2015-01-12 12:59:15 | 1/12/2015 |
| PROJECT: EARTHLINK |
| PERMIT#: 14120886 |
| CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| 1ST ELECTRICAL PLAN REVIEW |
| ACTION: DENIED |
| |
| 1) FBC- 107.3.5.3. PROVIDE A DETAILED ELECTRICAL |
| SERVICE DISTRIBUTION SYSTEM TO INCLUDE THE FOLLOWING: A |
| RISER DIAGRAM WITH A GROUNDING ELECTRODE SYSTEM, ALL |
| SERVICE DISCONNECTS, AND PANELS, ALL CONDUIT AND WIRE |
| SIZES, A COMPLETE DETAILED LOAD CALCULATION(S), CLEAR |
| AND SPECIFIC PANEL DIRECTORIES, AND ALL CIRCUIT NUMBERS |
| AS INDICATED ON THE PANEL DIRECTORIES TO BE SHOWN ON |
| THE ELECTRICAL FLOOR, AND CELING LIGHTING PLANS. THE |
| RISER DIAGRAM SUBMITTED IS INCOMPLETE.INDICATE AND |
| INCLUDE ON THE REVISED RISER DIAGRAM ALL UTILITY |
| SERVICE ENTRANCE CONDUIT AND WIRE SIZES, MAIN |
| DISCONNECTS, PANELS, FEEDERS, AND GROUNDING ELECTRODE |
| SYSTEM ASSOCIATED WITH THE SUITE UNDER CONSTRUCTION |
| ONLY. INDICATE AND DISDINGUISH BETWEEN WHAT IS EXISTING |
| TO REMAIL, WHAT IS EXISTING TO BE RELOCATED, AND WHAT |
| IS PROPOSED TO BE NEW. WITH THE LOAD CALCULATION |
| INDICATE WHAT IS THE EXISTING LOAD AND WHAT IS PROPOSED |
| TO BE ADDED, AND THE NEW TOTAL CONNECTED LOAD. |
| |
| 2) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| INTERRUPTED. NEC 110.9 |
| |
| 3) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| 110.16, 110.22 |
| |
| 4) PROVIDE THE LOCATION OF THE ELECTRICAL SERVICE AND |
| EACH OF THE ELECTRICAL PANELS. FOR THE PANEL THAT IS |
| BEING RELOCATED, PROVIDE BOTH THE OLD EXISTING LOCATION |
| AND THE NEW RELOACTED LOCATION ON THE ELECTRICAL FLOOR |
| PLAN. |
| |
| SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| ARE REQUIRED FOR SITE LIGHTING, GENERATORS. FIRE ALARM, |
| ACCESS CONTROL SYSTEM, SECURITY, CCTV, NETWORK, DATA, |
| AND, COMMUNICATION AS NEEDED. NOT ALL MAY BE UTILIZED |
| OR RQUIRED ON THIS PROJECT. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. SEE LINK: |
| HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| |
| ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| REVIEW. |
| |
| DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| 561-805-6717 OR [email protected] |
| |