Plan Review Details - Permit 14120864
Plan Review Stops For Permit 14120864
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2015-03-13 Cont ID  
Sent By JWitmer Date 2015-03-13 Time 13:04 Rev Time 0.00
Received By jwitmer Date 2015-03-13 Time   Sent To  
Notes
2015-03-13 13:04:48BUILDING PLAN REVIEW
 PERMIT: 14120864
 ADD: 1101 S FLAGLER DR.
 CONT: HEDRICK BROTHERS
 TEL: (561)689-8880
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 27/ 2014
 ACTION: (N)
  
 1) SHEET A1 REMOVED FROM DOCUMENTS HANDRAIL/ GUARDRAIL
 SYSTEMS ARE NO LONGER PART OF THE PROJECT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-01-27 Cont ID  
Sent By jwitmer Date 2015-01-27 Time 14:06 Rev Time  
Received By jwitmer Date 2015-01-27 Time 13:15 Sent To  
Notes
2015-01-27 14:06:23BUILDING PLAN REVIEW
 PERMIT: 14120864
 ADD: 1101 S FLAGLER DR.
 CONT: HEDRICK BROTHERS
 TEL: (561)689-8880
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 27/ 2014
 ACTION: DENIED
  
 1) SHEET A1 SHOWS A RAMP , GUARDRAIL/ HANDRAIL SYSTEM.
 PLEASE NOTE THE TOP OF THE LANDING IS 14.40' ABOVE
 GRADE, THE BOTTOM OF THE RAMP IS SET AT 11.88' OR A
 DIFFERENCE IN 2.52' IN ELEVATION OR 30 1/4 INCHES IN
 HEIGHT. WHEN A GUARDRAIL IS OVER 30 INCHES TALL, THE
 GUARD RAIL RAIL IS REQUIRED.
 2010 FBC-B 1013.1 WHERE REQUIRED. GUARDS SHALL BE
 LOCATED ALONG OPEN-SIDED WALKING SURFACES, INCLUDING
 MEZZANINES, EQUIPMENT PLATFORMS, STAIRS, RAMPS AND
 LANDINGS THAT ARE LOCATED MORE THAN 30 INCHES (762 MM)
 MEASURED VERTICALLY TO THE FLOOR OR GRADE.
  
 THE ISSUE IS THE REQUIREMENT FOR OPENING LIMITATIONS IN
 A CHANGE IN GRADE GREATER THAN 30 INCHES. SEE 2010
 FBC-B 013.3 OPENING LIMITATIONS.
 REQUIRED GUARDS SHALL NOT HAVE OPENINGS WHICH ALLOW
 PASSAGE OF A SPHERE 4 INCHES (102 MM) IN DIAMETER FROM
 THE WALKING SURFACE TO THE REQUIRED GUARD HEIGHT.
  
 ALSO SHOW COMPLIANCE WITH:
 1607.7.1 HANDRAILS AND GUARDS. HANDRAILS AND GUARDS
 SHALL BE DESIGNED TO RESIST A LOAD OF 50 POUNDS PER
 LINEAR FOOT (PLF) (0.73 KN/M) APPLIED IN ANY DIRECTION
 AT THE TOP AND TO TRANSFER THIS LOAD THROUGH THE
 SUPPORTS TO THE STRUCTURE. GLASS HANDRAIL ASSEMBLIES
 AND GUARDS SHALL ALSO COMPLY WITH SECTION 2407.
  
 1607.7.1.1 CONCENTRATED LOAD. HANDRAILS AND GUARDS
 SHALL BE ABLE TO RESIST A SINGLE CONCENTRATED LOAD OF
 200 POUNDS (0.89 KN), APPLIED IN ANY DIRECTION AT ANY
 POINT ALONG THE TOP, AND TO TRANSFER THIS LOAD THROUGH
 THE SUPPORTS TO THE STRUCTURE. THIS LOAD NEED NOT BE
 ASSUMED TO ACT CONCURRENTLY WITH THE LOADS SPECIFIED IN
 SECTION 1607.7.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2015-03-12 Cont ID  
Sent By RLecky Date 2015-03-12 Time 16:03 Rev Time 0.00
Received By skennedy Date 2015-03-12 Time 16:03 Sent To  
Notes
2015-03-12 16:03:46A SEPARATE SITE LIGHTING PERMIT IS SUBMITTED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-01-13 Cont ID  
Sent By rlecky Date 2015-01-13 Time 12:14 Rev Time 0.00
Received By rlecky Date 2015-01-13 Time 11:53 Sent To  
Notes
2015-01-13 12:15:42 
 14120864
 1101 S. FLAGLER
 SITE LIGHTING ELECTRIC
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE THE SPECIFICATIONS FOR THE LIGHTING POLES AND
 FIXTURES. PROVIDE SIGNED AND SEALED WIND LOADING
 CERTIFICATION FOR THE LIGHT POLE ASSEMBLY WITH FIXTURES
 FROM THE ENGINEER OF RECORD. NEC 110.2, FBC 1609.1,
 ASCE 7-10
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
 [email protected]
  
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2015-04-29 Cont ID  
Sent By Mgonzale Date 2015-04-29 Time   Rev Time 1.00
Received By mgonzale Date 2015-04-29 Time   Sent To I
Notes
2015-04-29 13:57:24APPROVED WITH PROVISOS:
  
 #1 THE WORK WITHIN THE RIGHT-OF-WAYS WILL BE
 REVIEWED/APPROVED UNDER ENGINEERING APPROVAL E15010026.
  
 #2 SIGNING AND MARKING PLAN: PROVIDE ALL WHEEL STOPS
 FOR THE ON-SITE PARKING PER CITY CODE.
 SECTION 94-443(C(5)(B)OF THE CODE OF ORDINANCES AND
 FIGURE XIV-2.
  
 #3 ALL SMALL CAR PARKING SPACES SHALL BE MARKED WITH
 INDIVIDUAL SIGNS STATING "SMALL CARS ONLY." [(CODE OF
 ORD. SECTION 94-485(N)(1)D].

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2015-03-12 Cont ID  
Sent By CRANFORD Date 2015-03-12 Time 15:45 Rev Time 0.00
Received By cranford Date 2015-03-06 Time 08:23 Sent To  
Notes
2015-03-10 13:27:31ENGINEERING DEPT COMMENTS
  
 THE WORK WITHIN THE RIGHT-OF-WAYS WILL BE
 REVIEWED/APPROVED UNDER ENGINEERING APPROVAL E15010026
  
 REGARDING THE SIGNING AND MARKING PLAN:
 1. REVISE THE PLAN TO SHOW ALL WHEEL STOPS FOR THE
 ON-SITE PARKING. SECTION 94-443(C(5)(B)OF THE CODE OF
 ORDINANCES AND FIGURE XIV-2.
 2. ALL SMALL CAR PARKING SPACES SHALL BE MARKED WITH
 INDIVIDUAL SIGNS STATING "SMALL CARS ONLY." [(CODE OF
 ORD. SECTION 94-485(N)(1)D]
  
 CONSTRUCTION DETAILS AND DESIGN CALCULATIONS FOR THE
 SITE GRADING, DRAINAGE, POTABLE WATER, AND SANITARY
 SEWER ARE BEING REVIEWED UNDER ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION E15010026.
  
  
 KELLY CRANFORD, PE
 CITY LAND DEVELOPMENT ENGINEER
 [email protected]
 561-494-1098 (OFFICE)
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2015-02-10 Cont ID  
Sent By cranford Date 2015-02-10 Time 15:01 Rev Time 0.00
Received By cranford Date 2015-02-10 Time 14:46 Sent To  
Notes
2015-02-10 14:49:40THIS IS A CONCEPTUAL LEVEL REVIEW. TECHNICAL DETAILS OF
 THE WATER, SEWER, STORMWATER, TRAFFIC CIRCULATION, AND
 SOLID WASTE COLLECTION ARE BEING REVIEWED AS PART PART
 OF THE ENGINEERING DEVELOPMENT APPROVAL AND BUILDING
 PERMIT APPLICATION PROCESSES (E15010026).
  
 1. PLEASE INCLUDE ONE COPY OF THE LANDSCAPE PLAN
 SHOWING THAT THE CLEAR ZONE AROUND THE FIRE HYDRANTS
 WILL BE MAINTAINED. A WORKING SPACE OF NOT LESS THAN 36
 INCHES IN DIAMETER AND 78 INCHES IN HEIGHT SHALL BE
 PROVIDED AND MAINTAINED AROUND THE CIRCUMFERENCE OF
 FREE-STANDING FIRE DEPARTMENT CONNECTIONS. (FBC SECTION
 912 AND CWPB CODE 94-302)
  
 2. SUBMIT POTABLE WATER DEMAND, SANITARY PEAK FLOW, AND
 YARDAGE CALCULATIONS FOR THE POTABLE WATER, SANITARY
 SEWER, AND SOLID WASTE COLLECTION.
  
 3. PLEASE REVISE THE LANDSCAPE PLAN TO SHOW LOCATIONS
 OF ALL WATER METERS, VALVES, CLEAN-OUTS, DRAINAGE
 FACILITIES, SANITARY LINES ETC. CONSIDER UTILIZING ROOT
 BARRIERS WHERE PLANTINGS ARE NEAR UNDERGROUND
 STORMWATER, SANITARY, OR POTABLE WATER LINES.
  
 4. SUBMIT A FORMAL STRIPING PLAN FOR THE WORK WITHIN
 THE FLAGLER RIGHT-OF-WAY. (SEE CONDITION 2 OF SITE PLAN
 APPROVAL LETTER.) PLAN SHALL INCLUDE LAND DIMENSIONS,
 STRIPING DETAILS, ETC. OVERLAID ON AN AERIAL
 PHOTOGRAPH.
  
 5. PLEASE REVISE THE SIGNING AND MARKING PLAN TO
 INCLUDE THE SIGNAGE MENTIONS IN CONDITION 3B OF THE
 SITE PLAN APPROVAL LETTER.
  
 KELLY CRANFORD, PE
 CITY LAND DEVELOPMENT ENGINEER
 [email protected]
 561-494-1098 (OFFICE)
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-01-06 Cont ID  
Sent By pleduc Date 2015-01-06 Time   Rev Time 0.00
Received By pleduc Date 2015-01-02 Time 12:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-04-29 Cont ID  
Sent By skennedy Date 2015-04-29 Time 15:50 Rev Time 0.00
Received By skennedy Date 2015-04-20 Time   Sent To  
Notes
2015-04-20 16:11:19INCOMING SENT TO ZONING BOX.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-27 Cont ID  
Sent By jroach Date 2015-03-27 Time 14:30 Rev Time 0.00
Received By jroach Date 2015-02-24 Time   Sent To  
Notes
2015-02-24 17:47:11SENT TO C07

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-10 Cont ID  
Sent By cranford Date 2015-02-10 Time 15:02 Rev Time 0.00
Received By cranford Date 2014-12-31 Time 13:32 Sent To  
Notes
2014-12-31 13:33:00C25
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-01-08 Cont ID  
Sent By tklarge Date 2015-01-08 Time 05:38 Rev Time 0.00
Received By tklarge Date 2015-01-08 Time 05:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2015-04-21 Cont ID  
Sent By jroach Date 2015-04-21 Time 14:47 Rev Time 0.00
Received By jroach Date 2015-04-21 Time 14:47 Sent To ENG
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2015-03-27 Cont ID  
Sent By JRoach Date 2015-03-27 Time 14:20 Rev Time 0.00
Received By jroach Date 2015-03-25 Time 16:21 Sent To  
Notes
2015-03-27 14:28:53ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 03.27.2015
 PERMIT NO.: 14120864
 ADDRESS: 1101 S. FLAGLER DRIVE
 CONTRACTOR/CONTACT: JIM KLEEN
 TELEPHONE NO.: 561.310.5150
 SCOPE OF REVIEW: INSTALLATION PAVING AND STRIPING.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ALL APPLICABLE PERMITS SHALL BE OBTAINED FROM THE
 CITY'S ENGINEERING & PUBLIC WORKS DEPARTMENT, INCLUDING
 BUT NOT LIMITED TO A RIGHT-OF-WAY PERMIT. AT THE TIME
 OF APPLICATION SUBMITTAL FOR SUCH PERMITS, A FORMAL
 STRIPING PLAN SHALL BE PROVIDED FOR THE RE-STRIPING OF
 SOUTH FLAGLER DRIVE, AS CONCEPTUALLY SHOWN IN THE
 ABOVE-REFERENCED SITE PLAN. THE STRIPING PLAN SHALL
 INCLUDE LANE DIMENSIONS, STRIPING DETAILS, ETC.
 OVERLAID ON AN AERIAL PHOTOGRAPH.
  
 2. THE PROPERTY SHALL BE REPLATED.
  
 3. SEPARATE PERMIT APPLICATION SHALL BE PROVIDED FOR
 PROPOSED FENCING. DETAILS OF THE FENCING SHALL BE
 INCLUDED.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG

Review Stop Z ZONING
Rev No 1 Status F Date 2015-01-16 Cont ID  
Sent By jroach Date 2015-01-16 Time 10:34 Rev Time 0.00
Received By jroach Date 2015-01-13 Time 16:42 Sent To  
Notes
2015-01-16 10:34:29ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 01.15.2015
 PERMIT NO.: 14120864
 ADDRESS: 1101 S. FLAGLER DRIVE
 CONTRACTOR/CONTACT: RICK RICALTON
 TELEPHONE NO.: 561.689.8880
 SCOPE OF REVIEW: INSTALLATION OF DRAINAGE AND NEW
 PARKING AREAS.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ALL APPLICABLE PERMITS SHALL BE OBTAINED FROM THE
 CITY?S ENGINEERING & PUBLIC WORKS DEPARTMENT, INCLUDING
 BUT NOT LIMITED TO A RIGHT-OF-WAY PERMIT. AT THE TIME
 OF APPLICATION SUBMITTAL FOR SUCH PERMITS, A FORMAL
 STRIPING PLAN SHALL BE PROVIDED FOR THE RE-STRIPING OF
 SOUTH FLAGLER DRIVE, AS CONCEPTUALLY SHOWN IN THE
 ABOVE-REFERENCED SITE PLAN. THE STRIPING PLAN SHALL
 INCLUDE LANE DIMENSIONS, STRIPING DETAILS, ETC.
 OVERLAID ON AN AERIAL PHOTOGRAPH.
  
 2. THE PROPERTY SHALL BE REPLATED.
  
 3. A SITE PLAN SHALL BE PROVIDED AND SHALL INCLUDE A
 PARKING STRIPING DETAIL, A DETAIL OF THE DUMPSTER
 ENCLOSURE, A BIKE RACK DETAIL, ETC.
  
 4. SIGNAGE SHALL BE INSTALLED ALONG THE DRIVEWAY NORTH
 OF THE LEARNING CENTER/DAY CARE INDICATING THAT IT IS A
 FIRE LANE WITH NO PARKING ON BOTH SIDES OF THE ROAD.
 ADDITIONALLY, A SIGN SHALL BE PLACED AT THE EAST END OF
 THE ROADWAY INDICATING ?NARROW ROADWAY AHEAD? WITH THE
 NARROWEST DIMENSION. ALL SIGNAGE SHALL BE DESIGNED AND
 INSTALLED AT THE DISCRETION, AND SUBJECT TO THE
 APPROVAL OF, THE FIRE MARSHALL.
  
 5. SEPARATE PERMIT APPLICATION SHALL BE PROVIDED FOR
 PROPOSED FENCING. DETAILS OF THE FENCING SHALL BE
 INCLUDED.
  
 6. SHOULD A STOP SIGN BE PLACED AT THE PROPOSED STOP
 BAR AT THE NORTHWEST CORNER OF THE CHURCH OFFICE
 BUILDING, AT THE LOCATION OF THE CROSSWALK?
  
 7. SHOULD A NO RIGHT TURN / ONE-WAY SIGN BE INSTALLED
 WHERE THE DAYCARE DROP-OFF PARKING LOT INTERSECTS WITH
 THE ONE-WAY DRIVE ALONG THE NORTH PROPERTY LINE?
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  
2015-01-07 17:14:081/7/15


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved