Plan Review Details - Permit 14120384
Plan Review Stops For Permit 14120384
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-02-24 Cont ID  
Sent By shill Date 2016-02-24 Time 17:08 Rev Time 0.00
Received By shill Date 2016-02-24 Time 17:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-12 Cont ID  
Sent By shill Date 2014-12-12 Time 07:46 Rev Time 0.00
Received By shill Date 2014-12-12 Time 07:46 Sent To  
Notes
2014-12-12 10:04:22****CORRECTIONS****
 ****LOFTIN PLACE 6TH LEVEL POST TENSION ENGINEERING****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. THERE IS A COVER SHEET FOR "PT CALCULATIONS FOR
 GRAVITY LOADS", BUT NO CALCULATIONS WERE SUBMITTED.
 CALCULATIONS TO BE IN ACCORDANCE WITH FAC61G15-23.
 SIGNATURE/SEAL ARE COPIES AND TITLE BLOCK IS LACKING.
  
 2. DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS
 FS471 (PTE TENDON AND REINFORCEMENT PLANS).
 ADDITIONALLY, THERE SHOULD BE A TITLE BLOCK FOR THE
 ENGINEER SEALING THE PLAN. IF THE ENGINEER IS WORKING
 THROUGH A COMPANY, THAT COMPANY NAME AND CERTIFICATE OF
 AUTHORIZATION NUMBER ARE TO BE IN THE TITLE BLOCK. THE
 SEAL IS TO COMPLY WITH FAC61G15-23.
  
 TITLE BLOCK IS LACKING (UNLESS THE TITLE BLOCK IS "PTE
 SYSTEMS INT'L LLC, IN WHICH CASE THERE SHOULD BE A
 CERTIFICATE OF AUTHORIZATION), SEAL IS REDUCED AND
 ILLEGIBLE, SIGNATURE IS A PHOTOCOPY.
  
 IF CONTRACTOR AND ENGINEER WOULD LIKE TO PROVIDE
 SUBMITTALS DIGITALLY, PLEASE CONTACT [email protected].
  
 2. THE REVIEW LETTER FROM BBM IS NOT SIGNED, FAC
 61G15-30.005.
  
 3. PLANS SHOW A ROUND RED MARK WITHOUT A CORRESPONDING
 NOTE OR LEGEND. FBC 107, PLEASE CLARIFY.
  
 **ADDED 2/2/16**
 THE SHOP DRAWING REVIEW STAMP FOR BBM STRUCTURAL
 ENGINEERS ON THE COVER LETTER IS LEGIBLE, BUT IT IS NOT
 CLEAR WHICH ENGINEER REVIEWED THE DELEGATED
 ENGINEERING. THE INITIALS ARE "HW"; PLEASE REVISE TO
 INCLUDE THE NAME AND PROFESSIONAL ENGINEER NUMBER. THE
 LETTER IS FOR THE PT CALCULATIONS, BUT CALCULATIONS
 WERE NOT SUBMITTED. EITHER THE SHOP DRAWING REVIEW
 STAMP ON THE PLANS SHOULD BE MADE LEGIBLE, WITH THE
 INDIVIDUAL PERFORMING THE REVIEW CLEAR, OR THE REVIEW
 LETTER SHOULD BE REVISED TO INCLUDE THE PLANS.
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-24 Cont ID  
Sent By shill Date 2016-02-24 Time 17:08 Rev Time 0.00
Received By shill Date 2016-02-22 Time 15:03 Sent To  
Notes
2016-02-22 15:03:15SHILL'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-12 Cont ID  
Sent By shill Date 2014-12-12 Time 10:04 Rev Time 0.00
Received By shill Date 2014-12-10 Time 16:15 Sent To  
Notes
2014-12-10 16:15:37INCOMING SENT TO S. HILLS DESK.