Plan Review Details - Permit 14120241
Plan Review Stops For Permit 14120241
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-01-27 Cont ID  
Sent By jwitmer Date 2015-01-27 Time 10:18 Rev Time 0.00
Received By jwitmer Date 2015-01-27 Time 10:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-16 Cont ID  
Sent By JWITMER Date 2014-12-16 Time 08:49 Rev Time 0.00
Received By jwitmer Date 2014-12-16 Time 06:46 Sent To  
Notes
2014-12-16 08:49:20BUILDING PLAN REVIEW
 REVISION: 14120241
 PERMIT: 14050913
 ADD: 1016 CLARE SUITE # 3
 CONT: RIELLY CONSTRUCTION
 TEL: (561)262-6876
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. DEC. 16/ 2014
 ACTION: DENIED
  
 1) SHEET LS 1.1 SHOWS THE REMOVAL OF THE LIFT TO THE
 SECOND FLOOR. THE FIRST LETTER OF DISPROPORTIONATE COST
 LETTER SHOWED THAT THE OWNERS WERE APPLYING MORE THAN
 THE 20% DISPROPORTIONATE COST WITH THE INCLUSION OF A
 VERTICAL LIFT. THE LIFT HAS BEEN REMOVED FROM THE
 SUBMITTED REVISION. THE NEW LETTER SHOWING THE COST
 BREAK DOWN WHERE THE DISPROPORTIONATE COST HAVE BEEN
 MET NEEDS TO BE UPDATED SINCE THE REVISION SHOWS THE
 REMOVAL OF ACCESSIBLE ELEMENTS..
  
 LS1.1 PLEASE PROVIDE A COST BREAK DOWN WHERE 20% OR
 $70.00 DOLLARS IN ACCESSIBLE UPGRADES TO THE BUILDING.
 2010 FL ACCESSIBILITY CODE 202.4.2 ACCESSIBLE FEATURES
 IN THE EVENT OF DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 2) SHEET A1.1 NOTE # 2 SHOWS THE ELEVATOR WITH A 6'-0"
 X 8'-9" ELEVATOR DOOR ON LS1.1 WHERE AS THE DOOR
 SCHEDULE SHOWS IT AS A 4'-0" X 7'-0" DOOR.
 SHEET A1.1 SHOWS A 3'-0" DOOR OPENING, PLEASE CORRECT
 THE DETAIL AND PROVIDE HOW THIS DOOR IS GOING TO OPEN.
 NOTE 3002.1.1 OPENING PROTECTIVES.
 OPENINGS IN HOISTWAY ENCLOSURES SHALL BE PROTECTED AS
 REQUIRED IN CHAPTER 7. FBC-B TABLE 715.4.
  
 SHEET A 1.2 SHOWS THE SAME 3'-0" DOOR OPENING ON THE
 ELEVATOR, PLEASE PROVIDE A DETAIL HOW THE LINTEL OR
 BEAM WILL TIE INTO THE SIDE WALLS. NOTE THIS DOOR DOES
 NOT SHOW UP ON THE DOOR SCHEDULE SHEET A3.1.
  
 3) SHEET A5.1 NEW NOW THE SHAFT PENETRATES THE ROOF,
 THE SECTION THRU THE SHAFT INDICATES THE USE OF A NEW 3
 PLY MODIFIED BITUMENON TAPERED RIGID INSULATION BY JOHN
 MANSVILLE OR EQUAL.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 4) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, PLEASE
 IDENTIFY WHICH SUB-SYSTEM IS TO BE APPLIED.
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) SHEET A5.1 & S3 NEITHER PROVIDE THE WIND DESIGN
 CRITERIA FOR THE NEW ROOF:
  
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 6.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 6.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 6.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 6.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 6.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 7) WHILE THE BUILDING CODE DOES NOT INDICATE THE
 REQUIREMENT FOR SUMP PITS IN ELEVATOR HOISTWAY PITS
 THIS BEING A FIRE SPRINKLERED BUILDING, SUMP PUMPS WILL
 PUMP OT THE PIT IF THE FIRE SPRINKLERS ARE ACTIVATED.
 THE OTHER ISSUE WOULD BE IF A HYDROLIC ELEVATOR IS USED
 PLEASE REVIEWFBC-P 1003.4 AAND EXCEPTION.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2014-12-17 Cont ID  
Sent By DHAYES Date 2014-12-17 Time 12:26 Rev Time 0.00
Received By dhayes Date 2014-12-17 Time 12:26 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2014-12-16 Cont ID  
Sent By PLEDUC Date 2014-12-16 Time   Rev Time 0.00
Received By pleduc Date 2014-12-16 Time 11:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-27 Cont ID  
Sent By jwitmer Date 2015-01-27 Time 10:18 Rev Time 0.00
Received By jwitmer Date 2015-01-24 Time 08:13 Sent To  
Notes
2015-01-24 08:13:49SENT TO C-05.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-27 Cont ID  
Sent By hmoser Date 2014-12-27 Time 11:18 Rev Time 0.00
Received By hmoser Date 2014-12-08 Time 12:06 Sent To  
Notes
2014-12-09 12:13:40C21

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-12-27 Cont ID  
Sent By HMOSER Date 2014-12-27 Time 11:18 Rev Time 0.00
Received By hmoser Date 2014-12-27 Time 10:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-01-26 Cont ID  
Sent By tklarge Date 2015-01-26 Time 11:42 Rev Time 0.00
Received By tklarge Date 2015-01-26 Time 10:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-12-18 Cont ID  
Sent By JWITMER Date 2014-12-18 Time 05:51 Rev Time 0.00
Received By tklarge Date 2014-12-17 Time 15:10 Sent To  
Notes
2014-12-18 05:38:221) SUBMIT 2 COPIES OF MANUF. SPEC SHEETS/INSTALLATION
 MANUAL FOR THE STANCOR EFLUENT PUMP SYSTEM. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 2) SUBMIT MANUF. SPEC SHEETS FOR THE EEMAX
 INSTANTANEOUS WATER HEATER.WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 3) THE CONNECTION OF THE ELEVATOR SUMP TO THE BUILDING
 DRAINAGE SYSTEM SHALL BE BY INDIRECT WASTE PER THE 2010
 FL. PLOBG. CODE SEC. 301.6.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  