Plan Review Details - Permit 14120199
Plan Review Stops For Permit 14120199
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-12-09 Cont ID  
Sent By shill Date 2014-12-09 Time 12:11 Rev Time 0.00
Received By shill Date 2014-12-09 Time 12:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-12-05 Cont ID  
Sent By shill Date 2014-12-05 Time 17:58 Rev Time 0.00
Received By shill Date 2014-12-05 Time 17:58 Sent To  
Notes
2014-12-05 18:01:19****CORRECTIONS****
 COURTESY REVIEW, INFORMATION PROVIDED BY EMAIL
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED
  
 1. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 THE TWO SOUND TESTS PROVIDED ARE COMPLIANT WITH FBC
 1207.
  
 NO FLAME SPREAD TEST WAS PROVIDED. PLEASE CONTACT THE
 MANUFACTURER TO SEE IF THIS PRODUCT (ECO SILENCER) IS
 THE SAME AS OTHER PRODUCTS WITH A SIMILAR NAME BY THE
 SAME MANUFACTURER FOR WHICH THERE IS A FLAME SPREAD
 TEST. THE MANUFACTURER WOULD NEED TO PROVIDE A LETTER
 OF EXPLANATION.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-05 Cont ID  
Sent By shill Date 2014-12-05 Time 17:58 Rev Time 0.00
Received By shill Date 2014-12-05 Time 17:58 Sent To  
Notes
2014-12-05 17:58:42****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT. THE TEST
 REPORT PROVIDED HAS A SUSPENDED CEILING.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
  
  