Plan Review Details - Permit 14120246
Plan Review Stops For Permit 14120246
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-02-27 Cont ID  
Sent By jwitmer Date 2015-02-27 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2015-02-27 Time 06:45 Sent To  
Notes
2015-02-25 17:13:37NEW DRAWINGS SUBMITTED. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2014-12-12 Cont ID  
Sent By jwitmer Date 2014-12-12 Time 07:00 Rev Time 0.00
Received By jwitmer Date 2014-12-12 Time 06:22 Sent To  
Notes
2014-12-11 16:43:50BUILDING PROVISO:
 3RD FLOOR WORK OVER 50 % OF LEASEABLE FLOOR AREA OF
 FLOOR PLATE WILL NEED TO SHOW CODE
 COMPLIANCE WITH 2010 FL EXISTING BLDG CODE 703.2.2 .
 703.2.2 SUPPLEMENTAL SHAFT AND FLOOR OPENING ENCLOSURE
 REQUIREMENTS.
 WHERE THE WORK AREA ON ANY FLOOR EXCEEDS 50 PERCENT OF
 THAT FLOOR AREA, THE ENCLOSURE
 REQUIREMENTS OF SECTION 703.2 SHALL APPLY TO VERTICAL
 OPENINGS OTHER THAN STAIRWAYS THROUGHOUT THE FLOOR.
 2010 FBC-B 708.14.1 ELEVATOR LOBBIES OR EXCEPTIONS.
 EXCEPION #6
 ENCLOSED ELEVATOR LOBBIES ARE NOT REQUIRED WHERE THE
 ELEVATOR HOISTWAY IS PRESSURIZED IN ACCORDANCE WITH
 SECTION 708.14.2.
  
 NOTE: PERMIT # 14090238 IS FOR THE PRESSURIZATION OF
 ELEVATOR SHAFTS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-03-19 Cont ID  
Sent By skennedy Date 2015-03-19 Time 12:05 Rev Time 0.00
Received By skennedy Date 2015-03-19 Time 12:05 Sent To  
Notes
2015-02-25 17:14:57NEW DRAWINGS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-02-11 Cont ID  
Sent By DHAYES Date 2015-02-11 Time 16:06 Rev Time 0.00
Received By dhayes Date 2015-02-11 Time 15:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-01-07 Cont ID  
Sent By dhayes Date 2015-01-07 Time 15:38 Rev Time 0.00
Received By dhayes Date 2015-01-07 Time 13:59 Sent To  
Notes
2015-01-07 14:40:311/7/2015
 PROJECT: #RD FL SPEC SUITE
 PERMIT#: 14120246
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) INDICATE ON THE PLAN THE RELOCATION OF RADIENT HEAT
 PANELS CIRCUITRY AS WELL AS THE REQUIRED CIRCUITRY AND
 DISCONNECTS FOR THE INSTALLATION OF VAV BOXES SHOWN ON
 MECHANICAL PLANS.
  
 2) PROVIDE REVISED ELECTRICAL CIRCUIT DIRECTORY TO
 IDENTIFY ANY MODIFICATION OF EXISTING CIRCUITRY AND
 ADDITION OF ANY NEW CIRCUITRY REQUIRED FOR INSTALLATION
 OF NEW EQUIPMENT. EVERY CIRCUIT AND CIRCUIT
 MODIFICATION SHALL BE LEGIBLY IDENTIFIED AS TO ITS
 CLEAR, EVIDENT, AND SPECIFIC PURPOSE OR USE. NEC 408.4
  
 3) PROVIDE A LOAD CALCULATION TO TAKE INTO
 CONSIDERATION THE ADDITION OR INSTALLATION OF ANY NEW
 CIRCUITRY. NEC 220
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-03-09 Cont ID  
Sent By scaldero Date 2015-03-09 Time 11:25 Rev Time 0.00
Received By scaldero Date 2015-03-09 Time 11:25 Sent To  
Notes
2015-02-25 17:14:03NEW DRAWINGS SUBMITTED. JG.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-12-09 Cont ID  
Sent By pleduc Date 2014-12-09 Time   Rev Time 0.00
Received By pleduc Date 2014-12-09 Time 10:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-03-19 Cont ID  
Sent By skennedy Date 2015-03-19 Time 12:05 Rev Time 0.00
Received By skennedy Date 2015-02-24 Time 17:18 Sent To  
Notes
2015-02-25 17:18:29RE-SUBMITTAL SENT TO B21 BIN FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-02-11 Cont ID  
Sent By dhayes Date 2015-02-11 Time 16:06 Rev Time 0.00
Received By dhayes Date 2015-02-05 Time 18:45 Sent To  
Notes
2015-02-05 18:46:05SENT TO H MOSER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-27 Cont ID  
Sent By hmoser Date 2015-01-27 Time 13:13 Rev Time 0.00
Received By hmoser Date 2014-12-08 Time 18:00 Sent To  
Notes
2014-12-08 18:01:09B02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-12-12 Cont ID  
Sent By jwitmer Date 2014-12-12 Time 07:00 Rev Time 0.00
Received By jwitmer Date 2014-12-12 Time 07:00 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-03-19 Cont ID  
Sent By skennedy Date 2015-03-19 Time 12:05 Rev Time 0.00
Received By skennedy Date 2015-03-19 Time 12:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-02-06 Cont ID  
Sent By HMOSER Date 2015-02-06 Time 14:02 Rev Time 0.00
Received By hmoser Date 2015-02-06 Time 14:02 Sent To E
Notes
2015-02-06 14:10:34PLAN FAIL
 SAME AS LAST REVIEW REFER TO SECTION 607.5.1
 2010 FBC (M)
 PLAN REVIEW BY HAROLD MOSER
 OFFICE 561-805-6732
 FAX 561-805-6676
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-01-27 Cont ID  
Sent By hmoser Date 2015-01-27 Time 13:13 Rev Time 0.00
Received By hmoser Date 2015-01-27 Time 10:42 Sent To  
Notes
2015-01-27 13:13:09PLAN DENIED
 VAV #1 AND #2 SHOW DUCT GOING INTO ELEVATOR LOBBY.
 FIRE DAMPERS REQUIRED PER SECTION 607.5 WHERE REQUIRED
 2010 FBC (M)
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2014-12-20 Cont ID  
Sent By tklarge Date 2014-12-20 Time 03:21 Rev Time 0.00
Received By tklarge Date 2014-12-20 Time 03:07 Sent To  
Notes
***NONE***