Plan Review Details - Permit 14120908
Plan Review Stops For Permit 14120908
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-07-28 Cont ID  
Sent By shill Date 2015-07-28 Time 16:29 Rev Time 0.00
Received By shill Date 2015-07-28 Time 16:29 Sent To  
Notes
2015-07-28 16:30:57PROVISOS (REVISED 8/19/15)
  
 ISSUED AT CONTRACTOR'S RISK
  
 IF OTHER TRADES FAIL THIS PLAN REVIEW (2ND PLAN REVIEW)
 AND THIS PERMIT IS NOT ISSUED IN THIS REVIEW CYCLE,
 ADDRESS ALL ITEMS WITH THE EXCEPTION OF "INFORMATION
 ONLY" ITEMS.
  
 1. CHANGES TO THE PROPERTY LINE (REPLAT) REQUIRE THAT
 COMPLIANCE WITH FBC TABLE 705.8 (MAXIMUM AREA OF
 EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION
 DISTANCE) AND FBC TABLE 602 (FIRE RESISTANCE RATING
 REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE
 SEPARATION DISTANCE) BE SHOWN. A REVISION WILL BE
 REQUIRED PRIOR TO CERTIFICATE OF COMPLETION.
  
 DISTANCE TO PROPERTY LINE AND OPENINGS ALLOWED HAS NOT
 BEEN REVIEWED. HOWEVER, PLEASE NOTE THE LARGE WINDOWS,
 ROOM 104 DINING ROOM. IF DISTANCE TO PROPERTY LINE IS
 10 FEET TO LESS THAN 25 FEET, UNPROTECTED OPENINGS ARE
 LIMITED TO 45%.
  
 BASED ON INFORMATION PROVIDED: BEARING WALLS ARE
 REQUIRED TO BE 3 HOURS. STRUCTURAL FRAME IS REQUIRED TO
 BE 2 HOURS.
  
 2. THE ART IN PUBLIC PLACES WAS SENT VIA EMAIL, CITY OF
 WEST PALM BEACH CODE OF ORDINANCES 78-123, 78-126.
  
 THIS PERMIT WILL BE ISSUED WITH THE PROVISO THAT,
 WITHIN 90 DAYS OF ISSUANCE, THE APPROVAL WILL BE
 PROVIDED. PLEASE SEND A COPY OF THE APPROVAL WHEN
 AVAILABLE VIA EMAIL TO [email protected] IN ORDER TO
 DOCUMENT THE PERMIT FILE.
  
 3. SHEET A101 SHOWS A PROPOSED FUTURE 2 HOUR FIRE DOOR.
 SEE FBC TABLE 715.4, A 3 HOUR FIRE DOOR IS REQUIRED FOR
 A 3 HOUR FIRE WALL.
  
 4. ADVISORY ONLY, PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED FOR REVIEW PRIOR
 TO INSTALLATION IF NOT SUBMITTED AT THIS TIME, FBC 107,
 FBC 1609 (SUBMITTAL, NO FEE).
  
 5. ADVISORY ONLY; PARKING LOT STRIPING, AWNINGS, SIGNS
 AND OTHER INDEPENDT STRUCTURE ELEMENTS REQUIRE SEPARATE
 PERMITS WHICH WOULD INCLUDE FEES, BUILDING PERMIT
 APPLICATIONS, PLANS AND REVIEWS.
  
 6. ADVISORY ONLY; SPEC SHEETS IN APPENDIX WERE NOT
 REVIEWED.
  
 7. PRIOR TO INSTALLATION, SUBMITTALS FOR THE UL
 ASSEMBLIES WILL BE REQUIRED. THE SUBMITTAL SHOULD
 INCLUDE THE UL ASSEMBLY WITH SPECIFIC OPTIONS ELECTED
 TO BE INDICATED. THE SUBMITTAL IS REQUIRED TO BE
 REVIEWED BY DOR. THE SUBMITTAL IS REQUIRED TO BE
 APPROVED THROUGH PLAN REVIEW PRIOR TO COMMENCEMENT.
  
 REVISE SHEET G001, REQUIRED FIRE RESISTIVE RATINGS.
 DISTANCE TO PROPERTY LINE IS FOR GREATER THAN 30FT
 SEPARATION. AS THERE IS A PROPERTY LINE BETWEEN THE TWO
 BUILDINGS, THIS IS NOT ACCURATE. DUE TO THE EXCEPTION
 FOR ONE STORY (1 HOUR REDUCTION FBC TABLE 601 FOOTNOTE
 A), DISTANCE TO PROPERTY LINE (FBC TABLE 602) APPEARS
 TO BE MORE RESTRICTIVE (2 HOUR REEQUIRED FROM 5 FEET TO
 UNDER 20 FEET).
  
 8. SHEET A301, SPECIFY UL ASSEMBLY AND RATING REQUIRED
 FOR THE MECHANICAL ROOM FLOOR, BEARING WALLS,
 STRUCTURAL FRAME, FBC TABLE 601. THE ROOF WAS SPECIFIED
 BUT NOT THE OTHER STRUCTURAL ELEMENTS.
  
 9. A601, PROVIDE A LEGEND FOR THE HARDWARE SCHEDULE. A
 CLOSER IS REQUIRED FOR DOORS 111 AND 112, FBC
 ACCESSIBILITY 604.8.2.2. ALL DOORS (AND GATES, IF
 APPLICABLE) SERVING ASSEMBLY OCCUPANCY TO HAVE FIRE
 EXIT HARDWARE, FBC 1008.1.10. SPEC SHEETS WERE
 SUBMITTED BUT CONTAINED INFORMATION NOT CODE RELATED
 (FINISHES, HINGES, KICK PLATES, ETC.). SPEC BOOKS
 CANNOT BE USED IN LIEU OF PLANS TO SHOW CODE COMPLIANCE
 DUE TO THE LARGE AMOUNT OF INFORMATION NOT RELEVANT TO
 CODE COMPLIANCE, FBC 107.
  
 10. FBC 713, PROVIDE PENETRATION DETAILS FOR WALLS AND
 FLOORS.
  
 11. FBC 2010 ACCESSIBILITY 703, SIGNS TO COMPLY WITH
 THIS SECTION.
  
 12. TESTED ASSEMBLIES OR CALCULATED FIRE RESISTANCE
 DETAILS REQUIRED FOR ALL ELEMENTS REQUIRED TO BE RATED
 PER FBC TABLE 601. SUBMIT DETAILS PRIOR TO
 INSTALLATION.
  
 13. REVISION REQUIRED FOR G101. PER ARCHITECT, THE
 OCCUPANCY SEPARATION WILL BE ELIMINATED. THIS WALL IS A
 CORRIDOR WALL, 1 HOUR RATING REQUIRED, 20 MINUTE
 OPENING PROTECTION REQUIRED.
  
 14. RE-PLAT TO BE FILED WITHIN 45 DAYS OF PERMIT
 ISSUANCE (AGREEMENT BETWEEN OWNER AND DEVELOPMENT
 SERVICES).
  
 15. THRESHOLD PLAN STATEMENT REQUIRED BY FS 553.79 TO
 BE CORRECTED ON STRUCTURAL DRAWINGS. EVIDENCE THAT THIS
 HAS BEEN CORRECTED IS TO BE SENT TO ME VIA EMAIL PRIOR
 TO PERMIT ISSUANCE. PLANS TO BE SUBMITTED AS A REVISION
 PRIOR TO COMMENCEMENT IF PERMIT IS ISSUED THIS REVIEW
 CYCLE. IF PERMIT IS NOT ISSUED IN THIS REVIEW CYCLE,
 REVISED DRAWINGS TO BE RESUBMITTED.
 NOTE - CONFIRMATION SENT VIA EMAIL FROM STRUCTURAL
 ENGINEER 8/18/15
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-07-27 Cont ID  
Sent By S. Hill Date 2015-07-27 Time 15:09 Rev Time 0.00
Received By shill Date 2015-07-23 Time 10:22 Sent To  
Notes
2015-07-27 15:10:39****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 41. PROVIDE INFORMATION FOR THE MCKEON DOOR (SPEC
 SHEETS AND TEST REPORT), INSTALLATION INSTRUCTIONS.
 MODEL D200E PROPOSED. PLEASE SEE FBC 715.4.2 ALLOWS UL
 10B AS A TESTED STANDARD. SEE SPEC SHEETS PROVIDED;
 THIS DOOR APPEARS TO BE LIMITED TO 20 MINUTES , 45
 MINUTES REQUIRED.
  
 THIS INFORMATION MAY BE SENT VIA EMAIL.
  
 ** IMPACT FEE PAYMENT REQUIRED (SEE IMPACT FEE REVIEW)
 **SEE THRESHOLD REVIEW - AGREEMENT AND PLAN REQUIRED TO
 BE REVISED PRIOR TO PERMIT ISSUANCE
  
 PROVISO ITEMS:
  
 1. CHANGES TO THE PROPERTY LINE (REPLAT) REQUIRE THAT
 COMPLIANCE WITH FBC TABLE 705.8 (MAXIMUM AREA OF
 EXTERIOR WALL OPENINGS BASED ON FIRE SEPARATION
 DISTANCE) AND FBC TABLE 602 (FIRE RESISTANCE RATING
 REQUIREMENTS FOR EXTERIOR WALLS BASED ON FIRE
 SEPARATION DISTANCE) BE SHOWN. A REVISION WILL BE
 REQUIRED PRIOR TO CERTIFICATE OF COMPLETION.
  
 2. THE ART IN PUBLIC PLACES WAS SENT VIA EMAIL, CITY OF
 WEST PALM BEACH CODE OF ORDINANCES 78-123, 78-126.
  
 THIS PERMIT WILL BE ISSUED WITH THE PROVISO THAT,
 WITHIN 90 DAYS OF ISSUANCE, THE APPROVAL WILL BE
 PROVIDED. PLEASE SEND A COPY OF THE APPROVAL WHEN
 AVAILABLE VIA EMAIL TO [email protected] IN ORDER TO
 DOCUMENT THE PERMIT FILE.
  
 3. SHEET A101 SHOWS A PROPOSED FUTURE 2 HOUR FIRE DOOR.
 SEE FBC TABLE 715.4, A 3 HOUR FIRE DOOR IS REQUIRED FOR
 A 3 HOUR FIRE WALL.
  
 4. ADVISORY ONLY, PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED FOR REVIEW PRIOR
 TO INSTALLATION IF NOT SUBMITTED AT THIS TIME, FBC 107,
 FBC 1609 (SUBMITTAL, NO FEE).
  
 5. ADVISORY ONLY; PARKING LOT STRIPING, AWNINGS, SIGNS
 AND OTHER INDEPENDT STRUCTURE ELEMENTS REQUIRE SEPARATE
 PERMITS WHICH WOULD INCLUDE FEES, BUILDING PERMIT
 APPLICATIONS, PLANS AND REVIEWS.
  
 6. ADVISORY ONLY; SPEC SHEETS IN APPENDIX WERE NOT
 REVIEWED.
  
 7. PRIOR TO INSTALLATION, SUBMITTALS FOR THE UL
 ASSEMBLIES WILL BE REQUIRED. THE SUBMITTAL SHOULD
 INCLUDE THE UL ASSEMBLY WITH SPECIFIC OPTIONS ELECTED
 TO BE INDICATED. THE SUBMITTAL IS REQUIRED TO BE
 REVIEWED BY DOR. THE SUBMITTAL IS REQUIRED TO BE
 APPROVED THROUGH PLAN REVIEW PRIOR TO INSTALLATION.
  
 8. SHEET A301, SPECIFY UL ASSEMBLY AND RATING REQUIRED
 FOR THE MECHANICAL ROOM FLOOR, BEARING WALLS,
 STRUCTURAL FRAME, FBC TABLE 601. THE ROOF WAS SPECIFIED
 BUT NOT THE OTHER STRUCTURAL ELEMENTS.
  
 9. A601, PROVIDE A LEGEND FOR THE HARDWARE SCHEDULE. A
 CLOSER IS REQUIRED FOR DOORS 111 AND 112, FBC
 ACCESSIBILITY 604.8.2.2. ALL DOORS (AND GATES, IF
 APPLICABLE) SERVING ASSEMBLY OCCUPANCY TO HAVE FIRE
 EXIT HARDWARE, FBC 1008.1.10. SPEC SHEETS WERE
 SUBMITTED BUT CONTAINED INFORMATION NOT CODE RELATED
 (FINISHES, HINGES, KICK PLATES, ETC.). SPEC BOOKS
 CANNOT BE USED IN LIEU OF PLANS TO SHOW CODE COMPLIANCE
 DUE TO THE LARGE AMOUNT OF INFORMATION NOT RELEVANT TO
 CODE COMPLIANCE, FBC 107.
  
 10. FBC 713, PROVIDE PENETRATION DETAILS FOR WALLS AND
 FLOORS.
  
 11. FBC 2010 ACCESSIBILITY 703, SIGNS TO COMPLY WITH
 THIS SECTION.
  
 12. TESTED ASSEMBLIES OR CALCULATED FIRE RESISTANCE
 DETAILS REQUIRED FOR ALL ELEMENTS REQUIRED TO BE RATED
 PER FBC TABLE 601. SUBMIT DETAILS PRIOR TO
 INSTALLATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-04-21 Cont ID  
Sent By shill Date 2015-04-21 Time 09:49 Rev Time 0.00
Received By shill Date 2015-04-12 Time 11:16 Sent To  
Notes
2015-04-12 14:37:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENTS FROM FIRST BUILDING PLAN REVIEW BY JIM WITMER
 WHICH ARE STILL APPLICABLE:
  
 1) MISSING INFORMATION EVEN FOR A FOUNDATION PERMIT:
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION
  
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS:
 1.1) SITE PLAN SHOWING LOCATION OF THE NEW BUILDING AND
 THE RELATIONSHIP OF OTHER BUILDINGS, PROVIDE DISTANCES
 BETWEEN.
 1.2) SURVEY WITH FLOOD ZONE DESIGNATION
 1.3) SOILS REPORT WITH THE MINIMUM BEARING VALUE FOR
 THIS BUILDING (DUNKELBERGER REPORT DATED 12/31/14
 REFERENCE ON SHEET S4.1; PROVIDE ALL GEOTECHNICAL
 REPORTS APPLICABLE TO THIS PROJECT).
 1.4) ARCHITECTURAL SHEET SHOWING THE 1ST FLOOR OR
 BOTTOM FLOOR, WITH FINISH FLOOR ELEVATIONS.
 1.5) OK
 1.6) MINIMUM BUILDING TYPE/ NUMBER OF STORIES (INCLUDE
 NUMBER OF STORIES FOR EXISTING BUILDING)
  
 2. THRESHOLD FORMS WERE E-MAILED TO RYAN TEMPONE
 1/10/2015 01:05 PM BY JIM WITMER.
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) OK; SHEET S 3.4, THRESHOLD INSPECTION NOTES ARE
 INCLUDED IN THIS SUBMITTAL.
 KEN CONRAD, CHIEF BUILDING INSPECTOR HAS BEEN ADVISED
 THAT THE PLAN IS AVAILABLE FOR HIS REVIEW.
  
 2B) THRESHOLD INSPECTOR REQUIRED; SEE PREVIOUS LIST FOR
 SPECIFICS.
  
 2C) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND FIRE SAFETY STANDARDS AS
 DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND 633 FLORIDA STATUTE.
  
 2ND REVIEW, I WAS UNABLE TO LOCATE THIS STATEMENT. SEE
 OTHER COMMENTS; THIS STATEMENT IS TYPICALLY
 INCORPORATED INTO EVERY PAGE.
  
 2D) SPECIAL INSPECTOR RESUME REQUIRED; SEE PREVIOUS
 LIST FOR SPECIFICS.
  
 2E) CONTRACTOR RESUME REQUIRED; SEE PREVIOUS LIST FOR
 SPECIFICS.
  
 2F) INFORMATIONAL ONLY; NOTE THIS IS A DIGITAL PLAN,
 AFTER PERMIT ISSUANCE, THE PERMIT LIBRARIAN WILL E-MAIL
 YOU, THE APPROVED AND BATCH STAMPED PLANS SO YOU MAY
 PRINT YOUR PLANS, TWO SETS OF PLANS WILL NEED TO BE
 PRINTED IN COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE
 OTHER FOR THE MEP INSPECTORS.
  
 2G) INFORMATIONAL ONLY; PLEASE CALL THE CITY OF WEST
 PALM BEACH?S AUTOMATED TELEPHONE INSPECTIONS LINE (561)
 805-6700) FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF
 JOBSITE INSPECTIONS.
  
 3) PLEASE PROVIDE DOCUMENTATION HOW THE JOBSITE WILL
 COMPLY WITH :
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 110.7 IMPACT OF
 CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO
 ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS PERMITTED TO AFFECT SAID
 PROPERTY PURSUANT TO A CONSENT GRANTED BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS OR CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES, BUT IS NOT LIMITED TO, THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFFS, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL HISTORIC
 SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL
 NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS,
 POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON
 EXISTING PROPERTIES RESULTING IN A SIGNIFICANT DECREASE
 OF PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE
 DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 2ND REVIEW; A STATEMENT IT TYPICALLY INCORPORATED INTO
 THE PLAN.
  
 4. 2010 FBC B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 5) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 THIS MAY BE DONE AT ANY TIME DURING THE PLAN REVIEW
 PROCESS, BUT MUST BE DONE PRIOR TO PERMIT ISSUANCE.
  
 NEW COMMENTS (NEW SHEETS SUBMITTED; SCOPE EXPANDED FROM
 FOUNDATION ONLY TO ADDITION TO EXISTING BUILDING):
 6. FOR ALL THRESHOLD JOBS, FS 553.79(7)(D)?ALL PLANS
 FOR THE BUILDING WHICH ARE REQUIRED TO BE SIGNED AND
 SEALED BY THE ARCHITECT OR ENGINEER OF RECORD CONTAIN A
 STATEMENT THAT, TO THE BEST OF THE ARCHITECT?S OR
 ENGINEER?S KNOWLEDGE, THE PLANS AND SPECIFICATIONS
 COMPLY WITH THE APPLICABLE MINIMUM BUILDING CODES AND
 THE APPLICABLE FIRESAFETY STANDARDS AS DETERMINED BY
 THE LOCAL AUTHORITY IN ACCORDANCE WITH THIS CHAPTER AND
 CHAPTER 633.
  
 PLEASE INCORPORATE THIS STATEMENT INTO THE PLANS. IT IS
 TYPICAL FOR THIS STATEMENT TO BE ON EACH SHEET. IF
 DESIGNER OBJECTS TO INCLUDING THIS STATEMENT ON EACH
 SHEET AND WOULD LIKE THE STATEMENT ON ONE SHEET ONLY,
 PLEASE ADVISE AND THIS OPTION WILL BE INVESTIGATED WITH
 THE APPROPRIATE BOARD.
  
 7. THIS DINING ROOM ADDITION TO AN EXISTING BUILDING IS
 TO BE CONNECTED TO A NEW BUILDING. SEE PREVIOUS LIST
 AND REFERENCE TO FBC 3104.5. IT IS NOT CLEAR WHETHER
 THE NEW BUILDING WILL BE CONSIDERED AN ADDITION TO THE
 EXISTING BUILDING, ON THE SAME PARCEL, CONNECTED BY A
 WALKWAY, OR IF WILL BE TREATED AS A NEW BUILDING,
 SEPARATE PARCEL, OR NEW BUILDING, SAME PARCEL (WITH
 UNITY OF TITLE, SEE OTHER COMMENTS).
  
 8. IT APPEARS THAT ALL PARTIES (ARCHITECT, ENGINEER,
 CONTRACTOR, OWNER) ARE IN AGREEMENT THAT THIS PROJECT
 WILL BE TREATED AS A THRESHOLD JOB. IF ANY OF THE
 PARTIES DISAGREE WITH THIS CLASSIFICATION, PLEASE
 CONTACT ME.
  
 CHIEF BUILDING INSPECTOR AGREES THAT, IF ALL PARTIES
 FOR THE TWO PROJECTS (DINING ROOM EXPANSION AND PHASE
 I, 14120908 AND 14120909) ARE THE SAME, ONE SET OF
 THRESHOLD DOCUMENTS (RESUMES, AGREEMENTS) IS
 ACCEPTABLE. IF THIS IS NOT ACCEPTABLE TO ANY OF THE
 PARTIES, PLEASE CONTACT ME TO DISCUSS.
  
 9. THE BUSINESS LICENSE NUMBER, NAME AND ADDRESS SHOWN
 ON THE PLAN (PERKINS EASTMAN, FS95000000559,
 PITTSBURGH, PA) ARE NOT CONSISTENT WITH DBPR RECORDS
 (PERKINS EASTMAN ARCHITECTS, D.P.C., INC, AA26000763,
 NEW YORK, NY). SINCE THE ADDRESS, NAME, AND LICENSE
 NUMBER ARE DIFFERENT FROM DBPR RECORDS, IT IS NOT
 POSSIBLE TO DETERMINE THE ARCHITECT (COMPANY) TAKING
 RESPONSIBILITY FOR THE DESIGN.
 SEE FS 481.219, CERTIFICATE OF AUTHORIZATION REQUIRED
 AND THE NUMBER IS TO BE ON ALL FINAL CONSTRUCTION
 DOCUMENTS.
  
 HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/PRO/ARCH/STATUTES.
 HTML
  
 10. PAPA RECORDS SHOW A PROPERTY LINE WHICH IS NOT
 SHOWN ON THE PLANS SUBMITTED. WILL THE TWO PROPERTIES
 REMAIN SEPARATE PARCELS, HAVE THEY ALREADY BEEN
 COMBINED WITH A UNITY OF TITLE, OR WILL THEY BE
 COMBINED WITH A UNITY OF TITLE? IF THEY ARE TO REMAIN
 SEPARATE PARCELS, SEE FBC TABLE 602, TABLE 705.8 AND
 REVISE PLAN TO SHOW COMPLIANCE (DISTANCE TO PROPERTY
 LINE, RATED WALLS AS APPLICABLE, PROTECTED OPENINGS IF
 PERMITTED).
  
 IT APPEARS THAT THE PROPERTY LINE BETWEEN 4920 LORING
 DRIVE AND 4850 LORING DRIVE DIVIDES THE NEW BUILDING
 KNOWN AS TRADITIONS II PHASE ONE.
  
 HTTP://WWW.PBCGOV.COM/PAPA/ASPS/PROPERTYDETAIL/PROPERTY
 DETAIL.ASPX?PARCEL=74424312260030000&SRCHTYPE=ADV&OWNER
 =&STREETNO=4850&PREFIX=&STREETNAME=LORING&SUFFIX=&POSTD
 IR=&UNITNO=&SRCHPARCEL=&RANGE=&TWP=&SECTION=&BOOK=&PAGE
 =&LEGAL=&SUBDIV=&MUNI=&ZIP=&USETYPE=&CONDO=
  
 DISTANCE OF PROPOSED DINING ROOM ADDITION TO THE
 PROPERTY LINE IS UNCLEAR.
  
 IF YOU HAVE NOT ALREADY SUBMITTED APPLICATION FOR UNITY
 OF TITLE AND WISH TO DO SO, THE APPLICATION IS
 AVAILABLE ONLINE:
  
 HTTP://WPB.ORG/WP-CONTENT/UPLOADS/SITES/7/2012/05/2011-
 11-14-16-09-54-APPLICATIONFORUNITYOFTITLE.PDF
  
 11. AS PERMITS 14120908 AND 14120909 WERE INITIALLY
 FOUNDATION PERMITS, PLEASE PROVIDE NEW APPLICATIONS
 WITH THE NEW SCOPE OF WORK AND VALUE, SIGNED BY THE
 QUALIFIER AND THE OWNER. ALSO PLEASE NOTE THAT IT
 APPEARS THAT THE NEW BUILDING (TRADITIONS II PHASE ONE)
 IS LOCATED PRIMARILY ON A PARCEL WITH AN ADDRESS OF
 4850 LORING DRIVE, LOCATED ON TRACT C, PARCEL ID
 74-42-43-12-26-003-0000.
  
 I WAS UNABLE TO LOCATE A RECORDED UNITY OF TITLE WHICH
 COMBINES THE TWO SEPARATE PARCELS. IF AVAILABLE, PLEASE
 PROVIDE. SEE OTHER COMMENT REGARDING DISTANCE TO
 PROPERTY LINE.
  
 12. ADVISORY ONLY, THE ART IN PUBLIC PLACES WAS SENT
 VIA EMAIL, CITY OF WEST PALM BEACH CODE OF ORDINANCES
 78-123, 78-126.
  
 THIS PERMIT WILL BE ISSUED WITH THE PROVISO THAT,
 WITHIN 90 DAYS OF ISSUANCE, THE APPROVAL WILL BE
 PROVIDED. PLEASE SEND A COPY OF THE APPROVAL WHEN
 AVAILABLE VIA EMAIL TO [email protected] IN ORDER TO
 DOCUMENT THE PERMIT FILE.
  
 13. ADVISORY ONLY, FS 553.79(7)(C)ALL SHORING AND
 RESHORING PROCEDURES, PLANS, AND DETAILS BE SUBMITTED
 TO THE ENFORCEMENT AGENCY FOR RECORDKEEPING.
 SHORING/RESHORE ENGINEERING TO BE SUBMITTED AT EACH
 LIFT. FAILURE TO SUBMIT SHORING/RESHORE PLANS TO THE
 BUILDING DIVISION FOR PLAN REVIEW AT THE TIME OF EACH
 LIFT MAY RESULT IN A STOP WORK ORDER. AS THIS ISSUE HAS
 BEEN PROBLEMATIC IN THE PAST, IT IS RECOMMENDED THAT A
 NOTE BE INCORPORATED INTO THE PLAN.
  
 14. ADVISORY ONLY, PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED FOR REVIEW PRIOR
 TO INSTALLATION IF NOT SUBMITTED AT THIS TIME, FBC 107,
 FBC 1609 (SUBMITTAL, NO FEE).
  
 15. ADVISORY ONLY, AT THIS TIME, THE "R" (ROOFING) STOP
 HAS A REVIEW STATUS OF "N". PRODUCT APPROVALS AND
 ENGINEERING, IF APPLICABLE, WILL BE REQUIRED AT TIME OF
 ROOF SUB PERMIT APPLICATION IF NOT SUBMITTED DURING THE
 PLAN REVIEW PROCESS FOR THE ADDITION.
  
 16. ADVISORY ONLY, NO ACTION REQUIRED AT THIS TIME.
 PLEASE BE ADVISED THAT LANDSCAPE SHEETS HAVE BEEN
 VOIDED BY ZONING AND HAVE NOT BEEN REVIEWED. A SEPARATE
 LANDSCAPE PERMIT AND REVIEW WILL BE REQUIRED.
  
 17. ADVISORY ONLY; PARKING LOT STRIPING, AWNINGS, SIGNS
 AND OTHER INDEPENDT STRUCTURE ELEMENTS REQUIRE SEPARATE
 PERMITS WHICH WOULD INCLUDE FEES, BUILDING PERMIT
 APPLICATIONS, PLANS AND REVIEWS.
  
 18. FBC EXISTING BUILDING 101.5, ADDITION AND
 ALTERATION TO COMPLY WITH ONE OF THE COMPLIANCE METHODS
 LISTED IN SECTIONS 101.5.1 THROUGH 101.5.3 AS SELECTED
 BY APPLICANT. REVISE PLAN TO INDICATE METHOD OF
 COMPLIANCE SELECTED. AS THIS IS BOTH AN ADDITION AND AN
 ALTERATION, WITH FUTURE ADDITIONS PLANNED, INFORMATION
 REGARDING THE EXISTING BUILDING (SUCH AS THE CODE IT
 WAS PERMITTED UNDER) WOULD HELP EXPEDITE PLAN REVIEW.
 FOR INSTANCE, THE COMMENT REGARDING THE FIRE RESISTANCE
 RATING FOR THE FIRE PUMP ROOM; 2 HOURS REQUIRED BY
 TABLE 508.2.5. IN ORDER TO DETERMINE WHETHER THIS WAS
 IN COMPLIANCE WHEN THE BUILDING WAS CONSTRUCTED AND CAN
 REMAIN AS IS, CODE IN EFFECT FOR CONSTRUCTION OF
 EXISTING BUILDING AND METHOD OF ALTERATION IS REQUIRED.
 THIS IS ONE EXAMPLE OF ISSUES WHICH MAY ARISE, BOTH IN
 PLAN REVIEW AND IN THE FIELD, WHICH WOULD BE ADDRESSED
 UNDER THE APPLICABLE PORTIONS OF THE EXISTING BUILDING
 CODE.
  
 19. FBC ENERGY CONSERVATION 103.2.1.2, ENERGY CALCS
 REQUIRED.
  
 20. G001 PROVIDES A SUMMARY OF BUILDING CODE
 REQUIREMENTS BUT I WAS UNABLE TO LOCATE INFORMATION
 REGARDING THE EXISTING BUILDING. PLEASE PROVIDE
 BUILDING HEIGHT, AREA, TOTAL OCCUPANT LOAD (SEE COMMENT
 REGARDING RISK CATEGORY).
  
 IT APPEARS THAT THIS ADDITION IS AN ADDITION TO A HIGH
 RISE AND IS BEING TREATED AS SUCH IN PLAN REVIEW.
  
 21. G101, PATH OF TRAVEL IS SHOWN ACROSS THE DIAGONAL
 OF THE ROOMS. FBC 1016.1, THIS SHOULD BE SHOWN ALONG
 THE NATURAL UNOBSTRUTED PATH OF TRAVEL. AS FURNITURE
 WILL BE PLACED IN THE CENTER OF THE ROOM, THE PATH
 SHOULD BE MEASURED ALONG THE ROOM PERIMETER.
  
 22. SHEET G101, 2 HOUR SEPARATION REQUIRED FOR THE FIRE
 PUMP ROOM, FBC 2010 508.2.5. SEE OTHER COMMENT
 REGARDING EXISTING BUILDING CODE; IT IS NOT CLEAR IF
 THIS SHOULD BE ADDRESSED OR WAS COMPLIANT AT TIME OF
 PERMITTING.
  
 23. G101, 200 SF PER OCCUPANT IN THE EXTERIOR COURTYARD
 (AREA 110) DOES NOT APPEAR TO BE A REASONABLE OCCUPANT
 LOAD, ESPECIALLY AS ADJACENT TO THIS AREA ON ALL SIDES
 IS ASSEMBLY. IT APPEARS THAT THIS AREA SHOULD ALSO BE
 CLASSIFIED AS ASSEMBLY, 15 SF PER PERSON. PLEASE REVISE
 OCCUPANCY CLASSIFICATION AND OCCUPANT LOAD. IT APPEARS
 HIGHLY LIKELY THAT THIS AREA MAY BE USED AS OUTDOOR
 DINING AT SOME POINT.
  
 24. G101, FOR ASSEMBLY AREAS, OCCUPANT LOAD CAN BE
 BASED ON NET SF AREA, SEE TABLE 1004; GROSS SF WAS
 STATED IN SOME PLACES AND NET WAS STATED IN OTHER
 PLACES. IT IS ACCEPTABLE TO EXCEED THE MINIMUM
 REQUIREMENTS OF THE CODE (USE GROSS RATHER THAN NET),
 BUT THIS METHOD SHOULD REMAIN CONSISTENT.
  
 25. EXIT STRATEGY NOT CLEAR. EX VERANDA IS LABELED AS
 R2, BUT APPEARS TO NOW PRIMARILY SERVE THE ASSEMBLY
 AREA. IT APPEARS THAT THE R2 CORRIDOR EXITS THROUGH
 DOORS 101 AND 101B. IT APPEARS THAT THE EXISTING A2 WAS
 SEPARATED FROM THE EXITING AREA (LOUNGE AND VERANDA)
 ALTHOUGH THE SEPARATION IS NOT SHOWN AS CONTINUOUS ON
 THIS PLAN.
  
 THE NEW ADDITION IS NOW OPEN TO THE EX VERANDA AND USES
 THE SAME EXIT AS THE R2 OCCUPANCY. ONCE A GIVEN LEVEL
 OF EXIT PROTECTION IS ACHIEVED, SUCH LEVEL OF PROECTION
 SHALL NOT BE REDUCED UNTIL ARRIVAL AT THE EXIT
 DISCHARGE. IN THE MEETING, CLASSIFICATION OF THIS AREA
 WAS DISCUSSED. FEEL FREE TO CONTACT ME FOR FURTHER
 DISCUSSION. PERHAPS CONSIDER A VESTIBULE, 1027.1 TO
 RESOLVE THE ISSUE OF A2 EXITING THROUGH R2 OR R2
 EXITING THROUGH A2.
  
 26. G101, REVISE PLAN TO SHOW THE EXIT DISCHARGE. THE
 PATH FROM THE EXIT TO THE PUBLIC WAY OR OTHER COMPLIANT
 AREA SHOULD BE SHOWN ON EITHER THIS PLAN OR ANOTHER
 SHEET, FBC 1027.
  
 27. G101, DOOR 102 IS SHOWN AS AN EXIT, BUT A101 SHOWS
 THIS DOOR ENTERING ANOTHER (FUTURE) BUILDING, PLEASE
 CLARIFY, FBC 3302.1. ALTHOUGH THIS MAY BE ADDRESSED ON
 ANOTHER PLAN CURRENTLY IN THE PLAN REVIEW PROCESS, EACH
 PERMIT IS TO DEMONSTRATE CODE COMPLIANCE WITHOUT
 RELYING ON ANOTHER PLAN (PARTICULARLY ONE WHICH IS NOT
 YET ISSUED OR REVIEWED).
  
 28. UL ASSEMBLIES ARE SPECIFIED ON THE PLANS IN VARIOUS
 PLACES (EXAMPLE A301). FBC 107, EITHER INCORPORATE THE
 UL DETAILS INTO THE PLAN OR, PRIOR TO INSTALLATION, A
 SUBMITTAL WILL BE REQUIRED. THE SUBMITTAL SHOULD
 INCLUDE THE UL ASSEMBLY WITH SPECIFIC OPTIONS ELECTED
 TO BE MARKED. THE SUBMITTAL IS REQUIRED TO BE REVIEWED
 BY DOR. IF THE UL ASSEMBLIES ARE NOT INCORPORATED INTO
 THE PLAN WITH OPTIONS INDICATED, THE SUBMITTAL IS
 REQUIRED TO BE APPROVED THROUGH PLAN REVIEW PRIOR TO
 INSTALLATION.
  
 IF THE ASSEMBLIES WITH APPLICABLE OPTIONS ARE NOT
 INCORPORATED INTO THE PLAN, FUTURE SUBMISSION AS A
 SUBMITTAL WILL BE A PROVISO ITEM.
  
 29. SHEET A301 AND OTHER PAGES AS APPLICABLE, SPECIFY
 FIRE RESISTANCE RATING ON THE PLAN SO DESIGN INTENT IS
 CLEAR, FBC TABLE 601. IF A REDUCTION IS TAKEN DUE TO AN
 EXCEPTION, CITE THE APPLICABLE EXCEPTION (SUCH AS FBC
 2010 BUILDING 402.1.1(2)) AND PROVIDE ENOUGH
 INFORMATION REGARDING THE EXISTING BUILDING TO
 DEMONSTRATE COMPLIANT APPLICABILITY.
  
 30. SHEET A301, SPECIFY UL ASSEMBLY AND RATING REQUIRED
 FOR THE MECHANICAL ROOM FLOOR, BEARING WALLS,
 STRUCTURAL FRAME, FBC TABLE 601.
  
 31. SHEET S3.1, WIND LOADS, 170 MPH, RISK CATEGORY II,
 EXPOSURE C, ENCLOSED IS STATED AS WIND DESIGN CRITIERA
 FBC 1609. SEE SHEET G000, THE MAP FOR RISK CATEGORY III
 AND IV BUILDINGS IS SHOWN (FBC FIGURE 1609B). PLEASE
 CORRELATE.
  
 IN ORDER TO ESTABLISH RISK CATEGORY, PROVIDE TOTAL
 BUILDING OCCUPANT LOAD.
  
 32. S2.1 APPEARS TO HAVE A TYPO, TOP RIGHT, NOTE
 (STATES "PER ACI 18.12.4"); PLEASE CORRECT OR CLARIFY
 AS APPLICABLE.
  
 33. S3.1, STANDARDS CANNOT BE REFERENCED AS "LATEST
 EDITION," SEE FBC 2010 CHAPTER 35. DESIGN IS TO COMPLY
 WITH THE STANDARD VERSION REFERENCED IN CHAPTER 35,
 REVISE ALL AS APPLICABLE.
  
 IF ENGINEER HAS SPECIFIC CONDITIONS WHERE THE EDITION
 USED FOR DESIGN CONFLICTS WITH THE EDITION SPECIFIED IN
 FBC CHAPTER 35, THIS CAN BE PROPOSED UNDER FBC 104.11,
 ALTERNATIVE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION. IF APPLICABLE, THIS SHOULD BE DONE PRIOR
 TO RESUBMITTAL FOR CONSIDERATION BY THE BUILDING
 OFFICIAL.
  
 34. SECTION 1 S4.1, ALSO SECTION 5 AND OTHER PLACES,
 PLYWOOD SHEATHING SHOWN. THIS BUILDING IS REQUIRED TO
 BE NON COMBUSTIBLE, FBC 602.1. REVISE TO INCLUDE
 REQUIREMENT FOR FRT (ALSO TO CORRELATE WITH A101 AND
 OTHER SHEETS), FBC 603.1.1.1.3.
  
 35. S3.2, SPECIFY FLOOR LOADS FOR 2ND FLOOR MECHANICAL
 ROOM, FBC 1606, 1607.
  
 36. A101, DETAILS 7 AND 11, REVISE TO SHOW CENTER LINE
 AND DISTANCE REQUIRED FOR GRAB BAR, SEE FBC 2010
 ACCESSIBILITY FIGURE 604.5.2.
  
 37. A101, DETAIL 3, DOOR APPEARS TO ENCROACH CLEAR
 FLOOR SPACE REQUIRED FOR LAVATORY IN ROOM 111, FBC 2010
 ACCESSIBILITY 603.2.3.
  
 38. A101, DETAIL 3, SHOW 18IN CLEARANCE FOR DOOR 112,
 PULL SIDE, FBC ACCESSIBILITY FIGURE 404.2.4.1(A).
  
 39. A101, DETAIL 3, PROVIDE A DETAIL FOR THE DRINKING
 FOUNTAIN (INCLUDING CLEAR FLOOR SPACE), FBC 2010
 ACCESSIBILITY 211.
  
 40. DETAIL A502 AND 1 A503, OTHER LOCATIONS, ROOF
 DETAIL IS LACKING THE 90LB OR OTHER CAP SHEET FOR TILE
 WHICH IS A REQUIREMENT IN THE CONCRETE ROOF TILE
 PRODUCT APPROVAL, FBC 1609.
  
 41. PROVIDE INFORMATION FOR THE MCKEON DOOR (SPEC
 SHEETS AND TEST REPORT), INSTALLATION INSTRUCTIONS.
 ALSO DISCUSSED IN THE MEETING WAS THE PRACTICALITY FOR
 ACCESS FOR MAINTENANCE, FBC 107.
  
 42. A601, PROVIDE A LEGEND FOR THE HARDWARE SCHEDULE. A
 CLOSER IS REQUIRED FOR DOORS 111 AND 112, FBC
 ACCESSIBILITY 604.8.2.2. ALL DOORS (AND GATES, IF
 APPLICABLE) SERVING ASSEMBLY OCCUPANCY TO HAVE FIRE
 EXIT HARDWARE, FBC 1008.1.10.
  
 43. FBC 1503.4, PROVIDE ROOF DRAINAGE CALUCLATIONS.
  
 44. DETAIL 4 SHEET A503, OVERFLOW SCUPPER APPEARS TO BE
 AT ROOF LEVEL. SEE FBC 1503.4.2.1, OVERFLOW SCUPPERS TO
 BE NOT LESS THAN 2 INCHES NOR MORE THAN 4 INCHES ABOVE
 THE ROOF COVERING.
  
 45. SHEET G101, FIRST FLOOR LIFE SAFETY PLAN, DOES NOT
 INCLUDE EXITING FOR THE OCCUPANTS OF THE COURTYARD, FBC
 1004.8. REVISE PLAN TO INCLUDE TRAVEL DISTANCE. IF
 OCCUPANT LOAD IS OVER 50, DOOR 109A TO SWING IN THE
 DIRECTION OF TRAVEL, BUT ALSO CANNOT BLOCK THE
 CORRIDOR, FBC 1008.1.2, 1005.2.
  
 46. FBC 713, PROVIDE PENETRATION DETAILS FOR WALLS AND
 FLOORS.
  
 47. SEE FIRE COMMENTS REGARDING EXIT SIGNS, FBC 1011.1.
  
 48. REVISE PLAN TO SHOW LOCATION AND TYPE OF FIRE ALARM
 DEVICES, FBC 403.4.2, FBC ACCESSIBILITY 702.
  
 49. NO INFORMATION PROVIDED REGARDING SOME OF THE OTHER
 HIGH RISE REQUIREMENTS (FBC 403). SOME MAY BE EXISTING
 IN ANOTHER PORTION OF THE BUILDING NOT SHOWN, SOME MAY
 NOT BE REQUIRED DUE TO CODE IN EFFECT WHEN BUILDING WAS
 PERMITTED, BUT IN ORDER TO PROVIDE A COMPLETE REVIEW,
 DESIGNER TO ELECT METHOD OF ALTERATION AND STATE THE
 CODE UNDER WHICH THE EXISTING BUILDING WAS CONSTRUCTED.
  
 50. FBC 2010 ACCESSIBILITY 703, SIGNS TO COMPLY WITH
 THIS SECTION.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-01-10 Cont ID  
Sent By jwitmer Date 2015-01-10 Time 13:42 Rev Time 0.00
Received By shill Date 2015-01-10 Time 10:24 Sent To  
Notes
2015-01-10 13:09:46BUILDING PLAN REVIEW
 PERMIT: 14120908
 ADD: 4920 LORING DR.
 CONT: THE WHITING TURNER CO.
 CONTACT: RYAN TEMPONE
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW- FOUNDATION PERMIT/ TRADITION I DINING ROOM
 EXTENTION
 DATE: SAT. JAN. 10/ 2015
 ACTION: DENIED
  
 NOTE: FOUNDATION PERMIT/ PHASED PERMITING. 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION
 105.13 PHASED PERMIT APPROVAL. AFTER SUBMITTAL OF THE
 APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCTION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION
 OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED
 AT THE HOLDER?S OWN RISK WITH THE BUILDING OPERATION
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE, ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  
 1) MISSING INFORMATION EVEN FOR A FOUNDATION PERMIT:
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION
  
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.1 COMMERCIAL BUILDINGS:
 1.1) SITE PLAN SHOWING LOCATION OF THE NEW BUILDING AND
 THE RELATIONSHIP OF OTHER BUILDINGS, PROVIDE DISTANCES
 BETWEEN.
 1.2) SURVEY WITH FLOOD ZONE DESIGNATION
 1.3) SOILS REPORT WITH THE MINIMUM BEARING VALUE FOR
 THIS BUILDING
 1.4) A ARCHITECTURAL SHEET SHOWING THE 1ST FLOOR OR
 BOTTOM FLOOR, WITH FINISH FLOOR ELEVATIONS.
 1.5) OCCUPANCY TYPE
 1.6) MINIMUM BUILDING TYPE/ NUMBER OF STORIES
  
 2) SINCE THE TRADITION TOWER WILL BE ASSUMED THE 10
 STORY THERE HAS BEEN DISCUSSION ABOUT, THIS BUILDING
 WOULD BE CLASSIFIED AS A THRESHOLD BUILDING BY
 DEFINITION AND NEED TO MEET THE STATE REQUIREMENTS FOR
 SUCH A BUILDING. NOTE SHEET S-1.1 DRAWING INDEX
 INDICATES 10 FLOOR FRAMING PLAN.
  
 THE DINING ROOM APPEARS TO BE AN ADDITION TO ANOTHER
 BUILDING BUT CONNECTED BY A ENCLOSED PEDESTRIAN WALKWAY
 BETWEEN BUILDINGS. THE BUILDING TYPE IS NOT KNOWN FOR
 THE OTHER BUILDING, OCCUPANCY, SPRINKLERED OR NOT. THE
 PLANS ALSO DO NOT SHOW FIRE BARRIERS BETWEEN THE
 PEDESTRIAN WALKWAY AND THE BUILDING. PLEASE SHOW
 COMPLIANCE WITH 2010 FBC-B 3104.5.
  
 SINCE THE HEIGHT OF THE BUILDING THE DINING ROOM
 ADDITION IS PART OF THE THRESHOLD BUILDING REQUIREMENTS
 WILL STAY PART OF THIS REVIEW. IN REVIEWING THE P. B.C.
 PROPERTY APPRAISERS OFFICE LIST A STRUCTURE AT 4920
 LORING DR, IS THIS AND ADDITION TO THAT STRUCTURE.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 NOTE :THRESHOLD FORMS WERE E-MAILED TO RYAN TEMPONE
 1/10/2015 01:05 PM.
  
 THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) "
 THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS
 GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH
 HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN
 THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS.
  
 2A) SHEET S-8.10THRESHOLD INSPECTION NOTES NOT INCLUDED
 IN THIS SUBMITTAL. 109.3.6.1 THE ENFORCING AGENCY SHALL
 REQUIRE A SPECIAL INSPECTOR TO PERFORM STRUCTURAL
 INSPECTIONS ON A THRESHOLD BUILDING PURSUANT TO A
 (WRITTEN/ TYPED) STRUCTURAL INSPECTION PLAN PREPARED BY
 THE ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN
 MUST BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE
 ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A
 THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL
 INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION
 PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE
 ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED
 DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE INSPECTION COMPANY &
 THRESHOLD INSPECTOR WILL NEED TO FILL OUT THE SPECIAL
 INSPECTOR AGREEMENT FORMS AND RESUBMIT TO THE CITY FOR
 REVIEW. CONTACT KEN CONRAD MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER
 INFORMATION
 BEFORE THE PERMIT MAY BE ISSUED.
  
 2C) THRESHOLD BLDG, REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND 633 FLORIDA STATUTE.
  
 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
 CONTACT KEN CONRAD
 TEL: 561-805-6666
 E-MAIL: [email protected]
  
 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE
 SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD:
 [email protected]
  
 2F) NOTE THIS IS A DIGITAL PLAN, AFTER PERMIT ISSUANCE,
 THE PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND
 BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO
 SETS OF PLANS WILL NEED TO BE PRINTED IN COLLOR, (1)
 FOR THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP
 INSPECTORS.
  
 2G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR
 IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS.
  
 3) PLEASE PROVIDE DOCUMENTATION HOW THE JOBSITE WILL
 COMPLY WITH :
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 110.7 IMPACT OF
 CONSTRUCTION. ALL CONSTRUCTION ACTIVITY REGULATED BY
 THIS CODE SHALL BE PERFORMED IN A MANNER SO AS NOT TO
 ADVERSELY IMPACT THE CONDITION OF ADJACENT PROPERTY,
 UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT
 GRANTED BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS
 OR CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY
 OWNER. THIS INCLUDES, BUT IS NOT LIMITED TO, THE
 CONTROL OF DUST, NOISE, WATER OR DRAINAGE RUN-OFFS,
 DEBRIS, AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW
 CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL
 HISTORIC SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT
 PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN
 COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES.
 ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL
 NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS,
 POOLS, PATIOS, DRIVEWAYS, DECKS OR SIMILAR ITEMS, ON
 EXISTING PROPERTIES RESULTING IN A SIGNIFICANT DECREASE
 OF PERMEABLE LAND AREA ON ANY PARCEL OR HAS ALTERED THE
 DRAINAGE FLOW ON THE DEVELOPED PROPERTY SHALL, AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED PROFESSIONAL SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 4) 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 5) THE (4) FOUNDATION SHEETS SUBMIITED DOES NOT HAVE
 ENOUGH INFORMATION ON THESE SHEETS WITH DIMENSIONS, NOR
 STEEL LAYOUT FOR THE VERTICAL COLUMNS, NOR COLUMN
 SIZES. THE DETAIL SHEETS AND SECTIONS FOR ELEVATOR PITS
 ARE ALSO MISSING FROM THIS SUBMITTAL, THE MINIMUM
 BEARING VALUE NOT PROVIDED, MINIMUM CONCRETE DESIN MIX,
 THERE IS NOT ENOUGH INFORMATION PROVIDED TO DO A
 THROGOUGH REVIEW.
  
 6) 2010 FBC-B 1816.1 TERMITE PROTECTION. TERMITE
 PROTECTION SHALL BE PROVIDED BY REGISTERED
 TERMITICIDES, INCLUDING SOIL-APPLIED PESTICIDES,
 BAITING SYSTEMS AND PESTICIDES APPLIED TO WOOD, OR
 OTHER APPROVED METHODS OF TERMITE PROTECTION LABELED
 FOR USE AS A PREVENTATIVE TREATMENT TO NEW
 CONSTRUCTION. SEE SECTION 202, REGISTERED TERMITICIDE.
 UPON COMPLETION OF THE APPLICATION OF THE TERMITE
 PROTECTIVE TREATMENT, A CERTIFICATE OF COMPLIANCE SHALL
 BE ISSUED TO THE BUILDING DEPARTMENT BY THE LICENSED
 PEST CONTROL COMPANY THAT CONTAINS THE FOLLOWING
 STATEMENT: "THE BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF SUBTERRANEAN TERMITES.
 TREATMENT IS IN ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE
 AND CONSUMER SERVICES."
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-08-27 Cont ID  
Sent By dharvey Date 2015-08-27 Time 10:18 Rev Time 0.00
Received By dharvey Date 2015-08-27 Time 10:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-06 Cont ID  
Sent By dhayes Date 2015-05-06 Time 10:28 Rev Time 0.00
Received By dhayes Date 2015-05-06 Time 08:13 Sent To  
Notes
2015-05-06 08:21:225/6/2015
 PROJECT: TRADITION ONE DINING ROOM EXPANSION
 PERMIT#: 14120908
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 SHEET E001
 1) CLARIFY NOTE 1. THIS NOTE SIMPLY STATES "PANEL IN
 SCOPE OF WORK." PROVIDE ADDITIONAL DETAIL REGARDING
 THIS NOTE AND ELIMINATE THE NOTES THAT DO NOTE PERTAIN
 TO THIS SCOPE OF WORK. INDICATE THE FULL EXTENT OF THE
 SCOPE OF WORK INVOLVING THE PANELS IN THIS SCOPE. IS IT
 A NEW PANEL WITH A NEW FEEDER? IF EXISTING INDICATE IN
 THE PANEL SCHEDULES ON SHEET E601 WHICH CIRCUIITS ARE
 NEW, WHICH ARE RELOCATED, FROM WHERE, AND WHICH ARE
 EXISTING TO REMAIN.
  
 SHEET E002
 CLARIFY NOTE 1. THIS NOTE SIMPLY STATES "PANEL IN SCOPE
 OF WORK." PROVIDE ADDITIONAL DETAIL REGARDING THIS NOTE
 AND ELIMINATE THE NOTES THAT DO NOTE PERTAIN TO THIS
 SCOPE OF WORK. INDICATE THE FULL EXTENT OF THE SCOPE OF
 WORK INVOLVING THE PANELS IN THIS SCOPE. IS IT A NEW
 PANEL WITH A NEW FEEDER? IF EXISTING INDICATE IN THE
 PANEL SCHEDULES ON SHEET E601 WHICH CIRCUIITS ARE NEW,
 WHICH ARE RELOCATED, FROM WHERE, AND WHICH ARE EXISTING
 TO REMAIN.
  
 SHEET E102
 1) INDICATE THE LOCATIONS OF THE ELECTRICAL PANELS IN
 THIS SCOPE NLGP1A, EMLGP1, AND NHHP ON THE FLOOR PLAN.
 2) IDENTIFY CIRCUITS CLEARLY ON THE FLOOR PLAN. INCLUDE
 THE NAME OF THE PANEL OF ORIGIN AS WELL AS THE CIRCUIT
 NUMBER.
 3) CLARIFY CIRCUITRY AND EQUIPMENT ON FLOOR PLAN. THERE
 IS A NOTE 2 THAT CALLS OUT AN RTU ON THE SECOND FLOOR
 AND A CONFLICTING EQUIPMENT DESIGNATION AS AHU-1-1 WITH
 A NOTE THE MAKES REFFERENCE TO THE CIRCUIT FEEDING IT
 COMING FROM PANEL MDP. THERE IS NO EQUIPMENT NAMED
 EITHER RTU OR AHU 1-1 IN PANEL MDP. CLARIFY IF THIS IS
 AND AHU OR AND RTU. CLARIFY IT'S NUMBER DESIGNATION,
 PANEL AND CIRCUIT FEEDING IT.
  
 SHEET E-103
 1) FBC-ENERGY 505.2 LIGHTING CONTROLS (MANDATORY).
 LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS
 REQUIRED IN SECTIONS 505.2.1, 505.2.2, 505.2.3 AND
 505.2.4.
 2) INDICATE THE LOCATIONS OF THE ELECTRICAL PANELS IN
 THIS SCOPE NLGP1A, EMLGP1, AND NHHP ON THE FLOOR PLAN.
 3) IDENTIFY CIRCUITS CLEARLY ON THE FLOOR PLAN. INCLUDE
 THE NAME OF THE PANEL OF ORIGIN AS WELL AS THE CIRCUIT
 NUMBER.
  
 E601
 1) INDICATE WHICH CIRCUIITS ARE NEW, WHICH ARE
 RELOCATED, FROM WHERE, AND WHICH ARE EXISTING TO
 REMAIN.
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR SITE LIGHTING, GENERATORS. HOOD
 EXHAUST, FIRE ALARM, ACCESS CONTROL SYSTEM, SECURITY,
 CCTV, AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2015-08-19 Cont ID  
Sent By cranford Date 2015-08-19 Time 14:51 Rev Time 0.00
Received By cranford Date 2015-08-19 Time 14:49 Sent To  
Notes
2015-08-19 14:51:10ENGINEERING DEVELOPMENT APPLICATION RECEIVED 7/22/2015
 (E15080021)

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2015-06-30 Cont ID  
Sent By cranford Date 2015-06-30 Time 09:27 Rev Time 0.00
Received By cranford Date 2015-06-30 Time 09:09 Sent To  
Notes
2015-06-30 09:27:10SEE PREVIOUS COMMENTS

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-04-10 Cont ID  
Sent By cranford Date 2015-04-10 Time 09:22 Rev Time 0.00
Received By cranford Date 2015-04-10 Time 09:11 Sent To  
Notes
2015-04-10 09:22:49ENGINEERING DEVELOPMENT APPROVAL FROM THE CITY?S PUBLIC
 WORKS DEPARTMENT IS REQUIRED FOR ALL PROJECTS INVOLVING
 OR AFFECTING THE CITY?S STREET RIGHT-OF-WAYS,
 EASEMENTS, POTABLE WATER SYSTEM, SANITARY SEWER SYSTEM,
 STORMWATER SYSTEM, SOLID WASTE COLLECTION, OR
 PEDESTRIAN AND VEHICULAR TRAFFIC. THIS INCLUDES ANY
 WORK THAT INCREASES IMPERVIOUS AREAS; CHANGES THE
 DIRECTION, VELOCITY, OR TIMING OF STORMWATER DISCHARGE;
 OR CREATES A CONDITION OF ENVIRONMENTAL CONCERN. THE
 ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS CAN
 BE DOWNLOADED AT
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 PLEASE SUBMIT AN APPLICATION FOR ENGINEERING
 DEVELOPMENT APPROVAL AND MAKE A NOTE ON THE CIVIL PLANS
 INCLUDED IN THE BUILDING APPLICATION SUBMITTAL THAT
 THEY ARE FOR REFERENCE ONLY.
  
 KELLY CRANFORD, PE
 CITY LAND DEVELOPMENT ENGINEER
 [email protected]
 561-494-1098 (OFFICE)
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-07-15 Cont ID  
Sent By wjolin Date 2015-07-15 Time 11:00 Rev Time 0.00
Received By wjolin Date 2015-06-25 Time 14:11 Sent To  
Notes
2015-06-25 17:40:214920 LORING DRIVE
 PERMIT #14120908
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE DEPT RESPONSE: COINCIDENTALLY THE EFFECTIVE DATE
 OF THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE
 IS DECEMBER 31, 2014.
 DESIGN TEAM RESPONSE: "PROJECT SUBMITTED 12/31/2014.
 THIS PROJECT IS UNDER THE 2010 FFPC."
 ORIGINAL COMMENT - SHEET G001: UPDATE THE CODE LIST TO
 REFERENCE THE 5TH EDITION OF THE FLORIDA FIRE
 PREVENTION CODE WHICH CONTAINS THE 2012 EDITION OF BOTH
 NFPA 1 AND NFPA 101 WITH FLORIDA AMENDMENTS.
  
 DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-03-31 Cont ID  
Sent By wjolin Date 2015-03-31 Time 14:27 Rev Time 0.00
Received By wjolin Date 2015-03-31 Time 11:15 Sent To  
Notes
2015-03-31 11:25:344920 LORING DRIVE
 PERMIT #14120908
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 DEMO: PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION
 AND DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS
 OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 DEMO: PROVIDE DRAWING NOTE INDICATING, "FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY."
  
 DEMO: PER NFPA 241, CONSTRUCTION/DEMOLITION AREAS SHALL
 BE SEPARATED WITH A 1-HOUR FIRE BARRIER FROM OTHER
 AREAS NOT UNDER CONSTRUCTION OR DEMOLITION.
  
 SHEET G001: UPDATE THE CODE LIST TO REFERENCE THE 5TH
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2012 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 SHEET G101: TWO DINING ROOM EXITS DISCHARGE OUTSIDE AT
 THE EAST SIDE OF THE BUILDING INTO THE CONSTRUCTION
 ZONE FOR THE NEW HIGH-RISE BUILDING.
  
 SHEET G101: FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES
 WITH AN OCCUPANT LOAD OF 100 OR MORE PERSONS (50
 PERSONS PER THE FLORIDA BUILDING CODE), PANIC HARDWARE
 SHALL BE PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH.
 NO OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT
 BE RELEASED BY THE PANIC HARDWARE.
  
 SHEET A101: SUBMIT A FURNITURE/SEATING PLAN.
  
 SHEET A101: EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING
 FIXED SEATS SHALL HAVE THE OCCUPANT LOAD OF THE ROOM
 POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM
 THE ROOM. SIGNS SHALL BE DURABLE AND INDICATE THE
 NUMBER OF OCCUPANTS PERMITTED FOR EACH ROOM.
  
 SHEET A101: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED
 EXIT DOORS WITH EXIT SIGNS.
  
 SHEET E103: VERANDA #101/CORRIDOR HAS EXIT SIGNS SPACED
 MORE THAN 100 FEET APART.
  
 SHEET E103: NO ENGINEERED FIRE ALARM DRAWINGS
 SUBMITTED. PER FBC SECTION 907.1.1 CONSTRUCTION
 DOCUMENTS - "CONSTRUCTION DOCUMENTS FOR FIRE ALARM
 SYSTEMS SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND
 SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS
 OF THIS CODE, THE FLORIDA FIRE PREVENTION CODE, AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL." PER SECTION
 12.3.4.3.3, PROVIDE SPEAKER/STROBE NOTIFICATION
 APPLIANCES AS ASSEMBLY OCCUPANCIES WITH AN OCCUPANT
 LOAD EXCEEDING 300 OCCUPANTS SHALL RECEIVE FIRE ALARM
 NOTIFICATION BY VISIBLE SIGNALS AND VOICE
 ANNOUNCEMENTS.
  
 SHEET FP001: NO WATER SUPPLY INFORMATION PROVIDED
 (HYDRANT FLOW TEST OR FIRE PUMP TEST DATA).
  
 DISCLAIMER: REVIEW AND APPROVAL BY THE AHJ SHALL NOT
 RELIEVE THE OWNER, CONTRACTOR, ETC. OF THE
 RESPONSIBILITY OF COMPLIANCE WITH CODE (NFPA 1, SECTION
 1.14.4). FBC SECTION 105.4.1 PERMIT INTENT: A PERMIT
 ISSUED SHALL BE CONSTRUED TO BE A LICENSE TO PROCEED
 WITH THE WORK AND NOT AS AUTHORITY TO VIOLATE, CANCEL,
 ALTER OR SET ASIDE ANY OF THE PROVISIONS OF THE
 TECHNICAL CODES, NOR SHALL ISSUANCE OF A PERMIT PREVENT
 THE BUILDING OFFICIAL FROM THEREAFTER REQUIRING A
 CORRECTION OF ERRORS IN PLANS, CONSTRUCTION OR
 VIOLATIONS OF THIS CODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-08-27 Cont ID  
Sent By skennedy Date 2015-08-27 Time 10:28 Rev Time 0.00
Received By skennedy Date 2015-06-19 Time 11:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-05-06 Cont ID  
Sent By lmarchan Date 2015-05-06 Time 15:32 Rev Time 0.00
Received By lmarchan Date 2015-03-06 Time 14:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-28 Cont ID  
Sent By skennedy Date 2015-01-28 Time 10:30 Rev Time 0.00
Received By skennedy Date 2015-01-05 Time 14:32 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2015-08-06 Cont ID  
Sent By shill Date 2015-08-06 Time 13:26 Rev Time 0.00
Received By shill Date 2015-08-06 Time 13:26 Sent To  
Notes
2015-08-06 13:30:58PER WILLIE SWOPE, NO IMPACT FEES REQUIRED
 SEE EMAIL IN FILE
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2015-07-29 Cont ID  
Sent By shill Date 2015-07-29 Time 18:12 Rev Time 0.00
Received By shill Date 2015-07-29 Time 18:12 Sent To  
Notes
2015-07-29 18:13:38THE PLANS SUBMITTED ARE NOT STAMPED BY THE COUNTY. NO
 RECEIPT WAS PROVIDED.
  
 IMPACT FEE ASSESSMENT REQUIRED, 561-233-5025
  
 (IMPACT FEES FOR 14120909, PHASE I AND PHASE II, ARE OK
 AND HAVE BEEN ROUTED TO RECORDS)
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-07-27 Cont ID  
Sent By shill Date 2015-07-27 Time 15:33 Rev Time 0.00
Received By shill Date 2015-07-27 Time 15:33 Sent To  
Notes
2015-07-27 15:34:11IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY PRIOR TO
 PERMIT ISSUANCE. THE PLANS ARE TO BE STAMPED AND THE
 RECEIPT SHOWING FEES WERE PAID IS TO BE PROVIDED.
  
 561-233-5025
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-04-12 Cont ID  
Sent By shill Date 2015-04-12 Time 18:07 Rev Time 0.00
Received By shill Date 2015-04-12 Time 18:07 Sent To  
Notes
2015-04-12 18:08:06SEE BUILDING REVIEW
 561-233-5025 FOR MORE INFORMATION
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-08-06 Cont ID  
Sent By hmoser Date 2015-08-06 Time 10:54 Rev Time 0.00
Received By hmoser Date 2015-07-30 Time 13:53 Sent To  
Notes
2015-08-06 10:54:14PASS PROVISO
 1) SEPARATE APPLICATION, PLANS AND PERMIT REQUIRED FOR
 KITCHEN HOODS.
 KITCHEN HOODS AND EXHAUST WERE NOT REVIEWED ON THIS
 PLAN.
 2) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-04-22 Cont ID  
Sent By hmoser Date 2015-04-22 Time 14:41 Rev Time 0.00
Received By hmoser Date 2015-04-20 Time 10:11 Sent To  
Notes
2015-04-20 13:59:18PLAN DENIED
 1) GREASE DUCT AND HOOD REQUIRE SEPARATE APPLICATION,
 PLAN AND PERMIT
 2) PROVIDE FRESH AIR REQUIREMENTS ON THE PLAN PER TABLE
 403.3 FBC (M) 2010
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 4 Status P Date 2015-08-11 Cont ID  
Sent By tklarge Date 2015-08-11 Time 13:41 Rev Time 0.00
Received By tklarge Date 2015-08-11 Time 13:40 Sent To  
Notes
2015-08-11 13:41:20APPROVED WITH THE FOLLOWING PROVISOS;
  
 1) SUBMIT TOTAL BTU LOAD ON GAS SYSTEM, THE TOTAL
 DISTANCE FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET, TYPE OF PIPE, TYPE OF GAS, PSI OF THE SYSTEM,
 MANUF. SPECS FOR ALL NEW EQUIPMENT. WPB AMEND. TO FBC
 SEC. 103.3.5.1.5.
 2)SUBMIT ROOF DRAINAGE CALCULATIONS.CALCULATIONS SHALL
 INCLUDE 1/2 THE AREA OF ANY VERTICAL WALL THAT DIVERTS
 RAINWATER TO THE ROOF AND SHALL ALSO INCLUDE ANY AREAS
 OF THE SLOPED ROOFS THAT DIVERT RAINWATER ONTO THE FLAT
 ROOFS.2010 FBC-PLUMBING SEC. 1106..1, 1106.4, 1106.7..
 3)TWO COPIES OF "KES" DRAWINGS SHALL BE SUBMITTED FOR
 REVIEW. WPB AMNED. TO FBC SEC. 107.2.1.
 4) SIZING OF SANITARY AND INDIRECT WASTE PIPING SHALL
 COMPLY W/CHAPT.7 & CHAPT. 8 OF 2010 FBC-PLUMBING.
 5) PER THE LIFE-SAFETY PLAN (G101) THE TOTAL ASSEMBLY
 OCCUPANT LOAD IS 160 PERSONS. IT IS DESIGNATED AS A-2.
 TABLE 403.1 REQUIRES 2 WATER CLOSETS FOR MALES (1 PER
 75) AND TWO FOR FEMALES (1 PER 75). THE PLAN SHOWS ONE
 EACH. REVISE THE FIXTURE COUNT AND SHOW THE ADDITIONAL
 FIXTURES IN THE RESTROOMS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-08-04 Cont ID  
Sent By tklarge Date 2015-08-01 Time 04:32 Rev Time 0.00
Received By tklarge Date 2015-08-01 Time 02:39 Sent To  
Notes
2015-08-01 04:39:251) SUBMIT TOTAL BTU LOAD ON GAS SYSTEM, THE TOTAL
 DISTANCE FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET, TYPE OF PIPE, TYPE OF GAS, PSI OF THE SYSTEM,
 MANUF. SPECS FOR ALL NEW EQUIPMENT. WPB AMEND. TO FBC
 SEC. 103.3.5.1.5.
 2)SUBMIT ROOF DRAINAGE CALCULATIONS.CALCULATIONS SHALL
 INCLUDE 1/2 THE AREA OF ANY VERTICAL WALL THAT DIVERTS
 RAINWATER TO THE ROOF AND SHALL ALSO INCLUDE ANY AREAS
 OF THE SLOPED ROOFS THAT DIVERT RAINWATER ONTO THE FLAT
 ROOFS.2010 FBC-PLUMBING SEC. 1106..1, 1106.4, 1106.7..
 3)TWO COPIES OF "KES" DRAWINGS SHALL BE SUBMITTED FOR
 REVIEW. WPB AMNED. TO FBC SEC. 107.2.1.
 4) SIZING OF SANITARY AND INDIRECT WASTE PIPING SHALL
 COMPLY W/CHAPT.7 & CHAPT. 8 OF 2010 FBC-PLUMBING.
 5) PER THE LIFE-SAFETY PLAN (G101) THE TOTAL ASSEMBLY
 OCCUPANT LOAD IS 160 PERSONS. IT IS DESIGNATED AS A-2.
 TABLE 403.1 REQUIRES 2 WATER CLOSETS FOR MALES (1 PER
 75) AND TWO FOR FEMALES (1 PER 75). THE PLAN SHOWS ONE
 EACH. REVISE THE FIXTURE COUNT AND SHOW THE ADDITIONAL
 FIXTURES IN THE RESTROOMS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-04-04 Cont ID  
Sent By tklarge Date 2015-04-04 Time 12:33 Rev Time 0.00
Received By tklarge Date 2015-04-04 Time 04:36 Sent To  
Notes
2015-04-04 06:41:191) THE PERMIT APPLICATION IS FOR A FOUNDATION ONLY BUT
 THERE ARE ADDITIONAL PLUMBING PLANS IN THE SET FOR WHAT
 APPEARS TO BE MOST OF THE PLUMBING. I UNDERSTAND THE
 REASONING FOR THIS BUT SINCE THE PERMIT IS FOR THE
 FOUNDATION ONLY, SUBMIT ONLY THE PLUMBINHG PLANS THAT
 ARE RELEVANT TO THE INSTALLATION OF THE UNDERGROUND
 PLUMBING. INCLUDE CONDENSATE, SANITARY, STORM, DOMESTIC
 WATER, GAS, ETC. WPB AMEND. TO 2010 FBC SEC.
 107.3.5.1.3.
 2) SUBMIT A SLAB REPAIR DETAIL FOR THE CONCRETE SLAB
 THAT IS TO BE CUT TO INSTALL THE PLUMBING.WPB AMEND. TO
 2010 FBC SEC.107.2.1.
 3) SHT.P501 - AS DRAWN, THE SANITARY RISER DIAGRAM DOES
 NOT COMPLY WITH THE 2010 FPC SEC.909.1 FOR A HORIZONTAL
 WET VENT AND THE TYPE OF FIXTURES AND DRAINAGE FIXTURE
 UNIT LOAD PERMITTED PER TABLE 909.3.
 4) SHT. P501 - SIZE ALL SECTIONS OF THE SANITARY RISER
 DIAGRAM WHEN PLANS ARE RESUBMITTED.WPB AMEND. TO 2010
 FBC SEC. 107.3.5.1.3.
  
 THE FOLLOWING ADDITIONAL PLUMBING COMMENTS WILL APPLY
 WHEN THE ENTIRE PLAN IS SUBMITTED FOR THE MASTER
 PERMIT:
  
 ADDITIONAL COMMENTS
 4) SHT. A101 - ENLARGED TOILET ROOM DETAIL #3 (ROOM
 #111 ) - THE DOOR APPEARS TO SWING INTO THE CLEAR FLOOR
 SPACE FOR THE LAVATORY IN TOILET ROOM #111. COMPLY WITH
 THE 2010 FAC SEC.603.2.3.( SEE EXCEPTIONS).
 5) SHT. A103 - ROOF DRAIN RISER - 1/2 OF THE AREA OF
 ANY VERTICAL WALL THAT DIVERTS RAINWATER TO THE ROOF
 SHALL BE ADDED TO THE PROJECTED ROOF AREA FOR INCLUSION
 IN CALCULATING VERTICAL CONDUCTORS, LEADERS AND
 HORIZONTAL STORM DRAINAGE PIPING. 2010 FPC SEC.1106.4.
 6) SHT. A503 - ROOF SCUPPER DETAIL - SUPPLY THE LENGTH
 DIMENSION OF THE SCUPPER. THE DESIGN OF THE SCUPPER
 SHALL COMPLY W/ 2010 FPC TABLE 1106.7.THE PLAN NOTES
 THE SCUPPER IS DESIGNED PER SMACNA. CLARIFY.SEE 2010
 FBC SECS 1503.4 THROUGH 1503.4.2.1.
 7) SHT. A103 - THE AREAS OF THE SLOPED ROOFS THAT ARE
 DISCHARGING RAINWATER ONTO THE FLAT ROOFS SHALL ALSO BE
 ADDED INTO THE ROOF DRAINAGE CALCULATIONS. SUBMIT
 COMPLETE ROOF DRAINAGE CALCULATIONS THAT INCLUDE THE
 AREA OF THE PARAPET WALL AND ALSO THE SLOPED
 ROOFS.SUBMIT A COMPLETE STORMWATER RISER DIAGRAM FOR
 REVIEW.
 8) SHT.P001 - THE ACCESSIBLE DRINKING FOUNTAIN/COOLER
 IS LISTED AS A SINGLE LEVEL. TWO ARE REQUIRED PER THE
 FAC SEC.211.2. CLARIFY.
 9) SUBMIT FIRESTOPPING DETAILS FOR ALL FLOOR AND WALL
 PIPING PENETRATIONS. 2010 FBC SEC. 713.
 10) TWO COPIE OF COMPLETE SETS OF PLANS SHALL BE
 SUBMITTED WITH ALL SHEETS LISTED ON SHT.G 000 INCLUDING
 THE "KES " DRAWINGS REFERRED TO ON SHT. P100.
 11) SUBMIT A SLAB REPAIR DETAIL FOR WHERE THE SLAB IS
 TO BE CUT TO INSTALL ANY UNDERGROUND PLUMBING. WPB
 AMEND. TO 2010 FBC SEC.107.2.1.
 12) SHT. P100 - SIZE ALL SECTIONS OF THE STORMWATER
 DRAINAGE SYSTEM. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 13) THE DRINKING FOUNTAIN IN VESTIBULE #113 APPEARS TO
 VIOLATE SEC.307.1 FOR PROTRUSION LIMITS. CLARIFY.
 CLEARLY SHOW THE REQUIRED 30" X 48" CLEAR FLOOR SPACE
 FOR THE DRINKING FOUNTAIN. FAC SEC.305, 602.
 14) ALL HOSE BIBBS/WALL HYDRANTS SHALL BE VALVED PER
 THE FPC SEC.606.2.
 15) SUBMIT DETAILS/PIPING DIAGRAM FOR THE WATER
 FILTRATION SYSTEM. WPB AMEND. TO 2010 FBC SEC.107.2.1.
 16) THE WATER SUPPLY TO BEVERAGE DISPENSERS SHALL BE
 PROTECTED AGAINST BACKFLOW PER THE FPC SEC.608.16.1.
 COFFEE MACHINES AND NONCARBONATED BEVERAGE DISPENSERS
 SHALL BE PROTECTED AGAINST BACKFLOW PER THE FPC
 SEC.608.16.10.
 17) SUBMIT PLANS AND A GAS RISER DIAGRAM FOR ALL GAS
 PIPING TO BE INSTALLED. WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 18) SUBMIT A COMPLETE WATER RISER DIAGRAM FOR ALL NEW
 WATER PIPNG THAT IS GOING TO BE INSTALLED.
 19) SUBMIT A CONDENSATE RISER DIAGRAM FOR REVIEW.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status N Date 2015-01-13 Cont ID  
Sent By tklarge Date 2015-01-13 Time 13:42 Rev Time 0.00
Received By tklarge Date 2015-01-13 Time 13:41 Sent To  
Notes
2015-01-13 13:42:11NO PLUMBING SHOWN.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2015-08-21 Cont ID  
Sent By shill Date 2015-08-21 Time 08:54 Rev Time 0.00
Received By shill Date 2015-08-21 Time 08:54 Sent To  
Notes
2015-08-21 08:58:29PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND
 ROOFING SUB PERMIT ARE REQUIRED PRIOR TO INSTALLATION
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2015-04-12 Cont ID  
Sent By shill Date 2015-04-12 Time 17:36 Rev Time 0.00
Received By shill Date 2015-04-12 Time 17:36 Sent To  
Notes
2015-04-12 17:37:35NO ROOFING INFORMATION PROVIDED AT THIS TIME.
  
 DESIGN PRESSURES ON SHEET S3.4 HAVE NOT BEEN VERIFIED
 DUE TO A DISCREPANCY BETWEEN G000 AND S3.1 (RISK
 FACTOR).
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2016-04-22 Cont ID  
Sent By shill Date 2016-04-22 Time 06:54 Rev Time 0.00
Received By shill Date 2016-04-22 Time 05:54 Sent To  
Notes
2016-04-22 07:38:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PER CONVERSATION WITH WENDY ANDERSON, INVESTIGATOR
 FOR FLORIDA BOARD OF PROFESSIONAL ENGINEERS, THE TWO
 ENGINEERS WHICH HAVE TAKEN OVER PORTIONS OF THE JOB
 (MEPFT) ARE SUCCESSOR ENGINEERS (SEE FAC61G15-27.001)
 AND, AS SUCH, MUST PROVIDE ALL DOCUMENTS PREPARED BY
 THE ORIGINAL ENGINEER WITH THE SUCCESSOR PROFESSIONAL
 ENGINEER'S TITLE BLOCK IN COMPLIANCE WITH WITH FS471
 AND FAC61G15-23.002.
  
 IT APPEARS THAT THE INTENT OF THE TITLE BLOCK
 REQUIREMENT (FS471, FAC61G15-23.002) IS TO DEMONSTRATE
 RESPONSIBILITY, AND FBPE RESPONSIBILITY IS TAKEN BY
 INDIVIDUALS, NOT FIRMS. ALLOWING THE ORIGINAL
 ENGINEER'S NAME AND LICENSE NUMBER TO REMAIN ON ALL
 PLAN SHEETS (ALTHOUGH BOTH ORIGINAL ENGINEERS AND BOTH
 SUCCESSOR PROFESSIONAL ENGINEERS ALL WORK FOR THE SAME
 ENGINEERING FIRM) DOES NOT MEET THE INTENT OR THE
 LETTER OF THE LAW AND RULE. AS THIS DOCUMENT HAS BEEN
 REVISED TWICE SINCE ISSUANCE, PLEASE DO THE FOLLOWING:
  
 IN ORDER TO EXPEDITE APPROVAL OF ALL SIGNATURE
 DOCUMENTS, AND TO BRING THE PERMIT RECORD FILE INTO
 COMPLIANCE, PROVIDE A DOCUMENT WHICH SHOWS THE HISTORY
 OF EACH MEPFT SHEET (AND ANY OTHER SHEETS AFFECTED, IF
 APPLICABLE). A SPREADSHEET IS SUGGESTED (AND IS
 SOMETIMES PROVIDED TO US VOLUNTARILY FOR SOME PROJECTS
 TO BETTER TRACK LARGE PROJECTS).
  
 FOR ALL SHEETS NOT SUPERSEDED BY SUBSEQUENT REVISIONS,
 SUBMIT A REVISION WHICH CORRECTS THE TITLE BLOCK TO BE
 IN ACCORDANCE WITH FAC61G15-27.001, FAC61G15-23.002.
  
 2. THE FORMAT OF THE SIGNATURE DOCUMENT IS ACCEPTABLE
 (ONE PDF DOCUMENT, COVER PAGE CLEARLY INDICATES EACH
 SHEET FOR WHICH EACH DESIGN PROFESSIONAL IS TAKING
 RESPONSIBILITY, AND EACH DESIGN PROFESSIONAL HAS SIGNED
 AND SEALED EACH SHEET.
  
 THE BUILDING DIVISION WILL ALWAYS ACCEPT SIGNATURE
 DOCUMENTS, DIGITAL SIGNATURES, ELECTRONIC SIGNATURES
 WHICH ARE IN ACCORDANCE WITH THE LAW. A PREFERRED
 PRACTICE MAY BE DEVELOPED.
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2016-04-22 Cont ID  
Sent By shill Date 2016-03-24 Time 05:48 Rev Time 0.00
Received By shill Date 2016-03-24 Time 05:48 Sent To  
Notes
2016-04-22 05:50:26SPOT CHECKED FMEP PAGES; PLAN PAGES STILL HAVE SAME
 ISSUES (NOTHING APPEARS TO BE CHANGED BUT INCLUDE A
 DATE FOR A REVISION ON SOME SHEETS, NOTHING CLOUDED).
 CALLED RYAN TEMPONE TO DISCUSS ISSUES AND OPTIONS FOR
 RESOLUTION.
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2016-01-08 Cont ID  
Sent By shill Date 2016-04-22 Time 05:46 Rev Time 0.00
Received By shill Date 2016-01-07 Time 14:23 Sent To  
Notes
2016-04-22 05:48:06CALLED RYAN TEMPONE; SPOT CHECK OF THE SHEETS WHICH
 PREVIOUSLY HAD ISSUES (FMEP) ARE NOT IDENTICAL TO THE
 DIGITAL SET. HAD CONVERSATION ABOUT OPTIONS.
  
 NOTE THAT THE INCONSISTENCIES APPEAR TO BE DATES, BUT
 NO CLOUDED ITEMS SHOWN AS CHANGES. IT IS DIFFICULT TO
 DETERMINE WHAT, IF ANYTHING, WAS ACTUALLY CHANGED.
  
  
2016-01-07 14:23:41GIVEN TO SHILL TO VERIFY

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-09-23 Cont ID  
Sent By shill Date 2015-09-23 Time 09:58 Rev Time 0.00
Received By shill Date 2015-09-23 Time 09:58 Sent To  
Notes
2015-09-23 10:05:46THIS SET OF PLANS ARE STRICTLY FOR THE PURPOSE OF SEAL
 AND SIGNATURE FOR THE PLANS UPLOADED TO PROJECTDOX
 THIS SET OF PLANS DO NOT INCLUDE REDLINES, PROVISOS,
 AND PLAN REVIEWER STAMPS. SEE PROJECTDOX FOR THE ISSUED
 SET OF PLANS
  
 A SIGNED AND SEALED HARD COPY OF EACH SHEET WAS
 SUBMITTED
  
 A LETTER WAS SUBMITTED REGARDING THE CHANGE OF THE
 ELECTRICAL ENGINEER. THE COMPANY (TLC) REMAINS THE SAME
 BUT THE INDIVIDUAL NOW SIGNING AND SEALING THE
 ELECTRICAL PLANS IS DENNIS O. DAVIS, PE.
  
 ORIGINAL SIGNED AND SEALED GEOTECHNICAL REPORT IS
 REQUIRED.
  
 SHEET E003 VOIDED BY MIKE ALBARRAN (THIS SHEET IS AN
 OLD VERSION OF E002)
 SHEETS T000, T101, T201, T300 ARE VOIDED AS THE PAPER
 SIGNED & SEALED VERSION DATED 5/29/15 AND 2/13/15 ARE
 NOT IDENTICAL TO THE PROJECTDOX VERSION DATED 11/6/14
  
 PROVISO - ELECTRICAL ENGINEER IS TO EITHER:
 SUBMIT A SIGNED AND SEALED LETTER WHICH STATES THAT
 SHEET E701 VERSION DATED 5/29/15 IS IDENTICAL TO THE
 PROJECTDOX VERSION DATED 11/6/14, OR
 ELECTRICAL ENGINEER IS TO SUBMIT SHEET E701 SIGNED AND
 SEALED, VERSION DATED 11/6/14
  
 PROVISO - ENGINEER IS TO EITHER:
 SUBMIT A SIGNED AND SEALED LETTER WHICH STATES THAT
 SHEET FP101 VERSION DATED 2/13/15 IS IDENTICAL TO THE
 PROJECTDOX VERSION DATED 11/6/14, OR
 ENGINEER IS TO SUBMIT SHEET FP101 SIGNED AND SEALED,
 VERSION DATED 11/6/14
  
 PROVISO - ENGINEER IS TO EITHER:
 SUBMIT A SIGNED AND SEALED LETTER WHICH STATES THAT
 SHEET P102 VERSION DATED 2/13/15 IS IDENTICAL TO THE
 PROJECTDOX VERSION DATED 11/6/14, OR
 ENGINEER IS TO SUBMIT SHEET P102 SIGNED AND SEALED,
 VERSION DATED 11/6/14
  
 PROVISO - ENGINEER IS TO EITHER:
 SUBMIT A SIGNED AND SEALED LETTER WHICH STATES THAT
 SHEET M501 VERSION DATED 2/13/15 IS IDENTICAL TO THE
 PROJECTDOX VERSION DATED 11/6/14, OR
 ENGINEER IS TO SUBMIT SHEET M501 SIGNED AND SEALED,
 VERSION DATED 11/6/14
  
 LETTERS TO BE SENT VIA EMAIL TO [email protected],
 [email protected] TODAY AND ORIGINALS SENT VIA EXPRESS
 MAIL
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 CITY HALL
 401 CLEMATIS STREET, 1ST FLOOR
 BUILDING DIVISION
 WEST PALM BEACH, FL 33401
  
  
  
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status P Date 2015-08-04 Cont ID  
Sent By shill Date 2015-08-04 Time 16:56 Rev Time 0.00
Received By shill Date 2015-08-04 Time 16:56 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2015-07-27 Cont ID  
Sent By shill Date 2015-07-27 Time 09:47 Rev Time 0.00
Received By shill Date 2015-07-27 Time 09:47 Sent To  
Notes
2015-07-27 09:53:53****CORRECTIONS****
 14120908, 14120909
 THRESHOLD INSPECTION PLAN, SPECIAL INSPECTOR AGREEMENT
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THRESHOLD INSPECTION PLAN, ITEM 6.02 B AND C REFER
 TO OPENINGS IN THE FIRST 60 FEET. FBC 1609.1.2(2),
 PLEASE REVISE TO COMPLY WITH THIS SECTION (ALL OPENINGS
 REQUIRED TO HAVE IMPACT PROTECTION).
  
 2. THE SPECIAL INSPECTOR AGREEMENT IS LACKING THE
 SIGNATURE OF THE DESIGNER OF RECORD, PAGE 5 OF 6 (THIS
 SHOULD BE SIGNED AND SEALED).
  
 PLEASE REMOVE THE OLD SHEETS AND REPLACE WITH THE NEW
 SHEETS.
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2015-04-12 Cont ID  
Sent By shill Date 2015-04-12 Time 18:07 Rev Time 0.00
Received By shill Date 2015-04-12 Time 18:07 Sent To  
Notes
2015-04-12 18:07:39SEE BUILDING REVIEW
  

Review Stop Z ZONING
Rev No 4 Status P Date 2015-09-02 Cont ID  
Sent By eschneid Date 2015-09-02 Time 09:35 Rev Time 0.75
Received By eschneid Date 2015-09-02 Time 09:35 Sent To  
Notes
2015-09-02 09:37:52PASSED W/PROVISO
  
 1) LANDSCAPE AND IRRIGATION REQUIRE SEPARATE PERMITS
 WITH PLANS.
  
 2) RETAINING WALL UNDER PERMIT 15090033.
  
 3) ALL PLANS SHALL SHOW SAME AS-BUILT CONDITIONS PRIOR
 TO C.O.
  
 4) MINOR PD AMEDMENT IS REQUIRED FOR AS-BUILT
 CONDITIONS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.

Review Stop Z ZONING
Rev No 3 Status F Date 2015-07-31 Cont ID  
Sent By eschneid Date 2015-07-31 Time 11:43 Rev Time 2.00
Received By eschneid Date 2015-07-31 Time 11:43 Sent To  
Notes
2015-07-31 11:56:22FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) PLEASE CLARIFY IF THE RETAINING WALL IS INCLUDED AS
 PART OF THIS PERMIT. THE SITE AND CIVIL PLANS SHOW THE
 MAJORITY OF THE RETAINING WALL AREA AS "NOT INCLUDED".
 THE FOUNDATION PLAN SHOWS MOST OF THE WALL AS INCLUDED.
 PRESUMABLY THE BALANCE OF THE RETAINING WALL WOULD BE
 INCLUDED WITH THE TRADITIONS II PERMIT. WHY SPLIT UP
 THE RETAINING WALL AND NOT BUILD IT UNDER ITS OWN
 PERMIT?
  
 2) THE NEW RETAINING WALL IS SHOWN IN DIFFERENT
 LOCATIONS ON THE PLANS LISTED BELOW. PLEASE EXPLAIN WHY
 DIFFERING WALL LOCATIONS ARE SHOWN.
  
 SHEET L101 COTLEUR & HEARING MASTER PLAN
 SHEET S-1.1 ONM&J FOUNDATION PLAN
 SHEET 1A DUNKELBERGER LAKE BANK RETAINING WALL LOCATION
 PLAN - OVERVIEW (IN THE RETAINING WALL OVERALL
 STABILITY EVALUATION REPORT)
 SHEET 1B DUNKELBERGER RETAINING WALL LOCATION PLAN -
 DETAILED (IN THE RETAINING WALL OVERALL STABILITY
 EVALUATION REPORT)
 SHEET 1C DUNKELBERGER RETAINING WALL LOCATION PLAN -
 DETAILED (IN THE RETAINING WALL OVERALL STABILITY
 EVALUATION REPORT)
  
 3) THE LANDSCAPE PLANS CALL FOR LITTORAL PLANTING TO
 THE WEST OF THE OVERLOOK PORTION OF THE RETAINING WALL.
 PLEASE EXPLAIN HOW THIS WILL OCCUR GIVEN THE DEPTH AND
 SLOPE THAT ARE BEING PROPOSED.
  
 4) THE IRRIGATION AND LANDSCAPING REQUIRE SEPARATE
 PERMIT SUBMITTALS, WITH PLANS. PLEASE NOT RESUBMIT
 THESE SHEETS.
  
 5) THE BUILDING FOOTPRINT MEETS ZONING REQUIREMENTS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  

Review Stop Z ZONING
Rev No 2 Status F Date 2015-04-01 Cont ID  
Sent By eschneid Date 2015-04-01 Time 15:52 Rev Time 2.00
Received By eschneid Date 2015-04-01 Time 15:52 Sent To  
Notes
2015-04-01 15:59:30FAILED
  
 1) THE MINOR PLANNED DEVELOPMENT AMENDMENT FOR THIS
 EXPANSION HAS NOT RECEIVED FINAL APPROVAL FROM THE
 PLANNING DIVISION. THE FOOTPRINT OF THE EXPANSION
 MATCHES THE PLANS CURRENTLY UNDER REVIEW FOR THE MINOR
 AMENDMENT.
  
 2) ZONING CANNOT GRANT FINAL APPROVAL UNTIL THE MINOR
 AMENDMENT IS APPROVED.
  
 3) LANDSCAPE, PARKING, BICYCLE RACKS, ETC. REQUIRE
 SEPARATE PERMIT WITH PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2015-03-19 15:33:523/19/15
2015-03-10 13:55:463/10/15

Review Stop Z ZONING
Rev No 1 Status N Date 2015-01-28 Cont ID  
Sent By eschneid Date 2015-01-28 Time 10:29 Rev Time 0.00
Received By skennedy Date 2015-01-28 Time 10:29 Sent To  
Notes
2015-01-28 10:29:52REVIEW CYCLE STOPPED AS APPLICANT WILL SUBMIT REDESIGN
 FOR FULL BUILDING.