Plan Review Details - Permit 14120503
Plan Review Stops For Permit 14120503
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-12-19 Cont ID  
Sent By rmcdouga Date 2014-12-19 Time 07:19 Rev Time 0.00
Received By rmcdouga Date 2014-12-19 Time 07:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-16 Cont ID  
Sent By rmcdouga Date 2014-12-16 Time 09:56 Rev Time 0.00
Received By rmcdouga Date 2014-12-16 Time 09:56 Sent To  
Notes
2014-12-16 10:10:39PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) THE MAXIMUM DESIGN PRESSURE FOR THE ROOFING SYSTEM
 SPECIFIED ON PAGE 14 OF NOA NO. 14-0224.03 IS -60 PSF.
 THIS IS NOT ADEQUATE FOR ALL OF THE ROOF AREAS. SUBMIT
 TWO SETS OF SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 ENHANCED ROOF FASTENING AS REQUIRED BY GENERAL
 LIMITATION NUMBER 7 ON PAGE 16 OF THE NOA.