Plan Review Details - Permit 14120670
Plan Review Stops For Permit 14120670
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-02-17 Cont ID  
Sent By wjolin Date 2015-02-17 Time 12:49 Rev Time 0.00
Received By wjolin Date 2015-02-10 Time 15:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-01-21 Cont ID  
Sent By wjolin Date 2015-01-21 Time 13:08 Rev Time 0.00
Received By wjolin Date 2014-12-19 Time 11:43 Sent To M
Notes
2015-01-08 16:39:55705 NORTH OLIVE AVENUE
 PERMIT #14120670
 MASTER #14030096
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION FOR THE SPRINKLER WORK NEEDS TO
 INCLUDE A JOB VALUE (LABOR AND MATERIALS). KAST
 CONSTRUCTION'S MASTER PERMIT VALUE SHOULD NOT INCLUDE
 SUB-PERMIT VALUES SUCH AS FIRE SPRINKLER, FIRE ALARM,
 ETC.
  
 THE MASTER BUILDING PERMIT PLANS ALREADY ESTABLISH THE
 FIRE PROTECTION ENGINEER OF RECORD; THEREFORE, THE
 SPRINKLER SHOP DRAWINGS SHOULD NOT BE SIGNED AND SEALED
 BY BRIAN MESKOL P.E. UNLESS HE HAS BEEN ASSIGNED TO BE
 A DELEGATED ENGINEER BY THE ENGINEER OF RECORD.
  
 THE 1/16-INCH SCALED DRAWINGS ARE TOO DIFFICULT READ
 AND SCALE.
  
 PROVIDE CEILING/SOFFIT ELEVATIONS ON PLANS SO
 COMPLIANCE WITH OBSTRUCTION RULES CAN BE VERIFIED.
  
 INDICATE THE HANGER TYPE OR METHOD TO BE USED FOR
 RESTRAINING UPWARD MOVEMENT.
  
 FOR THE AREAS EXPOSED TO STRUCTURE (NO CEILING)
 INDICATE IF THE SPACE IS OBSTRUCTED CONSTRUCTION OR
 UNOBSTRUCTED CONSTRUCTION AND INDICATE THE MAXIMUM
 SPRINKLER DISTANCE LOCATED BELOW THE STRUCTURE OR ROOF
 DECK (IF OBSTRUCTED CONSTRUCTION).
  
 SHEET 1 OF 8: THE 6-INCH STANDPIPE FEED MAIN APPEARS TO
 BE ROUTED OUTSIDE OF THE BUILDING ADJACENT TO STAIR #5.
 INDICATE HOW THIS PIPING BE SUPPORTED AND PROTECTED
 FROM MECHANICAL DAMAGE.
  
 SHEET 1 OF 8: CONFIRM CORROSION RESISTANT PIPING AND
 FITTINGS ARE NOT APPROPRIATE FOR THE TRASH ROOMS AND
 PARKING STRUCTURE AREAS.
  
 SHEET 3 OF 8: CONFIRM THE PARKING GARAGE
 CEILING/STRUCTURE DOES NOT EXCEED A SLOPE OF 2 IN 12
 REQUIRING THE HYDRAULIC AREA TO BE INCREASED BY 30%.
  
 SHEET 6 OF 8: CONFIRM THE SPRAY FROM 4 CONTIGUOUS
 SPRINKLERS ON THE SAME 3/4-INCH CPVC BRANCH LINE IN
 UNIT B2 IS NOT MORE HYDRAULICALLY DEMANDING.
  
 SHEET 6 OF 8: PLANS INDICATE A SCALE OF 3/16"=1'-0";
 HOWEVER, THERE ARE NO PLAN DIMENSIONS OR SCALE BAR TO
 ENSURE THE SCALE IS ACCURATE ON THIS PAPER SIZE.
  
 NOTE: METRO SPRINKLER HAS INDICATED THAT THE
 UNDERGROUND FIRE LINE IS NOT IN THEIR SCOPE WORK. A
 SEPARATE PLAN, PERMIT AND CONTRACTOR IS NEEDED.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-17 Cont ID  
Sent By hmoser Date 2015-02-17 Time 13:02 Rev Time 0.00
Received By hmoser Date 2015-01-29 Time 13:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-24 Cont ID  
Sent By hmoser Date 2015-01-24 Time 09:01 Rev Time 0.00
Received By hmoser Date 2014-12-19 Time 11:10 Sent To  
Notes
2014-12-19 11:10:45ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-02-17 Cont ID  
Sent By hmoser Date 2015-02-17 Time 13:02 Rev Time 0.00
Received By hmoser Date 2015-02-17 Time 11:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-01-24 Cont ID  
Sent By hmoser Date 2015-01-24 Time 08:45 Rev Time 0.00
Received By hmoser Date 2015-01-24 Time 08:45 Sent To  
Notes
2015-01-24 09:01:08PLAN DENIED
 1) PROVIDE JOB VALUE ON APPLICATION
 2) NEED A LETTER FROM THE FIRST ENGINEER RELIEVING
 HIMSELF FROM THE JOB. WITH HIS SIGNATURE AND SEAL OR
 STAMP
 ON THE LETTER.
 3) REFER TO SECTION 107.2.1.4 QUALITY OF PLANS. 2010
 FBC
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805=6732
 FAX 561-805-6676
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2015-03-02 Cont ID  
Sent By skennedy Date 2015-03-02 Time 08:56 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***