Plan Review Details - Permit 14120664
Plan Review Stops For Permit 14120664
Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-01-27 Cont ID  
Sent By Mgonzale Date 2015-01-27 Time   Rev Time 1.00
Received By mgonzale Date 2015-01-27 Time   Sent To Z
Notes
2015-01-27 16:37:22NO COMMENTS. (WORK IS PRIVATE)

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-02-24 Cont ID  
Sent By wjolin Date 2015-02-24 Time 12:33 Rev Time 0.00
Received By wjolin Date 2015-02-18 Time 11:41 Sent To M
Notes
2015-02-18 14:23:11600 OKEECHOBEE BOULEVARD
 PERMIT #14120664
 MASTER #14050111
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 VICFLEX SPRINKLER DROPS: PROVIDE HYDRAULIC CALCULATIONS
 SUPPORTING THE USE OF THE FLEXIBLE SPRINKLER DROPS AND
 THE ADDITIONAL FRICTION LOSS ASSOCIATED WITH THESE
 PRODUCTS. PROVIDE A FLEXIBLE DROP DETAIL INDICATING THE
 MAXIMUM NUMBER OF BENDS PERMITTED AND THE MINIMUM BEND
 RADIUS PERMITTED IN THE LISTING DATA. INDICATE THE
 MAXIMUM LENGTH OF FLEXIBLE DROP TO BE USED. WHERE WILL
 THESE DROPS BE USED?
  
 SHEET FP-1: GENERAL FIRE SPRINKLER NOTES #6 & #7
 INDICATE THE USE OF STEEL PIPING; HOWEVER, THERE IS NO
 MENTION OF CPVC PIPING AND SPECIFICALLY WHERE IT WILL
 BE USED.
  
 SHEET FP-1: GENERAL FIRE SPRINKLER NOTE #12 INDICATES
 STANDPIPE VALVES WITH AN 1-1/2" REDUCER AND A REFERENCE
 TO THE CITY OF MIAMI FIRE RESCUE.
  
 SHEET FP-10: PROVIDE HYDRAULIC CALCULATIONS FOR THE
 LOBBY/ATRIUM SPRINKLERS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-01-07 Cont ID  
Sent By wjolin Date 2015-01-07 Time 11:03 Rev Time 0.00
Received By wjolin Date 2014-12-19 Time 12:03 Sent To M
Notes
2014-12-23 15:35:41600 OKEECHOBEE BOULEVARD
 PERMIT #14120664
 MASTER #14050111
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: PLANS INDICATE UNDERGROUND FIRE PROTECTION
 PIPING TO BE INSTALLED BY OTHERS. IS THIS TO BE DONE
 UNDER A SEPARATE PERMIT AND CONTRACTOR OR IS THIS PART
 OF SUMMER'S PERMIT AND SUMMERS IS HIRING A
 SUBCONTRACTOR?
  
 GENERAL: ELIMINATE THE 1-1/2" REDUCER FROM THE 2-1/2"
 HOSE VALVES.
  
 GENERAL: SUBMIT PRODUCT DATA FOR FIRE/JOCKEY PUMP,
 CONTROLLERS, TRANSFER SWITCH, PRESSURE REGULATING
 VALVES, BACKFLOW PREVENTERS, JOINT RESTRAINT
 ASSEMBLIES, PIPE, FITTINGS, HANGERS, ETC.
  
 GENERAL: NORTH ARROWS (ALL SHEETS) APPEAR TO BE
 POINTING IN THE WEST DIRECTION.
  
 SHEET FP-1: CANNOT LOCATE A SECONDARY FIRE DEPARTMENT
 CONNECTION REQUIRED FOR HIG-RISE BUILDINGS.
  
 SHEET FP-1: SPRINKLER NOTE #5 DOES NOT INDICATE WHICH
 ROOMS OR AREAS ARE DESIGNED AS LIGHT OR ORDINARY
 HAZARD. SHEET FP-2 EVEN INDICATES A STORAGE ROOM
 DESIGNATED AS ORDINARY HAZARD GROUP II WITH A DESIGN
 DENSITY OF 0.20 GPM/SF.
  
 SHEET FP-2: CONFIRM FIRE PUMP ROOM IS LARGE ENOUGH FOR
 PROPER INSTALLATION, CONTROLLER CLEARANCES AND WORKING
 SPACE. PROVIDE PLAN VIEW DIMENSIONING EQUIPMENT TO BE
 PROVIDED IN THIS ROOM.
  
 SHEET FP-2: COULD NOT LOCATE SPRINKLERS IN THE BASEMENT
 POOL EQUIPMENT ROOM #B020.
  
 SHEET FP-3: SPRINKLER COVERAGES IN SERVICE CORRIDOR
 APPEAR TO BE FOR LIGHT HAZARD. ORDINARY HAZARD MAY BE
 MORE APPROPRIATE FOR THE EQUIPMENT AND STORAGE
 TYPICALLY GATHERED IN THESE SPACES.
  
 SHEET FP-4: COULD NOT LOCATE SPRINKLER PROTECTION FOR
 HYDRAULIC SERVICE ELEVATOR ADJACENT TO STAIR #4.
  
 SHEET FP-6: VERIFY (WITH LOAD CALCULATIONS) BAR TERRACE
 CANOPY STRUCTURE CAN SUPPORT 5X THE WEIGHT OF
 WATER-FILLED SPRINKLER PIPE.
  
 SHEET FP-8: PUMP ROOM #253 IS LOCATED ON THE SECOND
 FLOOR. THESE SPRINKLERS WILL NEED TO BE SUPPLIED FROM
 THE SECOND FLOOR SYSTEM/FLOW SWITCH TO AVOID CONFUSION
 THINKING THERE IS A FIRE ON THE FIRST FLOOR WHEN IT IS
 ACTUALLY ON THE SECOND.
  
 SHEET FP-9: COULD NOT LOCATE A FIRE DEPARTMENT HOSE
 VALVE IN STAIR #3.
  
 SHEET FP-14: PLANS IN THE CENTRAL ELEVATOR LOBBY
 INDICATE AN 1-1/2" LINE GOING UP TO THE ROOF; HOWEVER,
 THE LINE SIZE INDICATES 1-INCH.
  
 SHEET FP-14: PLANS INDICATE RESIDENTIAL TYPE SPRINKLERS
 TO BE USED IN THE PRES SUITE #1238; HOWEVER, THE
 SCHEDULE INDICATES A QR TYPE SPRINKLER WITH A K-FACTOR
 OF 5.6.
  
 SHEET FP-16: THE FIRE PUMP ROOM SECTION VIEW SHOWS THE
 FIRE PUMP BEING FED FROM BELOW IN LIEU OF OVERHEAD.
 PROVIDE ACCURATE DETAIL ENSURING LAMINAR/NON-TURBULENT
 FLOW INTO THE FIRE PUMP SUCTION FLANGE. PER NFPA 20
 (2007 EDITION) SECTION 5.14.6.3.2, THE DISTANCE OF THE
 FIRE PUMP SUCTION FLANGE AND ANY ADJACENT SUCTION PIPE
 ELBOW/TEE FLANGE SHALL BE SEPARATED BY AT LEAST 10 PIPE
 DIAMETERS WHEN THE ELBOW/TEE HAS A CENTERLINE PLANE
 PARALLEL TO A HORIZONTAL SPLIT-CASE PUMP SHAFT. NOTE:
 THE CODE REQUIREMENTS HAVE NOT CHANGED IN THE LATEST
 EDITION OF THE STANDARD; HOWEVER, DIAGRAMS OF
 CORRECT/INCORRECT SUCTION PIPE INSTALLATIONS HAVE BEEN
 UPDATED IN FIGURE A4.14.6 OF NFPA 20 - 2013 EDITION.
  
 GENERAL: FOR SYSTEM PRESSURES EXCEEDING 100 PSI,
 ARMOVERS AND END OF BRANCH LINE PENDENT SPRINKLERS
 SHALL BE PROTECTED FROM UPWARD MOVEMENT. HANGERS SHALL
 BE LOCATED WITHIN 12-INCHES OF THE DROP ELBOW. INDICATE
 THE HANGER TYPE OR METHOD TO BE USED FOR RESTRAINING
 UPWARD MOVEMENT.
  
 GENERAL: FOR THE AREAS EXPOSED TO STRUCTURE (NO
 CEILING) INDICATE IF THE SPACE IS OBSTRUCTED
 CONSTRUCTION OR UNOBSTRUCTED CONSTRUCTION AND INDICATE
 THE SPRINKLER DISTANCE BELOW THE STRUCTURE OR ROOF DECK
 (IF OBSTRUCTED CONSTRUCTION).
  
 GENERAL: PER NFPA 13 (2007 EDITION) SECTION 24.2.1.2,
 PORTIONS OF SYSTEMS NORMALLY SUBJECTED TO SYSTEM
 WORKING PRESSURES IN EXCESS OF 150 PSI SHALL BE TESTED
 AT A PRESSURE OF 50 PSI ABOVE SYSTEM WORKING PRESSURE
 AND SHALL MAINTAIN THAT PRESSURE WITHOUT LOSS FOR
 2-HOURS.
  
 GENERAL: PROVIDE CHAIN WITH LOCK AND TAMPER SWITCHES
 FOR SUPERVISING THE BACKFLOW PREVENTER IN THE OPEN
 POSITION.
  
 GENERAL: PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT
 CONNECTION.
  
 GENERAL: PROVIDE PERMANENT WEATHERPROOF SIGN MARKING
 THE FIRE DEPARTMENT CONNECTION.
  
 GENERAL: INDICATE THE MAXIMUM SYSTEM WORKING PRESSURE
 ON EACH FLOOR. SPECIFY THE FLOORS THAT WILL HAVE
 PRESSURE REGULATING VAVLES AND THEIR DESIGN SETTINGS.
 RECOMMEND FIELD ADJUSTABLE TYPE VALVES.
  
 PRESSURE REGULATING VALVES: PER NFPA 14 SECTION 7.2.2
 WHEN SYSTEM PRESSURE-REGULATING DEVICES ARE USED IN
 LIEU OF PROVIDING SEPARATE PUMPS, MULTIPLE ZONES SHALL
 BE PERMITTED TO BE SUPPLIED BY A SINGLE PUMP AND
 PRESSURE-REGULATING DEVICE(S) UNDER THE FOLLOWING
 CONDITIONS:
 (1) PRESSURE-REGULATING DEVICE(S) SHALL BE PERMITTED TO
 CONTROL PRESSURE IN THE LOWER ZONE(S).
 (2) A METHOD TO ISOLATE THE PRESSURE-REGULATING
 DEVICE(S) SHALL BE PROVIDED FOR MAINTENANCE AND REPAIR.
 (3) REGULATING DEVICES SHALL BE ARRANGED SO THAT THE
 FAILURE OF ANY SINGLE DEVICE DOES NOT ALLOW PRESSURE IN
 EXCESS OF 175 PSI (12.1 BAR) TO MORE THAN TWO HOSE
 CONNECTIONS.
 (4) AN EQUALLY SIZED BYPASS AROUND THE
 PRESSURE-REGULATING DEVICE(S), WITH A NORMALLY CLOSED
 CONTROL VALVE, SHALL BE INSTALLED.
 (5) PRESSURE-REGULATING DEVICE(S) SHALL BE INSTALLED
 NOT MORE THAN 7 FT 6 IN. (2.31 M) ABOVE THE FLOOR.
 (6) THE PRESSURE-REGULATING DEVICE SHALL BE PROVIDED
 WITH INLET AND OUTLET PRESSURE GAUGES.
 (7) THE FIRE DEPARTMENT CONNECTION(S) SHALL BE
 CONNECTED TO THE SYSTEM SIDE OF THE OUTLET ISOLATION
 VALVE.
 (8) THE PRESSURE-REGULATING DEVICE SHALL BE PROVIDED
 WITH A PRESSURE RELIEF VALVE IN ACCORDANCE WITH THE
 MANUFACTURERS RECOMMENDATIONS.
 (9) REMOTE MONITORING AND SUPERVISION FOR DETECTING
 HIGH PRESSURE FAILURE OF THE PRESSURE-REGULATING DEVICE
 SHALL BE PROVIDED IN ACCORDANCE WITH NFPA 72, NATIONAL
 FIRE ALARM CODE.
  
 DRAIN: PER NFPA 14 SECTION 7.11.1 A PERMANENTLY
 INSTALLED 3 INCH DRAIN RISER WITH 2-1/2 INCH TEE (ON AT
 LEAST EVERY OTHER FLOOR) SHALL BE PROVIDED ADJACENT TO
 EACH STANDPIPE EQUIPPED WITH PRESSURE-REGULATING
 DEVICES TO FACILITATE TESTING OF EACH DEVICE.
  
 JOINT RESTRAINT: PER NFPA 13 & 24, SECTION 10.8.1.1,
 ALL TEES, PLUGS, CAPS, BENDS, REDUCERS, VALVES, AND
 HYDRANT BRANCHES SHALL BE RESTRAINED AGAINST MOVEMENT
 BY USING THRUST BLOCKS OR RESTRAINED JOINT SYSTEMS.
  
 CORROSION RESISTANCE: PER NFPA 13 & 24, SECTION
 10.8.3.5, AFTER INSTALLATION, RODS, NUTS, BOLTS,
 WASHERS, CLAMPS, AND OTHER RESTRAINING DEVICES SHALL BE
 CLEANED AND THOROUGHLY COATED WITH A BITUMINOUS OR
 OTHER ACCEPTABLE CORROSION-RETARDING MATERIAL.
  
 HYDRAULIC CALCULATIONS:
 BASEMENT CALCULATION INDICATES A OH GROUP 1; HOWEVER,
 DRAWINGS AND CALCULATION INDICATE A DESIGN DENSITY OF
 0.20 GPM/SF.
  
 CALCULATIONS INDICATE PRESSURES AVAILABLE AS HIGH AS
 213 PSI? WHERE ARE THE 165 PSI PRVS IN THESE
 CALCULATIONS?
  
 NO CALCULATIONS PERFORMED OR SUBMITTED FOR ROOF LEVEL
 SPRINKLERS.
  
 CALCULATIONS DO NOT NECESSARILY SUPPORT THE MOST
 HYDRAULICALLY DEMANDING PORTION OF THE SYSTEMS
 CALCULATED. FOR EXAMPLE, THE 12TH FLOOR CALCULATION
 SUPPORTS THE USE OF TWO RESIDENTIAL STYLE SPRINKLERS ON
 A 1-INCH PIPE; HOWEVER, PRES SUITE #1238 SHOWS 3
 SPRINKLERS SUPPLIED FROM AN 1-1/4" PIPE WHICH IS NOT
 SUPPORTED BY THE CALCULATIONS. THE BASEMENT LEVEL
 RESTROOM (MENS' B009) IS CERTAINLY LOCATED MORE REMOTE
 AND SUPPLIES 8 SPRINKLERS FROM 2-INCH PIPING WHICH IS
 NOT SUPPORTED BY CALCULATIONS.
  
 PLAN REVIEW HAS BEEN DISCONTINUED AT THIS TIME DUE TO
 TOO MANY COMMENTS. ADDITIONAL PLAN REVIEW COMMENTS MAY
 BE GENERATED WHEN PLANS ARE RESUBMITTED.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-25 Cont ID  
Sent By hmoser Date 2015-02-25 Time 07:37 Rev Time 0.00
Received By hmoser Date 2015-01-30 Time   Sent To  
Notes
2015-01-30 15:34:27SENT TO FIRE BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-14 Cont ID  
Sent By hmoser Date 2015-01-29 Time 12:48 Rev Time 0.00
Received By shill Date 2015-01-14 Time 12:48 Sent To  
Notes
2014-12-19 09:07:38ROUTED TO FIRE

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-02-25 Cont ID  
Sent By hmoser Date 2015-02-25 Time 07:37 Rev Time 0.00
Received By hmoser Date 2015-02-25 Time 07:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-01-14 Cont ID  
Sent By hmoser Date 2015-01-14 Time 12:20 Rev Time 0.00
Received By hmoser Date 2015-01-14 Time 12:20 Sent To ENG
Notes
2015-01-14 12:45:55PLAN DENIED
 REFER TO SECTION 107 FBC PLAN NOT LEGIBLE CAN NOT READ
 SOME OF THE
 PIPE SIZE.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 56+1-808-6676
  