Plan Review Details - Permit 14120454
Plan Review Stops For Permit 14120454
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-07-24 Cont ID  
Sent By rmcdouga Date 2015-07-24 Time 07:48 Rev Time 0.00
Received By rmcdouga Date 2015-07-23 Time 18:32 Sent To  
Notes
2015-07-13 18:55:29NEW DRAWINGS SUBMITTED. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-04-09 Cont ID  
Sent By rmcdouga Date 2015-04-09 Time 14:48 Rev Time 0.00
Received By rmcdouga Date 2015-04-09 Time 12:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-01-14 Cont ID  
Sent By rmcdouga Date 2015-01-14 Time 17:08 Rev Time 0.00
Received By rmcdouga Date 2015-01-13 Time 16:31 Sent To  
Notes
2015-01-14 17:22:42PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) CLEARLY SPECIFY THE COMPLETE SCOPE OF WORK FOR THIS
 PERMIT ON THE PLANS. FBC 107.2.1
  
 2) FBC 107.3.4.1 PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE WINDOW, STRUCTURAL MULLION
 AND DOOR NOAS OR FL PRODUCT APPROVALS THAT HAVE BEEN
 REVIEWED AND APPROVED IN WRITING BY THE ENGINEER.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-04-09 Cont ID  
Sent By rmcdouga Date 2015-04-09 Time 11:53 Rev Time 0.00
Received By rmcdouga Date 2015-04-09 Time 11:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-01-14 Cont ID  
Sent By rmcdouga Date 2015-01-14 Time 17:04 Rev Time 0.00
Received By rmcdouga Date 2015-01-14 Time 17:04 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2015-07-24 Cont ID  
Sent By fmittner Date 2015-07-24 Time 10:07 Rev Time 0.00
Received By fmittner Date 2015-07-24 Time 10:07 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2015-04-06 Cont ID  
Sent By fmittner Date 2015-04-06 Time 16:22 Rev Time 0.00
Received By fmittner Date 2015-04-06 Time 16:22 Sent To  
Notes
2015-04-06 16:23:20STILL HAVE NOT ADDRESSED COMMENTS FROM FIRST REVIEW.
 WINDOWS SHALL ALL BE SAME DESIGN EITHER 1/1 OR 6/1.
 FIREPLACE SHALL NOT BE REMOVED. QUESTIONS CONTACT
 FRIEDERIKE MITTNER AT 822-1457. SENT TO BLDG.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2014-12-11 Cont ID  
Sent By fmittner Date 2014-12-11 Time 16:08 Rev Time 0.00
Received By fmittner Date 2014-12-11 Time 16:08 Sent To  
Notes
2014-12-11 16:09:15REQUIRES SUBMITTAL OF A COA TO REVIEW MODIFICATIONS.
 WINDOWS SHALL ALL BE SAME DESIGN EITHER 1/1 OR 6/1.
 FIREPLACE SHALL NOT BE REMOVED. QUESTIONS CONTACT
 FRIEDERIKE MITTNER AT 822-1457. SENT TO BLDG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-27 Cont ID  
Sent By rmcdouga Date 2015-07-27 Time 07:08 Rev Time 0.00
Received By rmcdouga Date 2015-06-29 Time 18:51 Sent To  
Notes
2015-07-13 18:52:31RE-SUBMITTAL SENT TO R25 SHELF FOR REVIEW. JG.
  
 NOTE:
 6/29/15 RESUBMITTAL INFORMATION WAS ORIGINALLY ROUTED
 USING PERMIT 15030974 WHICH WAS THE NUMBER THE
 CONTRACTOR REFERENCED ON THE RE-SUBMITTAL FORM. (THIS
 PERMIT NUMBER IS FOR THE REAR STRUCTURE. THERE ARE TWO
 DIFFERENT PERMIT APPLICATIONS) JG.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-09 Cont ID  
Sent By rmcdouga Date 2015-04-09 Time 14:48 Rev Time 0.00
Received By rmcdouga Date 2015-03-23 Time   Sent To  
Notes
2015-04-08 10:35:054/8 RETURNED FROM HISTORIC; ROUTED TO RM DESK (SH)
  
  
2015-03-24 09:56:57INCOMING SENT TO HISTORICS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-14 Cont ID  
Sent By rmcdouga Date 2015-01-14 Time 17:08 Rev Time 0.00
Received By rmcdouga Date 2014-12-15 Time 18:40 Sent To  
Notes
2014-12-15 18:43:44R04

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-07-23 Cont ID  
Sent By rmcdouga Date 2015-07-23 Time 18:13 Rev Time 0.00
Received By rmcdouga Date 2015-07-23 Time 17:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-04-09 Cont ID  
Sent By rmcdouga Date 2015-04-09 Time 14:48 Rev Time 0.00
Received By rmcdouga Date 2015-04-09 Time 12:09 Sent To  
Notes
2015-04-09 14:48:18PLAN REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 MECHANICAL DENIED
  
 1) THE 9" RETURN AIR TRANSFER DUCT FOR THE MASTER
 BEDROOM SUITE ON THE FIRST FLOOR IS UNDERSIZED.
 FBC R1602.4 BALANCED RETURN AIR.
 RESTRICTED RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS
 ARE LOCATED IN CENTRAL ZONES AND CLOSED INTERIOR DOORS
 IMPEDE AIR FLOW TO THE RETURN GRILL OR WHEN CEILING
 SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS
 RESTRICT AIR MOVEMENT FROM ONE PORTION OF THE RETURN
 PLENUM TO ANOTHER. PROVISIONS SHALL BE MADE IN BOTH
 RESIDENTIAL AND COMMERCIAL BUILDINGS TO AVOID
 UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS CAUSED
 BY RESTRICTED RETURN AIR. PRESSURE DIFFERENTIALS ACROSS
 CLOSED DOORS WHERE RETURNS ARE CENTRALLY LOCATED SHALL
 BE LIMITED TO 0.01 INCH WC (2.5 PASCALS) OR LESS.
 PRESSURE DIFFERENTIALS ACROSS FIRE WALLS IN CEILING
 SPACE PLENUMS SHALL BE LIMITED TO 0.01 INCH WC (2.5
 PASCALS) BY PROVIDING AIR DUCT PATHWAYS OR AIR TRANSFER
 PATHWAYS FROM THE HIGH PRESSURE ZONE TO THE LOW ZONE.
 EXCEPTIONS:
 1. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR
 SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCH UNDERCUT TO ACHIEVE PROPER RETURN
 AIR BALANCE.
 2. TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1 INCH UNDERCUTTING OF DOORS TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 3. HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE
 REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS,
 EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL
 BE INCLUDED.
  
 2) THE WINDSPEED IS INCORRECTLY SPECIFIED AS 140 MPH ON
 SHEET M-1. FBC-R 301.2.1
  
 3) THE NUMBER OF BEDROOMS ARE INCORRECTLY LISTED AS (4)
 ON THE ENERGY CALCULATION FORM. THE PLANS SPECIFY A
 TOTAL OF (5). FOUR (4) BEDROOMS ARE LOCATED ON THE
 SECOND FLOOR AND ONE (1) THE MASTER BEDROOM ON THE
 FIRST FLOOR FOR A TOTAL OF (5). THE OWNER/AGENT IS
 REQUIRED TO SIGN THE ENERGY CALC. FORM. FBC ENERGY
 CONSERVATION, FBC 107.1 AND FBC 107.2.1
  
 4) SPECIFY THE SIZE OF THE SUPPLY DUCT TO THE 10 X 10
 GRILL IN THE LIVING ROOM. FBC 107.2.1
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-01-13 Cont ID  
Sent By rmcdouga Date 2015-01-13 Time 15:45 Rev Time 0.00
Received By rmcdouga Date 2015-01-13 Time 15:45 Sent To  
Notes
2015-01-13 16:31:42PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 MECHANICAL DENIED
  
 1) THE 2ND FLOOR MECHANICAL PLAN DOES NOT MATCH THE
 ARCHITECTURAL PLANS. FBC 107.2.1
  
 2) THERE IS NO RETURN SHOWN FOR THE MASTER BEDROOM
 SUITE ON THE FIRST FLOOR. FBC R1602.4
  
 3) THE WINDSPEED IS INCORRECTLY SPECIFIED AS 140 MPH ON
 SHEET M-1. FBC-R 301.2.1
  
 4) THERE ARE SEVERAL ERRORS ON THE ENERGY CALCULATION
 FORM. BASED ON THE PLANS SUBMITTED, THIS IS A SINGLE
 FAMILY DWELLING. THERE ARE NO COMMON WALLS. THE
 OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY CALC. FORM.
 TWO SETS OF ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS ARE REQUIRED. FBC ENERGY CONSERVATION, FBC
 107.1 AND FBC 107.2.1
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-07-23 Cont ID  
Sent By rmcdouga Date 2015-07-23 Time 18:35 Rev Time 0.00
Received By rmcdouga Date 2015-07-23 Time 18:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-12-20 Cont ID  
Sent By tklarge Date 2014-12-20 Time 09:13 Rev Time 0.00
Received By tklarge Date 2014-12-20 Time 08:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-12-11 Cont ID  
Sent By fmittner Date 2014-12-11 Time 16:09 Rev Time 0.00
Received By fmittner Date 2014-12-11 Time 16:09 Sent To B
Notes
***NONE***