Plan Review Details - Permit 14120369
Plan Review Stops For Permit 14120369
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-04-16 Cont ID  
Sent By skennedy Date 2015-04-16 Time 14:44 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-02-03 Cont ID  
Sent By jwitmer Date 2015-02-03 Time 17:30 Rev Time 0.00
Received By jwitmer Date 2015-02-03 Time 16:54 Sent To  
Notes
2015-02-03 17:30:40BUILDING PLAN REVIEW
 PERMIT: 14120369
 ADD: 101 N. CLEMATIS ST.
 CONT: TBD
 TEL: (305)606-0567
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. FEB. 03/ 2015
 ACTION: DENIED
  
 1)COMPLIED.
  
 2) 2ND REQUEST SUBMITTED FLOOR INSULATION FOR GENIEMAT
 TESTED TO ASTM E2179 THE WRONG STANDARD, PLEASE PROVIDE
 COMPLIANCE WITH THE (2) REQUIREMENTS LISTED BELOW:
  
 2A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2010 603.2 EXCEPTION (2) TILE FLOORING.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-17 Cont ID  
Sent By jwitmer Date 2014-12-17 Time 14:18 Rev Time 0.00
Received By jwitmer Date 2014-12-17 Time 14:10 Sent To  
Notes
2014-12-17 14:18:55BUILDING PLAN REVIEW
 PERMIT: 14120369
 ADD: 101 N. CLEMATIS ST.
 CONT: TBD
 TEL: (305)606-0567
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. DEC. 16/ 2014
 ACTION: DENIED
  
 1) THE ARCHITECTURAL SHEETS ARE SIGNED INBOTH SETS OF
 PLANS BUT NOT SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G16.003 ARCHITECTS.
  
 2) IT APPEARS THAT THE BATHROOM WILL HAVE A NEW TILED
 FLOOR, PLEASE PROVIDE COMPLIANCE WITH THE 2010 FBC-B:
  
 2A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2010 603.2 EXCEPTION (2) TILE FLOORING
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-10 Cont ID  
Sent By sciard Date 2015-03-10 Time 14:00 Rev Time 0.00
Received By sciard Date 2015-03-10 Time 14:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-01-12 Cont ID  
Sent By sciard Date 2015-01-12 Time 14:24 Rev Time 0.00
Received By sciard Date 2015-01-12 Time 14:24 Sent To  
Notes
2015-01-12 14:45:381. FBC 107.3.5.3. PROVIDE LOAD CALCULATION A ND PANEL
 SCHEDULE FOR RELOCATED PANEL WITH ADDITION OF TANKLESS
 WATER HEATER.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-12-16 Cont ID  
Sent By pleduc Date 2014-12-16 Time   Rev Time 0.00
Received By pleduc Date 2014-12-16 Time 12:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-03-10 Cont ID  
Sent By sciard Date 2015-03-10 Time 14:00 Rev Time 0.00
Received By sciard Date 2015-01-29 Time 07:24 Sent To  
Notes
2015-01-31 07:24:38B23

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-14 Cont ID  
Sent By hmoser Date 2015-01-14 Time 14:23 Rev Time 0.00
Received By hmoser Date 2015-01-07 Time 07:05 Sent To  
Notes
2015-01-08 07:08:01RESUBMITTAL WAS PUT IN WITH ORIGINAL PLANS THAT HAD NOT
 COMPLETED THE REVIEW CYCLE. MECHANICAL AND ELECTRICAL
 REVIEWS WERE NOT COMPLETED AT THIS TIME.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-14 Cont ID  
Sent By hmoser Date 2015-01-14 Time 14:22 Rev Time  
Received By hmoser Date 2014-12-09 Time   Sent To  
Notes
2014-12-10 15:57:34INCOMING SENT TO B23.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-01-14 Cont ID  
Sent By hmoser Date 2015-01-14 Time 14:22 Rev Time 0.00
Received By hmoser Date 2015-01-14 Time 14:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-12-20 Cont ID  
Sent By tklarge Date 2014-12-20 Time 08:52 Rev Time 0.00
Received By tklarge Date 2014-12-20 Time 08:32 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-12-22 Cont ID  
Sent By aaponte Date 2014-12-22 Time 15:32 Rev Time 0.00
Received By aaponte Date 2014-12-22 Time 15:32 Sent To  
Notes
2014-12-11 10:37:2412/11/14


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved