Plan Review Details - Permit 14120585
Plan Review Stops For Permit 14120585
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-01-30 Cont ID  
Sent By shill Date 2015-01-30 Time 17:31 Rev Time 0.00
Received By shill Date 2015-01-30 Time 17:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-18 Cont ID  
Sent By shill Date 2014-12-18 Time 10:04 Rev Time 0.00
Received By shill Date 2014-12-18 Time 10:04 Sent To  
Notes
2014-12-18 10:04:57****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE ENGINEERING FOR THIS STRUCTURAL REPAIR TO A
 COMMERCIAL (ASSEMBLY OCCUPANCY) BUILDING, FS 471, FBC
 1609. ENGINEERING TO INCLUDE WIND DESIGN CRITERIA.
  
 THE PLAN PROVIDED SPECIFIES CONNECTORS WHICH ARE
 EMBEDS, BUT THIS IS AN EXISTING BEAM. WIND DESIGN
 CRITERIA NOT INCLUDED, STUCCO DOES NOT HAVE A BOND
 BREAK, STUCCO THICKNESS NOT SPECIFIED. USE OF A
 CONNECTOR IN A MANNER OTHER THAN TESTED/ENGINEERED IS
 TO BE DESIGNED BY A STRUCTURAL ENGINEER.
  
 2. THERE IS AN EXPIRED PERMIT FOR THIS LOCATION,
 07080695, PLEASE RESOLVE.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-30 Cont ID  
Sent By shill Date 2015-01-30 Time 17:31 Rev Time 0.00
Received By shill Date 2015-01-22 Time 13:22 Sent To  
Notes
2015-01-23 13:22:25SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-18 Cont ID  
Sent By shill Date 2014-12-18 Time 10:07 Rev Time 0.00
Received By shill Date 2014-12-17 Time 11:35 Sent To  
Notes
2014-12-17 11:35:26<5000 BLDG