Plan Review Stops For Permit 14120246 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2015-02-27 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2015-02-27 |
Time |
06:59 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2015-02-27 |
Time |
06:45 |
Sent To |
|
|
Notes |
2015-02-25 17:13:37 | NEW DRAWINGS SUBMITTED. JG. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2014-12-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-12-12 |
Time |
07:00 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-12-12 |
Time |
06:22 |
Sent To |
|
|
Notes |
2014-12-11 16:43:50 | BUILDING PROVISO: | | 3RD FLOOR WORK OVER 50 % OF LEASEABLE FLOOR AREA OF | | FLOOR PLATE WILL NEED TO SHOW CODE | | COMPLIANCE WITH 2010 FL EXISTING BLDG CODE 703.2.2 . | | 703.2.2 SUPPLEMENTAL SHAFT AND FLOOR OPENING ENCLOSURE | | REQUIREMENTS. | | WHERE THE WORK AREA ON ANY FLOOR EXCEEDS 50 PERCENT OF | | THAT FLOOR AREA, THE ENCLOSURE | | REQUIREMENTS OF SECTION 703.2 SHALL APPLY TO VERTICAL | | OPENINGS OTHER THAN STAIRWAYS THROUGHOUT THE FLOOR. | | 2010 FBC-B 708.14.1 ELEVATOR LOBBIES OR EXCEPTIONS. | | EXCEPION #6 | | ENCLOSED ELEVATOR LOBBIES ARE NOT REQUIRED WHERE THE | | ELEVATOR HOISTWAY IS PRESSURIZED IN ACCORDANCE WITH | | SECTION 708.14.2. | | | | NOTE: PERMIT # 14090238 IS FOR THE PRESSURIZATION OF | | ELEVATOR SHAFTS. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2015-03-19 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-03-19 |
Time |
12:05 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-03-19 |
Time |
12:05 |
Sent To |
|
|
Notes |
2015-02-25 17:14:57 | NEW DRAWINGS SUBMITTED. JG. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2015-02-11 |
|
|
Cont ID |
|
Sent By |
DHAYES |
Date |
2015-02-11 |
Time |
16:06 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-02-11 |
Time |
15:47 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2015-01-07 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-01-07 |
Time |
15:38 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-01-07 |
Time |
13:59 |
Sent To |
|
|
Notes |
2015-01-07 14:40:31 | 1/7/2015 | | PROJECT: #RD FL SPEC SUITE | | PERMIT#: 14120246 | | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC | | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | 1ST ELECTRICAL PLAN REVIEW | | ACTION: DENIED | | | | 1) INDICATE ON THE PLAN THE RELOCATION OF RADIENT HEAT | | PANELS CIRCUITRY AS WELL AS THE REQUIRED CIRCUITRY AND | | DISCONNECTS FOR THE INSTALLATION OF VAV BOXES SHOWN ON | | MECHANICAL PLANS. | | | | 2) PROVIDE REVISED ELECTRICAL CIRCUIT DIRECTORY TO | | IDENTIFY ANY MODIFICATION OF EXISTING CIRCUITRY AND | | ADDITION OF ANY NEW CIRCUITRY REQUIRED FOR INSTALLATION | | OF NEW EQUIPMENT. EVERY CIRCUIT AND CIRCUIT | | MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS | | CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4 | | | | 3) PROVIDE A LOAD CALCULATION TO TAKE INTO | | CONSIDERATION THE ADDITION OR INSTALLATION OF ANY NEW | | CIRCUITRY. NEC 220 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. SEE LINK: | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED | | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE | | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE | | REVIEW. | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | 561-805-6717 OR [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2015-03-09 |
|
|
Cont ID |
|
Sent By |
scaldero |
Date |
2015-03-09 |
Time |
11:25 |
Rev Time |
0.00 |
Received By |
scaldero |
Date |
2015-03-09 |
Time |
11:25 |
Sent To |
|
|
Notes |
2015-02-25 17:14:03 | NEW DRAWINGS SUBMITTED. JG. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2014-12-09 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2014-12-09 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2014-12-09 |
Time |
10:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2015-03-19 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-03-19 |
Time |
12:05 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-02-24 |
Time |
17:18 |
Sent To |
|
|
Notes |
2015-02-25 17:18:29 | RE-SUBMITTAL SENT TO B21 BIN FOR REVIEW. JG. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-02-11 |
|
|
Cont ID |
|
Sent By |
dhayes |
Date |
2015-02-11 |
Time |
16:06 |
Rev Time |
0.00 |
Received By |
dhayes |
Date |
2015-02-05 |
Time |
18:45 |
Sent To |
|
|
Notes |
2015-02-05 18:46:05 | SENT TO H MOSER |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-01-27 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2015-01-27 |
Time |
13:13 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2014-12-08 |
Time |
18:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
IMPACT |
COUNTY IMPACT FEES |
Rev No |
1 |
Status |
N |
Date |
2014-12-12 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2014-12-12 |
Time |
07:00 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2014-12-12 |
Time |
07:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2015-03-19 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2015-03-19 |
Time |
12:05 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2015-03-19 |
Time |
12:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2015-02-06 |
|
|
Cont ID |
|
Sent By |
HMOSER |
Date |
2015-02-06 |
Time |
14:02 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2015-02-06 |
Time |
14:02 |
Sent To |
E |
|
Notes |
2015-02-06 14:10:34 | PLAN FAIL | | SAME AS LAST REVIEW REFER TO SECTION 607.5.1 | | 2010 FBC (M) | | PLAN REVIEW BY HAROLD MOSER | | OFFICE 561-805-6732 | | FAX 561-805-6676 | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2015-01-27 |
|
|
Cont ID |
|
Sent By |
hmoser |
Date |
2015-01-27 |
Time |
13:13 |
Rev Time |
0.00 |
Received By |
hmoser |
Date |
2015-01-27 |
Time |
10:42 |
Sent To |
|
|
Notes |
2015-01-27 13:13:09 | PLAN DENIED | | VAV #1 AND #2 SHOW DUCT GOING INTO ELEVATOR LOBBY. | | FIRE DAMPERS REQUIRED PER SECTION 607.5 WHERE REQUIRED | | 2010 FBC (M) | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
P |
Date |
2014-12-20 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2014-12-20 |
Time |
03:21 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2014-12-20 |
Time |
03:07 |
Sent To |
|
|
Notes |
|
|