Plan Review Details - Permit 14120265
Plan Review Stops For Permit 14120265
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-02-03 Cont ID  
Sent By jwitmer Date 2015-02-03 Time 12:28 Rev Time 0.00
Received By jwitmer Date 2015-02-03 Time 12:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-22 Cont ID  
Sent By jwitmer Date 2014-12-22 Time 16:43 Rev Time 0.00
Received By jwitmer Date 2014-12-22 Time 15:55 Sent To  
Notes
2014-12-22 16:43:23BUILDING PLAN REVIEW
 PERMIT: 14120265
 ADD: 205 DATURA ST.
 CONT: SMITHCO WPB INC.
 TEL: (561)633-3793
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. DEC. 22/2014
 ACTION: DENIED
  
 1) SHEET H02.01 INDICATES AN ALTERNATE LOCATION FOR THE
 ACCU-1, ACCU-2 & ACCU-3 UNITS IN THE ALLEY WAY. THERE
 ARE (2) ISSUES;
  
 1A) SUCH DRAWINGS AND SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC, AND THE TECHNICAL CODES SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR SHALL THE TERM "LEGAL"
 OR ITS EQUIVALENT OR ALTERNATE BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. (SEE ALSO SECTION 107.3.5).
  
 1B) IF THE DESIGNER DOES DECIDE TO PLACE THE ACCU UNITS
 IN THE ALLEY WAY PLEASE PROVIDE WHERE THE PROPERTY LINE
 IS LOCATED AND AT WHATIS THE DISTANCE FROM GRADE TO THE
 BOTTOM OF THE FRAMEWORK OF THE UNIT. PLEASE SHOW CODE
 COMPLIANCE WITH THE 2010 FBC-B 3202.3.2 WINDOWS,
 BALCONIES, ARCHITECTURAL FEATURES AND MECHANICAL
 EQUIPMENT. WHERE THE VERTICAL CLEARANCE ABOVE GRADE TO
 PROJECTING WINDOWS, BALCONIES, ARCHITECTURAL FEATURES
 OR MECHANICAL EQUIPMENT IS MORE THAN 8 FEET (2438 MM),
 1 INCH (25 MM) OF ENCROACHMENT IS PERMITTED FOR EACH
 ADDITIONAL 1 INCH OF CLEARANCE ABOVE 8 FEET, BUT THE
 MAXIMUM ENCROACHMENT SHALL BE 4 FEET.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-01-14 Cont ID  
Sent By sciard Date 2015-01-14 Time 14:16 Rev Time 0.00
Received By sciard Date 2015-01-14 Time 14:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-01-29 Cont ID  
Sent By pleduc Date 2015-01-29 Time   Rev Time 0.00
Received By pleduc Date 2015-01-29 Time 13:03 Sent To  
Notes
2015-01-29 13:13:24THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PROVISO:
  
 VENT PIPE APPEARS TO BREECH THE GENERATOR ROOM RATED
 WALL. CONFIRM THAT THE WALL IS RATED WHICH REQUIRES A
 FIRE DAMPER. ADDITIONALLY, PROVIDE A U.L. RATING
 LISTING TO PROTECT THE AREA AROUND THE VENT ON EACH
 SISE OF THE WALL.
  
 SEPARATE SHOP DRAWING ARE REQUIRED FOR THE PRE-ACTION
 SYSTEM.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-12-10 Cont ID  
Sent By pleduc Date 2014-12-10 Time   Rev Time 0.00
Received By pleduc Date 2014-12-10 Time 15:40 Sent To  
Notes
2014-12-10 16:19:17THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PROVISO:
  
 VENT PIPE APPEARS TO BREECH THE GENERATOR ROOM RATED
 WALL. CONFIRM THAT THE WALL IS RATED WHICH REQUIRES A
 FIRE DAMPER. ADDITIONALLY, PROVIDE A U.L. RATING
 LISTING TO PROTECT THE AREA AROUND THE VENT ON EACH
 SISE OF THE WALL.
  
 SEPARATE SHOP DRAWING ARE REQUIRED FOR THE PRE-ACTION
 SYSTEM.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-03 Cont ID  
Sent By jwitmer Date 2015-02-03 Time 12:28 Rev Time 0.00
Received By jwitmer Date 2015-01-28 Time 09:02 Sent To  
Notes
2015-01-28 09:04:13C20

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-20 Cont ID  
Sent By hmoser Date 2015-01-20 Time 15:37 Rev Time 0.00
Received By hmoser Date 2014-12-08 Time 07:56 Sent To  
Notes
2014-12-09 07:59:08C20

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-02-03 Cont ID  
Sent By hmoser Date 2015-02-03 Time 12:28 Rev Time 0.00
Received By jwitmer Date 2015-02-03 Time 12:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-01-20 Cont ID  
Sent By hmoser Date 2015-01-20 Time 15:36 Rev Time 0.00
Received By hmoser Date 2015-01-20 Time 15:22 Sent To  
Notes
2015-01-20 15:36:41PLAN DENIED
 1) MISSING FIRE DAMPER IN 10X6 DUCT AT GENERATOR
 ROOM PER SECTION 607.5.1 FIRE WALLS 2010 FBC (M)
 2) SEPARATE APPLICATION,PLAN AND PERMIT REQUIRED FOR
 FIRE SUPPRESSION SYSTEM
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676