBC-FUEL GAS SEC.404.15.1.
 44) PLAN REVIEW COMMENT # 77 - SHT. 297-412 - SUBMIT
 CALCULATIONS FOR COMBUSTION AIR IN ACCORDANCE WITH 2010
 FBC-FUEL GAS SEC. 304. SUBMIT DETAILS ON THE
 LOCATION/TERMINATION AND TYPES OF GAS VENTS, HEIGHT
 ABOVE THE ROOF, ETC.THE RESPNSE NARRATIVE REFERS TO
 DRAWINGS M206, M503 & M505. THERE ARE NO SUCH DETAILS
 ON M206 AND I COULD NOT FIND A SHEET LABELED M505.
 CLARIFY.
 45) IT APPEARS THAT CALCULATIONS FOR COMBUSTION AIR FOR
 THE GAS SYSTEM HAVE NOT BEEN SUBMITTED. I COULD NOT
 FIND THE CALCULATIONS ON ANY PLANS. CLARIFY.
 46) SHT.332-M504 - DETAIL #3 REFERS TO DETAIL #6 ON
 SHT. 327-M404. THERE IS NO SUCH DETAIL. CLARIFY.
 47) SUBMIT VENT DETAILS FOR THE POOL HEATERS . WPB
 AMEND. TO FBC SEC. 107.3.5.1.3.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-05-18 Cont ID  
Sent By tklarge Date 2015-05-18 Time 15:27 Rev Time 0.00
Received By tklarge Date 2015-04-11 Time 12:06 Sent To  
Notes
2015-05-06 10:24:231) THIS BUILDING IS CLASSIFIED AS AN R-2 OCCUPANCY ON
 SHT. G001 (001) AND IS EQUIPPED WITH AN ELEVATOR
 THEREFORE ALL THE RESIDENTIAL UNITS ON ALL THE FLOORS
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FEDERAL FAIR
 HOUSING ACT AND SEC. 233 OF THE 2010 FL. ACCESSIBILITY
 CODE.UNDER THE HEADING "FBC 2010 ACCESSIBILITY
 ACCESSIBLE UNITS" THERE IS A REFERENCE TO CODE SECTION
 11-9.1.4. THERE IS NO SUCH CODE SECTION IN THE 2010
 FBC.HOW ARE YOU ARRIVING TO THE FACT THAT ONLY 5% OF
 THE UNITS HAVE TO COMPLY WITH HANDICAP REQUIREMENTS?
 CALRIFY.
 2) THE APPLICATION SUBMITTED WITH THESE PLANS STATE
 "FOUNDATION ONLY" YET THE PLANS ARE FULL SETS FOR PHASE
 I & PHASE II. THE APPLICATION DOES NOT STATE IF THE
 FOUNDATION PLAN IS FOR BOTH PHASES OR JUST ONE.
 CLARIFY.
 3) SHT.G101 - CLARIFY HOW YOU ARRIVED AT THE REQD.
 FIXTURES FOR THE GROUP A-1, A-2, A-3 OCCUPANCIES. I
 CAME UP WITH SLIGHTLY DIFFERENT DECIMAL EQUIVQLENTS.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 4)SHT.G101 - DEFINE THE ASTERISKS ON THE PLUMBING
 FIXTURE TABLE. I DO NOT SEE ANY FOOTNOTES. CLARIFY.
 5) SHT. AS 106 - THE WATER SUPPLY FOR THE FOUNTAIN
 SHALL BE EQUIPPED WITH A BACKFLOW PREVENTION DEVICE PER
 2010 FPC SEC.608.1.
 6) SHT. AS 109 ( DETAIL #1 ) THE SINK SHALL COMPLY
 W/THE FAIR HOUSING ACT FOR ACCESSIBLE AND USABLE PUBLIC
 AND COMMON USE AREAS PER CFR 100.205.
 7) SHT. AS 106 - THE WATER SUPPLY FOR THE FOUNTAIN
 SHALL BE EQUIPPED WITH A BACKFLOW PREVENTION DEVICE PER
 2010 FPC SEC.608.1.
 8) SHT. AS109 - FLOOR DRAINS ARE SHOWN IN THE POOL
 SERVICE AREA. INDICATE IF THEY ARE CONNECTED TO THE
 STORM OR SANITARY SYSTEM.
 9) SUBMIT COMPLETE DETAILS FOR THE EMERGENCY GENERATOR.
 SUBMIT MANUFACTURER'S SPECS, FUEL AND FUEL PIPING
 DETAILS,GENERATOR EXHAUST, ETC. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 10) THE SINK IN THE ART STUDIO #124 ANF THE BREAK ROOM
 SINK #167 SHALL COMPLY W/THE FAIR HOUSING ACT FOR
 ACCESSIBLE AND USABLE PUBLIC AND COMMON USE AREAS PER
 CFR 100.205.
 11) SHT. A-400 SHOW THE LENGTH AND WIDTH DIMENSIONS OF
 THE REINFORCING FOR THE GRAB BARS FOR THE SHOWERS,
 TUBS, & WATER CLOSETS. ALSO, SHOW THE MINIMUM AND
 MAXIMUM HEIGHT DIMENSIONS FOR THE LOCATION OF
 REINFORCEMENT. COMPLY WITH CFR 100.205 (6) & ANSI
 A117.1.
 12) SHT. A401B - SHOW THE CLEAR INSIDE DIMENSIONS (L X
 W) OF THE SHOWER. A 30 X 48 INCH CLEAR FLOOR SPACE
 SHALL BE PROVIDED AT SHOWER STALLS, PARALLEL TO THE
 FIXTURE AND FLUSH WITH THE CONTROL WALL.
 13) SHT. A403 SHOW THE HEIGHTS OF THE CABINETS, GRAB
 BARS, ETC. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 14) INDICATE ON THE PLANS THE DESIGN SPECIFICATION (A
 OR B) BEING USED FOR THE DESIGN OF THE USABLE BATHROOMS
 .SPECIFICATION A APPLIES TO ALL BATHROOMS IN THE
 COVERED DWELLING UNIT AND ALL FIXTURES IN THOSE
 BATHROOMS MUST BE USABLE . SPECIFICATION B APPLIES TO
 ONE BATHROOM AND ONLY ONE OF EACH TYPE OF FIXTURE MUST
 BE USABLE; ADDITIONAL BATHROOMS IN THE UNIT ARE EXEMPT
 ONLY FROM MANEUVERING AND CLEAR FLOOR SPACE AT
 FIXTURES.
 15) SHT. A451 SHOW THE LENGTH OF THE AMBULATORY TOILET
 STALLS IN THE MEN'S & WOMEN'S RESTROOMS. COMPLY WITH
 THE 2010 FAC SEC. 604.8.2.1. DOORS SHALL NOT SWING INTO
 THE MINIMUM REQUIRED COMPARTMENT AREA PER SEC.
 604.8.2./ANSI A117.1.
 16) SHT. A452 GRAB BARS ARE REQUIRED IN THE ACCESSIBLE
 SHOWER IN THE ACCESSIBLE CHANGING ROOM. FAC SEC. 608.3
 & 609.4. A SEAT SHALL ALSO BE PROVIDED PER FAC
 SEC.608.4.
 17) SHT.A452 THE ACCESSIBLE CHANGING ROOM IS LISTED AS
 #149 ON THE PLAN VIEW IN DETAIL #014 AND AS #142 & 143
 ON THE ELEVATION DETAILS. IS THIS A TYPO? CLARIFY.
 18) SHT. A506 INDICATE ON THE PLAN IF THE FIREPLACE IS
 WOOD OR GAS BURNING. IF GAS, SUBMIT MANUF.
 SPECIFICATIONS FOR THE UNIT AND SHOW IT ON THE GAS
 RISER. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 19) SHT.A510 DETAIL #2 SHOW THE REQUIRED CLEARANCES FOR
 THE ACCESSIBLE LAVATORY PER THE FAC SEC.306.
 20) PLACE THE PLANS IN ORDER AS THEY ARE LISTED IN THE
 INDEX SHEET. TIME IS WASTED SEARCHING FOR THE LOCATION
 OF PLANS. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 21) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL THE
 GAS EQUIPMENT & APPLIANCES. APPLIANCES & EQUIPMENT
 SHALL BE LISTED PER THE 2010 FBC-FUEL GAS CODE SEC.
 301.3. MANUFACTURER'S INSTALLATION INSTRUCTIONS FOR ALL
 APPLIANCES/EQUIPMENT SHALL BE ON THE JOBSITE PER 2010
 FBC-FUEL GAS CODE SEC.305.1.
 22) FOOD SERVICE DRAWINGS. SUBMIT MANUFACTURING
 SPECIFICATIONS FOR ALL GAS EQUIPMENT. EQUIPMENT SHALL
 BE LISTED AND LABELED PER FBC-FUEL GAS SEC. 301.3.
 23) FOOD SERVICE EQUIPMENT SHALL BE NSF APPROVED .2010
 FBC-PLUMBING SEC.409.
 24) SHT. FS-4 - PLUMBING CONNECTION DETAILS FOR ITEMS #
 36,38,140. THERE IS NO LEGEND FOR THE ITEM #140 ON THE
 FS DRAWINGS. CLARIFY.
 25) SHT. P105 (2-125) PHASE II THE PLAN SHOWS A 4"
 RAINWATER LEADER (RL 13) WITH 1535 SQ. FEET DRAINING
 INTO IT. THE MAXIMUM SQUARE FOOTAGE IS 1504 PER
 FBC-PLUMBING TABLE 1106.3.SEE DRAIN NEAR GRIDLINE
 G/2.8.
 26) PROVIDE A SCUPPER DETAIL. SCUPPERS SHALL NOT HAVE
 AN OPENING DIMENSION LESS THAN 4 INCHES. 2010- FBC-
 PLUMBING SEC. 1107.3. SCUPPERS SHALL COMPLY WITH 2010
 FBC SEC. 1503.4.2.1.
 27) SHT.P100B (2-120) DOES NOT CORRELATE WITH THE
 SANITARY RISER ON SHT. P401 (2-128) AS TO THE LAYOUT.
 BRANCHES ARE SHOWN ON P100B THAT ARE NOT ON P401. ALSO
 SANITARY RISER #33 DOES NOT APPEAR TO CONNECT TO THE
 BUILDING DRAIN. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 28) SHT.P401 (2-128) THERE ARE NO CONTINUATION POINTS
 SHOWN FOR THE STACK VENTS OR BRANCH VENTS. CLARIFY. I
 HAVE IDENTIFIED THESE AREAS WITH A MARKUP.
 29) SHT. P100B (2-120) THERE IS A CD RISER & A SANITARY
 RISER THAT IS NOT NUMBERED. CLARIFY.IT HAS BEEN
 IDENTIFIED THEM WITH A MARKUP. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 30) SHT.P101B (2-121) ROOM #133.THERE IS A CD RISER
 THAT IS NOT NUMBERED.CLARIFY. IT HAS BEEN IDENTIFIED
 WITH A MARKUP.
 31) SHT. P102B (2-122) THERE IS A SANITARY RISER THAT
 IS NOT IDENTIFIED BY A NUMBER. SEE GRIDLINE F/4.2. IT
 IS IDENTIFIED WITH A MARKUP. CLARIFY. THIS OCCURS ON
 ALL LEVELS.
 31) SHT. P402 (2-129) WHERE IS SANITARY RISER #31?
 CLARIFY.
 32) SHT. P402 (2-129) SANITARY RISER #29 WC-1 APPEARS
 TO BE DRAINING INTO A 2 INCH LINE. IT APPEARS AS THOUGH
 WC-1 MAY BE MISLABELED. IF IT IS A WATER CLOSET THEN
 THE 3 " VENT STACK NEEDS TO BE INCREASED TO 4 INCHES
 PER 2010 FPC TABLE 916.1. CLARIFY.
 33) SHT. P402 (2-129) SANITARY RISER #29 DOES NOT
 COMPLY WITH FPC 2010 SEC. 909.1 FOR THE TYPE OF
 FIXTURES PERMITTED ON A HORIZONTAL WET VENT. ALSO, SIZE
 THE HORIZONTAL DRAIN BETWEEN WC-1 AND OB-1 ON THE
 RISER.
 34) SHT. P402 (2-129) SANITARY RISERS #28 AND #31 ARE
 NOT SHOWN ON THE PLAN. CLARIFY.
 35) SHT. P403 (2-130) & P201B (2-126) IDENTIFY THE
 OTHER TWO WATER MAINS AND PROVIDE PAGE NUMBER FOR
 CONTINUATION POINT. PROVIDE IDENTIFICATION LEGEND FOR
 THE MAINS. WPB AMEND. TO 2010 FBC SEC. 107.2.1.,
 107.3.5.1.3.
 36) SHT. P201B (2-126) OB-1 AND WC-1 (UNIT D2 # 102) -
 THE SYMBOL IS SHOWN ON THE PLAN VIEW BUT THERE IS NO
 WATER PIPING SHOWN TO THE FIXTURE. CLARIFY.
 37) SHT. P301 (2-127) - EXPLAIN HOW HALF OF UNIT A1C
 CAN BE LOCATED IN PHASE I AND THE OTHER HALF IN PHASE
 II. WHAT OCCURS IF BOTH PHASES ARE NOT BUILT AT THE
 SAME TIME?
 38) IT IS EXTREMELY DIFFICULT TO FIGURE WHICH
 CONDENSATE, SANITARY AND WATER RISER APPLY TO WHICH
 MODEL UNITS. SHOW THE LOCATION AND IDENTIFY THE RISERS
 ON THE ENLARGED FLOOR PLANS FOR THE UNITS. WPB AMEND.
 TO 2010 FBC SEC.107.2.1, 107.3.5.1.3.
 39) SHT. P501 (2-135) SHOW THE SIZE OF THE COPPER DWV
 LINE FROM THE WASHING MACHINE. THE MIN. SIZE OF THE
 TRAP & STANDPIPE SHALL BE 2" AND SHALL CONNECT TO A
 BRANCH DRAIN OR DRAINAGE STACK THAT IS A MINIMUM OF 3
 INCHES. FPC SEC.406.3. SEE ALSO SHT. P404.
 40) SHT. P404 (2-131) THE SIZE OF THE WATER RISERS DO
 NOT MATCH FROM THE 9TH TO THE 10TH FLOOR. REFER TO
 RISESRS # 24, 26, 27,29,30, & 31. CLARIFY.
 41) SHT. P404 (2-131) WATER RISER #28 IS NOT SHOWN ON
 THE PLAN. CLARIFY.
 42) 42) SHT.P105 (2-125) SUBMIT DETAILS FOR SECONDARY
 (EMERGENCY) ROOF DRAINAGE PER 2010 FBC-PLUMBING,
 SECS.1107.1, 1107.2, 1107.3 AND 2010 FBC-BUILDING,
 SECS. 1503.4.1, 1503.4.2.1.
 43) SHT.P405 (2-132) INDICATE THE SLOPE OF ALL THE
 HORIZONTAL STORM DRAIN PIPING. COMPLY WITH 2010
 FBC-PLUMBING TABLE 1106.3.
 COMMENTS ON THE STORM DRAIN SYSTEM ARE ASSUMING A 1%
 SLOPE ON THE PIPE.
 44) SHT.P405 (2-132) IF THE SLOPE OF THE PIPE IS 1/8"
 UNIT VERTICAL IN 12 UNITS HORIZONTAL (1% SLOPE), THEN
 THE UNDERGROUND STORM DRAIN DOWNSTREAM OF RL/ 9 MUST BE
 10", NOT 8".
 45) SHT.P405 SIZE THE STORM DRAIN DOWNSTREAM OF RL/2.
 46) SHT. P405 CHECK THE CALCULATIONS FOR THE TOTAL
 SQUARE FOOTAGE BEING DRAINED. MY CALCULATIONS ARRIVE AT
 32,200 SQ. FT.
 47) SHT.P407 (2-134) THE CONDENSATE RISER SHOWS 1/2"
 DRAINS FROM THE FAN COIL UNITS. THE MINIMUM SIZE DRAIN
 SHALL BE 3/4" I.D. PER FBC-PLBG., SEC.314.2.2 & TABLE
 314.2.2.
 48) SHT.P407 (2-134) IDENTIFY ALL THE CONDENSATE
 RISERS. (U/G, ROOF LEVEL, FAN COIL DETAILS) IT IS
 EXTREMELY DIFFICULT AND TIME CONSUMING TO TRY TO
 DETERMINE WHERE THESE RISERS ARE LOCATED. WPB AMEND. TO
 WPB SEC. 107.3.5.1.3.
 49) THE CONDENSATE RISERS FOR THE FAN COILS SHOW A 3"
 FLOOR DRAIN DISCHARGING INTO THE RISER. WHAT IS
 DISCHARGING INTO THIS FLOOR DRAIN?
 50) SHT.P407 (2-134) IDENTIFY THE PIECE OF EQUIPMENT
 SHOWN ON THE PLAN. WPB AMEND. TO 2010 FBC. 107.2.1.
 51) SHT.P407 (2-134) SHOWS A 4" CONDENSATE DRAIN INTO
 THE SUMP AND A 4" DISCHARGE AND DETAIL #2 SHOWS A 1 "
 DISCHARGE. CLARIFY.
 52) SHT. P501 (2-135)? SUBMIT MANUFACTURER'S
 SPECIFICATIONS/INSTALL MANUAL FOR THE CONDENSATE WATER
 PUMP PACKAGE STSP-3. WPB AMEND. TO 2010 FBC SEC.
 107.2.1. SHOW THE DIMENSIONS OF THE SUMP.
 53) 53) SHT.P002 (261) SUBMIT MANUF. SPECS FOR THE OIL
 SMART SUMP PUMP. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 54) SHT. P003 (262) - CLEARLY SHOW THE ENTIRE LIMITS OF
 PHASE ONE AND PHASE TWO ON THE PLAN.
 55) SHT. P003 (262) PLBG. KEYNOTE #3 STATES THE COOLING
 BASIN OVERFLOW TO SANITARY. COOLING TOWER WATER CANNOT
 DRAIN TO THE SANITARY PER CITY ORDINANCE 90-126 (5).
 56) SHT. P501 (299) THE GREASE TRAP SHALL COMPLY WITH
 2010 FPC SEC.1003.5.1 & 1003.5.2, 1003.5.3. SUBMIT
 SIZING CALCULATIONS FOR HE INTERCEPTOR IN ACCORDANCE
 WITH 2010 FPC. TABLE 1003.5.1.
 57) SHT. P501 (299) & SHT. P003 (262) SIZE THE INLET
 AND OUTLET LINE FROM THE INTERCEPTORS.
 58) SHT.P003 (262) SIZE THE 3 STORM LINES COMING FROM
 THE NEW RESIDENT BUILDING AND SIZE THE CDU LINE.
 59) SHT. P003 - THE CONDENSATE DISCHARGE LINE IS SHOWN
 AS 2" ON THE CIVIL PLANS AND AS 4". CLARIFY.
 60) THE COOLING TOWER SHALL COMPLY WITH NFPA 214.
 SUBMIT DETAILS.
 61) SUBMIT MANUF. SPECS FOR THE PIPE WRAP FOR THE
 UNDERGROUND CONDENSATE PIPE. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 62) INDICATE ON THE PLAN IF THE GENERATOR IS NEW OR
 EXISTING. IF NEW, SUBMIT SPECIFICATIONS FOR IT.
 63) SHT. 101C (268) LABEL THE RAINWATER LEADER LOCATED
 IN THE CARTS ROOM #155, THE DINING ROOM AND HOSTESS
 ROOM #157.
 64) SHT.P102A (269) LABEL THE CD RISER LOCATED IN ROOM
 #237 THAT GOES TO AREA MARKED ?OPEN TO BELOW.
 65 ) SHT. 205C (102B) LABEL THE CD RISER FROM THE FCU
 IN ROOM NEXT TO TRASH ROOM .
 66) SHT. P103A (271) IDENTIFY THE CD RISER IN COMMUNITY
 ROOM # 837. LABEL ALL THE CONDENSATE RISERS ON SHTS.
 P102A, P103A, 103B, ETC.
 67) IDENTIFY ALL THE SHEETS FOR CONTINUATION OF THE
 MATCH LINES. THERE ARE NO REFERENCE SHEET NUMBERS AT
 THE MATCH LINES .
 68) SUBMIT A LEGEND FOR IDENTIFICATION OF THE WATER
 MAINS AND WHAT THEY ARE. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 69) ROOF DRAINAGE INDICATE ON THE STORM RISER PLANS
 THAT THE SIZING OF THE STORM DRAINAGE INCLUDES 1/2 OF
 THE SQUARE FOOTAGE OF ANY VERTICAL (PARAPET) WALLS PER
 FBC-PLUMBING, SEC.1106.4.
 70) SHT. P401A (285) ? THE ISOMETRIC SHOWS A FLAT DRY
 VENT BY SAN. RISER #1. THE SHOWER DOWNSTREAM OF STACK
 S/8 MUST BE LOCATED DOWNSTREAM A MINIMUM OF 10 PIPE
 DIAMETERS OF THE UPPER DRAINAGE STACK. IDENTIFY THE
 PLUMBING FIXTURE DOWNSTREAM OF STACK S/15. SEE ALSO
 FIXTURE S-1 DOWNSTREAM OF STACK S/16. SEE FPC
 SEC.704.3.
 71) 71) SHT. P402 (287)SAN RISERS #1, #3, & # 6 DO NOT
 COMPLY WITH FPC SEC. 909 FOR ALLOWED FIXTURES ON A
 HORIZONTAL WET VENT. THE WASHING MACHINES AND S-2 ARE
 NOT FIXTURES IN A BATHROOM GROUP AND ARE NOT PERMITTED
 ON A WET VENT. ALSO, THE FIXTURE BT-1 IS NOT VENTED ON
 SAN. RISER #4.
 72) SHT.P412 (297) SHOWS 3 " GAS DROPS TO THE WATER
 HEATERS AND SHT.502 (300) SHOWS 1 1/4" AND A 2" GAS
 LINE TO THE WATER HEATERS. CLARIFY.
 73) SHT. P412 SHOWS THE LONGEST RUN AS 400 FT. BUT MY
 CALCULATIONS COME TO 498 FT. CLARIFY.
 74) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS
 EQUIPMENT. ALL EQUIPMENT/APPLIANCES SHALL BE LISTED AND
 LABELED PER FBC-FUEL GAS SEC. 301.3.
 75) SHT. P412 NATURAL GAS RISER DIAGRAM - IF THE
 LONGEST RUN IS CONFIRMED AT 498 FT. THEN THE PIPE SIZES
 OF THE FOLLOWING SECTIONS NEED TO BE REVISED AS
 FOLLOWS: PIPE SECTION I-J SHALL BE A MIN. OF 1 ??.
 SECTION H-I SHALL BE 3?. SECTION D-E SHALL BE 5?
 MINIMUM. A MAXIMUM OF 2110 CFH IS ALLOWED ON A 4" LINE
 AT ? PSI PER THE REFERENCED TABLE FROM NFPA.
 76) SHT. P412 - INSTALLATION OF UNDERGROUND PIPING
 SHALL COMPLY WITH NFPA SEC.7.1.6.2 OR 2010 FBC -FUEL
 GAS, SEC.404.6.2. INDICATE TYPE OF PIPING TO BE USED.
 77) SUBMIT CALCULATIONS FOR COMBUSTION AIR IN
 ACCORDANCE WITH 2010 FBC - FUEL GAS SEC.304. SUBMIT
 DETAILS ON LOCATION AND TYPES OF VENTS, HEIGHT ABOVE
 ROOF, ETC.
 78)SHT. P501 - SIZE ALL SECTIONS OF THE PIPING FOR THE
 DOMESTIC BOOSTER WATER PUMP, WATER SOFTENER AND
 PRESSURE REDUCING STATION. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
  
 ***PLEASE CONTACT CAROLINE PUELL, PERMIT LIBRARIAN,
 PRIOR TO UPLOADING REVISED PLANS TO ENSURE PROPER
 NAMING CONVENTIONS ORDER.***
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2015-08-17 Cont ID  
Sent By tklarge Date 2015-01-07 Time 13:53 Rev Time 0.00
Received By tklarge Date 2015-01-07 Time 13:53 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2015-08-10 Cont ID  
Sent By shill Date 2015-08-10 Time 07:21 Rev Time 0.00
Received By shill Date 2015-08-10 Time 07:21 Sent To  
Notes
2015-08-10 07:22:53****PROVISO****
 ISSUED AT CONTRACTOR?S RISK
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 2010 FLORIDA BUILDING CODE WITH 2012 FBC SUPPLEMENTS
 ADOPTED APRIL 25/2013.
  
 NO ROOF COVERING INFORMATION HAS BEEN SUBMITTED AT THIS
 TIME
  
 ROOF PRODUCT APPROVALS, REVIEWED BY DESIGNER OF RECORD,
 ARE TO BE SUBMITTED WITH ROOF PERMIT APPLICATION PRIOR
 TO INSTALLATION
  
 THE ROOF COVERING ASSEMBLY AT THE CONNECTING CORRIDOR
 IS TO HAVE A CLASS B RATING (PER SHEET G101, PER FBC
 706.6 EXCEPTION 3)
  
 ALL ROOFS TO MEET THE FOLLOWING DESIGN PRESSURES PER
 SHEET S8.5:
  
 ZONE 1 +52.0 / -76.4
 ZONE 2 +76.4 / -119.9
 ZONE 3 +52.0 / -119.9
  
  
  
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2015-05-06 Cont ID  
Sent By shill Date 2015-05-06 Time 15:14 Rev Time 0.00
Received By shill Date 2015-05-06 Time 15:14 Sent To  
Notes
2015-05-06 15:15:32****PROVISO****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 1. NO ROOF PRODUCT APPROVALS SUBMITTED.
  
 PRIOR TO INSTALLATION, ROOF PRODUCT APPROVALS ARE TO BE
 SUBMITTED FOR REVIEW. DESIGNER OF RECORD IS TO REVIEW
 THE PRODUCT APPROVALS AND ENGINEERING (IF APPLICABLE)
 PRIOR TO SUBMITTAL.
  
 NOTES:
  
 DESIGN PRESSURES ON SHEET S8.5
 FLAT METAL DECK
 WOOD DECK (PITCHED)
  
  
  
  
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2016-03-22 Cont ID  
Sent By shill Date 2016-01-08 Time 14:29 Rev Time 0.00
Received By shill Date 2016-01-07 Time 14:23 Sent To  
Notes
2016-01-22 07:14:42THE PLANS DO NOT MATCH THE ISSUED PERMIT. FOR INSTANCE,
 SEE THE FOLLOWING SHEETS:
  
 PHASE II, VOLUME II:
  
 FP 301, FP302 PROJECT DOX VERSION IS DATED 11/6/14,
 PAPER PLAN IS DATED 2/13/15.
  
 THE SIGNATURE DOCUMENTS ARE TO BE CONSISTENT WITH THE
 PERMIT ISSUED DOCUMENTS.
  
  
  
2016-01-07 14:24:06GIVEN TO SHILL TO VERIFY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-09-23 Cont ID  
Sent By shill Date 2015-09-23 Time 13:07 Rev Time 0.00
Received By shill Date 2015-09-23 Time 13:07 Sent To  
Notes
2015-09-23 17:00:40THE PAPER PLAN SET WAS SUBMITTED ONLY FOR THE PURPOSE
 OF PROVIDING SIGNATURE AND SEALS FOR ALL DESIGN
 PROFESSIONALS.
  
 ANOTHER CONSOLIDATED SIGNATURE AND SEAL FOR THE PERMIT
 PLANS WILL BE REQUIRED. CONTRACTOR WILL BE ADVISED OF
 THE PROCESS VIA EMAIL.
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2015-08-05 Cont ID  
Sent By shill Date 2015-08-05 Time 08:05 Rev Time 0.00
Received By shill Date 2015-08-05 Time 08:05 Sent To  
Notes
2015-08-05 08:06:08CONTRACTOR WAS GIVEN ONE SET ON 8/5/15
 ONE SET ROUTED TO RECORDS (SCANNING)
 ONE SET ROUTED TO KEN CONRAD'S DESK
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2015-07-27 Cont ID  
Sent By shill Date 2015-07-27 Time 09:54 Rev Time 0.00
Received By shill Date 2015-07-27 Time 09:54 Sent To  
Notes
2015-07-27 09:54:27****CORRECTIONS****
 14120908, 14120909
 THRESHOLD INSPECTION PLAN, SPECIAL INSPECTOR AGREEMENT
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THRESHOLD INSPECTION PLAN, ITEM 6.02 B AND C REFER
 TO OPENINGS IN THE FIRST 60 FEET. FBC 1609.1.2(2),
 PLEASE REVISE TO COMPLY WITH THIS SECTION (ALL OPENINGS
 REQUIRED TO HAVE IMPACT PROTECTION).
  
 2. THE SPECIAL INSPECTOR AGREEMENT IS LACKING THE
 SIGNATURE OF THE DESIGNER OF RECORD, PAGE 5 OF 6 (THIS
 SHOULD BE SIGNED AND SEALED).
  
 PLEASE REMOVE THE OLD SHEETS AND REPLACE WITH THE NEW
 SHEETS.
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2015-05-18 Cont ID  
Sent By shill Date 2015-05-18 Time 13:20 Rev Time 0.00
Received By shill Date 2015-05-18 Time 13:20 Sent To  
Notes
2015-05-18 13:21:13SPECIAL INSPECTOR AGREEMENT AND RESUMES FOR CONTRACTOR
 AND INSPECTORS REQUIRED
 SEE BUILDING COMMENTS
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2015-09-04 Cont ID  
Sent By eschneid Date 2015-09-04 Time 16:18 Rev Time 5.00
Received By eschneid Date 2015-09-04 Time 16:18 Sent To  
Notes
2015-09-04 16:33:05PASSED W/PROVISOS
  
 1) ALL ELEVATIONS, SECTIONS, ROOF PLANS AND DETAIL
 SHEETS SHALL BE REVISED TO ACCURATELY REFLECT THE LOWER
 BUILDING HEIGHT TO MEET THE REQUIREMENTS OF RESOLUTION
 NO. 49-13. THE BACK-UP MATERIAL SHOWS THE SLOPED TOWER
 ROOF MEETING THIS REQUIREMENT, BUT THERE SEEM TO BE
 SOME OF THE AREAS SURROUNDED BY PARAPETS THAT MAY
 EXCEED THE HEIGHT.
  
 2) THE RETAINING WALL UNDER PERMIT 15090033. ALL PLANS
 SHALL BE REVISED TO MATCH THE APPROVED RETAINING WALL.
 CURRENTLY THERE ARE A NUMBER OF DIFFERENT
 CONFIGURATIONS SHOWN.
  
 3) THE SITE PLANS SHOW A DIFFERENT ORIENTATION FOR THE
 BICYCLE RACK AND AREA BETWEEN THE BUILDINGS THAN THE
 ZONING APPROVED PLANS. THE CHANGES SHALL BE REFLECTED
 ON THE REVISED SITE PLANS AND ON A MINOR PD AMENDMENT.
 PLEASE NOTE THAT MORSELIFE CURRENTLY HAS A MINOR PD
 AMENDMENT UNDER REVIEW THAT COULD BE MODIFIED TO
 INCLUDE THE CHANGES.
  
 4) SHEET G101 SHOWS NOTE REFERENCING A 17 FOOT CLEAR
 FIRE TRUCK ACCESS ROAD (SOUTH OF POOL WALL). THE
 APPROVED SITE PLAN SHOWS THIS AS A 20 FOOT WIDE
 DRIVEWAY. PLEASE CORRECT SHEET G101. THIS CHANGE IS
 ALSO SHOWN ON SHEET L101. THIS SHALL BE INCLUDED ON THE
 PLAN REVISIONS.
  
 5) SHEET C101 SHOWS THE 20 FOOT FIRE DEPARTMENT ACCESS
 DRIVE ON THE EAST SIDE OF THE BUILDINGS AS NOT INCLUDED
 WITH THE CONSTRUCTION THE INITIAL TOWER. THIS WAS A
 REQUIREMENT OF THE FIRE DEPARTMENT TO SERVICE THE
 BUILDING AND THUS SHALL BE PROVIDED FOR IN PHASE 1.
  
 6) SEPARATE PERMITS, WITH PLANS, ARE REQUIRED FOR THE
 FOLLOWING:
  
 A. LANDSCAPE - PLEASE NOTE THAT THE ROW OR PARKING TO
 THE NORTH OF THE 20 FOOT FIRE DEPARTMENT ACCESS AREA
 SHALL BE TERMINATED BY THE REQUIRED TREE IN PHASE 1.
 B. IRRIGATION
 C. TEMPORARY CONSTRUCTION ACCESS DRIVE - NOTE: A TREE
 ALTERATION PERMIT IS REQUIRED PRIOR TO THE APPROVAL OF
 THE TEMPORARY ACCESS DRIVE TREE REMOVAL.
 D. PARKING LOT PAVING AND STRIPING
 E. BICYCLE RACK
 F. COMPACTOR ENCLOSURE
 G. POOL, SPA AND FOUNTAIN
 H. FENCES AND GATES
 I. GENERATOR BUILDING
 J. SITE LIGHTING
 K. COOLING TOWER AREA
  
 7) NOTE: THE FUTURE TRACT LINE DOES NOT MATCH UP WITH
 THE DOORWAY AS SHOWN ON SHEET L101. THE FUTURE TRACT
 LINE SHALL NOT CUT THROUGH THE CORRIDOR AT AN
 UNPROTECTED POINT.
  
 8) PLEASE REMEMBER THE DEADLINE FOR THE PLAT APPROVAL
 APPROVED BY ROBERT BROWN, BUILDING OFFICIAL.
  
 9) PLEASE NOTE THAT THE TRADITIONS PHASE II SHALL HAVE
 MET THE COMMENCEMENT OF DEVELOPMENT DATE OF NOVEMBER 3,
 2015, IN ACCORDANCE WITH ITS FINAL EXTENSION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 3 Status F Date 2015-08-07 Cont ID  
Sent By eschneid Date 2015-08-07 Time 11:00 Rev Time 8.00
Received By eschneid Date 2015-08-07 Time 11:00 Sent To  
Notes
2015-08-07 11:02:12FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) THE BUILDING APPEARS TO BE TALLER THAN THE 110 FEET
 PERMITTED BY THE TRADITIONS PHASE II APPROVALS
 (ORIGINALLY ORD. NO. 4110-08, CURRENT RES. NO. 49-13).
 THE WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS STATE, "...THE HEIGHT SHALL BE MEASURED AS
 THE VERTICAL DISTANCE FROM THE AVERAGE ELEVATION OF THE
 FINISHED GRADE OF THE BUILDING TO THE HIGHEST POINT OF
 THE TOP OF THE STRUCTURE OF A FLAT ROOF...". SECTION
 94-306 ALLOWS CERTAIN HEIGHT EXCEPTIONS AS FOLLOWS:
 "HEATING, VENTILATION, AND AIR CONDITIONING EQUIPMENT;
 CHURCH STEEPLES, BELL TOWERS, FLAG POLES, CHIMNEYS,
 PARAPETS, STAIR ENCLOSURES, TANKS, DECORATIVE FEATURES,
 ELEVATOR HOISTWAYS OR EQUIPMENT, TELEVISION OR RADIO
 ANTENNAS, AND RELATED MECHANICAL OR FUNCTIONAL FEATURES
 MAY EXCEED DISTRICT HEIGHT REQUIREMENTS BY TEN
 PERCENT." THE ELEVATION DRAWINGS SHALL BE AMENDED TO
 INCLUDE THE FOLLOWING DIMENSION LINES:
  
 A. THE BASE MEASURE SHALL BE FROM THE AVERAGE ELEVATION
 OF THE FINISHED GRADE OF THE BUILDING. IT APPEARS THAT
 THE ELEVATIONS PROVIDED ARE USING FINISHED FLOOR OR TOP
 OF THE SLAB. THE STRUCTURAL DRAWINGS INDICATE THAT THE
 FOUR (4) INCH SLAB IS ON GRADE, NOT AT GRADE, WHICH
 WOULD MAKE IT FOUR (4) INCHES HIGHER THAN THE AVERAGE
 ELEVATION OF THE FINISHED GRADE (THIS IS ALSO INDICATED
 ON THE BUILDING SECTION DRAWINGS). PLEASE CLARIFY.
 B. EXTEND THE DIMENSION LINE TO THE HIGHEST POINT OF
 THE BUILDING. STAFF HAS SCALED THE DRAWING AND IT
 APPEARS THAT THE HIGHEST POINTS ON THE BUILDING ARE 123
 FEET. SECTION 94-306 ALLOWS THE HEIGHT EXCEPTION FOR
 THIS BUILDING TO EXTEND TO 121 FEET (HEIGHT WAIVER TO
 110 FEET X 10% = 11 FEET ADDITIONAL HEIGHT EXCEPTION).
  
 2) PLEASE CLARIFY IF THE RETAINING WALL IS INCLUDED AS
 PART OF THIS PERMIT. THE SITE AND CIVIL PLANS SHOW THE
 MAJORITY OF THE RETAINING WALL AREA AS PART OF THIS
 PERMIT. THE FOUNDATION PLAN SHOWS MOST OF THE WALL NOT
 INCLUDED. PRESUMABLY THE BALANCE OF THE RETAINING WALL
 WOULD BE INCLUDED WITH THE DINING ROOM PERMIT. WHY
 SPLIT UP THE RETAINING WALL AND NOT BUILD IT UNDER ITS
 OWN PERMIT?
  
 3) THE NEW RETAINING WALL IS SHOWN IN DIFFERENT
 LOCATIONS ON THE PLANS LISTED BELOW. PLEASE EXPLAIN WHY
 DIFFERING WALL LOCATIONS ARE SHOWN.
  
 COTLEUR & HEARING PLANS
 MICHAEL B. SCHORAH & ASSOCIATES, INC. PLANS
 ONM&J PARTIAL FOUNDATION PLANS
 PERKINS EASTMAN ARCHITECTURAL PLANS
  
 4) THE LANDSCAPE PLANS CALL FOR LITTORAL PLANTING TO
 THE WEST OF THE OVERLOOK PORTION OF THE RETAINING WALL.
 PLEASE EXPLAIN HOW THIS WILL OCCUR GIVEN THE DEPTH AND
 SLOPE THAT ARE BEING PROPOSED.
  
 5) THE SITE PLANS SHOW A DIFFERENT ORIENTATION FOR THE
 BICYCLE RACK AND AREA BETWEEN THE BUILDINGS THAN THE
 APPROVED PLANS. THE CHANGES SHALL BE REFLECTED ON A
 MINOR PD AMENDMENT. PLEASE NOTE THAT MORSELIFE
 CURRENTLY HAS ONE UNDER REVIEW THAT COULD BE MODIFIED
 TO INCLUDE THE CHANGES.
  
 6) SHEET G101 SHOWS NOTE REFERENCING A 17 FOOT CLEAR
 FIRE TRUCK ACCESS ROAD (SOUTH OF POOL WALL). THE
 APPROVED SITE PLAN SHOWS THIS AS A 20 FOOT WIDE
 DRIVEWAY. PLEASE CORRECT SHEET G101. THIS CHANGE IS
 ALSO SHOWN ON SHEET L101
  
 7) SHEET C101 SHOWS THE 20 FOOT FIRE DEPARTMENT ACCESS
 DRIVE ON THE EAST SIDE OF THE BUILDINGS AS NOT INCLUDED
 WITH THE CONSTRUCTION THE INITIAL TOWER. THIS WAS A
 REQUIREMENT OF THE FIRE DEPARTMENT TO SERVICE THE
 BUILDING AND THUS SHALL BE PROVIDED FOR PHASE 1.
  
 8) THE PARKING LOT, CONSTRUCTION ACCESS ROADWAY AND
 DRIVE, IRRIGATION, LANDSCAPING, SITE LIGHTING,
 GENERATOR BUILDING, BICYCLE RACKS, COMPACTOR ENCLOSURE,
 COOLING TOWER AREA, AND FENCES/GATES REQUIRE SEPARATE
 PERMIT SUBMITTALS, WITH PLANS. PLEASE DO NOT RESUBMIT
 THESE SHEETS. PLEASE NOTE THAT THE ROW OR PARKING TO
 THE NORTH OF THE 20 FOOT FIRE DEPARTMENT ACCESS AREA
 SHALL BE TERMINATED BY THE REQUIRED TREE IN PHASE 1.
  
 9) TREE ALTERATION PERMIT IS REQUIRED PRIOR TO THE
 APPROVAL OF THE TEMPORARY ACCESS DRIVE TREE REMOVAL.
  
 10) NOTE: THE FUTURE TRACT LINE DOES NOT MATCH UP WITH
 THE DOORWAY AS SHOWN ON SHEET L101. THE FUTURE TRACT
 LINE SHALL NOT CUT THROUGH THE CORRIDOR AT AN
 UNPROTECTED POINT.
  
 11) PLEASE REMEMBER THE DEADLINE FOR THE PLAT APPROVAL
 APPROVED BY ROBERT BROWN, BUILDING OFFICIAL.
  
 12) PLEASE NOTE THAT THE TRADITIONS PHASE II SHALL HAVE
 MET THE COMMENCEMENT OF DEVELOPMENT DATE OF NOVEMBER 3,
 2015, IN ACCORDANCE WITH ITS FINAL EXTENSION.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2015-04-02 Cont ID  
Sent By eschneid Date 2015-04-02 Time 16:12 Rev Time 1.00
Received By eschneid Date 2015-04-02 Time 16:12 Sent To  
Notes
2015-04-02 16:12:40FAILED
  
 1) THE PROPOSED BUILDING STRADDLES THE CURRENT LOT LINE
 BETWEEN TRACTS B AND C. ORDINANCE NO. 4110-08, WHICH
 ADOPTED THE TRADITIONS PHASE 2 DEVELOPMENT, INCLUDED A
 CONDITION THAT PRIOR TO THE SUBMITTAL OF THE BUILDING
 PERMIT FOR VERTICAL CONSTRUCTION, A UNITY OF TITLE FOR
 TRACTS B AND C HAS TO BE RECORDED.
  
 2) MORSELIFE HAS SUBMITTED AN APPLICATION TO CHANGE THE
 TRACT BOUNDARIES TO MOVE THE LOT LINES BETWEEN THE
 BUILDINGS; HOWEVER, THIS HAS NOT YET BEEN APPROVED.
 PLEASE BE AWARE THAT THE NEW TRACT LINE LOCATION
 BISECTS THE CORRIDOR CONNECTING THE TWO BUILDINGS,
 WHICH MAY REQUIRE A FIRE RATED DOOR ON THE TRACT LINE.
  
 3) THE MINOR PLANNED DEVELOPMENT AMENDMENT FOR THE
 REVISED TRADITIONS PHASE 2 HAS NOT RECEIVED FINAL
 APPROVAL FROM THE PLANNING DIVISION.
  
 4) ZONING CANNOT REVIEW OR APPROVE UNTIL THE ITEMS IN
 1-3 ABOVE ARE SATISFIED.
  
 3) LANDSCAPE, PARKING, BICYCLE RACKS, ETC. REQUIRE
 SEPARATE PERMIT WITH PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
2015-03-10 13:54:173/10/15

Review Stop Z ZONING
Rev No 1 Status N Date 2015-01-28 Cont ID  
Sent By eschneid Date 2015-01-28 Time 10:31 Rev Time 0.00
Received By skennedy Date 2015-01-28 Time 10:31 Sent To  
Notes
2015-01-28 10:31:47REVIEW CYCLE ENDED AS APPLICANT WILL SUBMIT REDESIGN.