2014-12-07 09:58:50 | BUILDING PLAN REVIEW |
| PERMIT: 14120178 |
| ADD: 600 OKEECHOBEE BLVD |
| CONT: THERMA SEAL ROOF SYSTEMS |
| TEL: (561) 223-2096 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SUN. DEC. 07/ 2014 |
| ACTION: DENIED |
| |
| 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 2) TO DATE THERE HAS BEEN NO SUBMITTALS IN REGARDS TO |
| THE INSULATING CONCRETE ROOF DECK. THE FOLLOWING |
| REQUIREMENTS WOULD NEED TO SHOW CODE COMPLIANCE FOR THE |
| USE OF A LIGHTWEIGHT INSULATING ROOF DECK SYSTEM: |
| |
| 1917.1.3 CELLULAR/AGGREGATE (HYBRID) LIGHTWEIGHT |
| INSULATING CONCRETE. |
| INSULATED CONCRETE FORMULATED BY COMBINING PREFORMED |
| FOAM WITH LOW DENSITY AGGREGATES TO IMPART PROPERTIES |
| OF BOTH AGGREGATE AND CELLULAR LIGHTWEIGHT INSULATING |
| CONCRETE. IT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH |
| OF 200 PSI (1379 KPA) WHEN TESTED IN COMPLIANCE WITH |
| ASTM C 495 AND C 796. |
| |
| 1917.1.4 WALKABILITY. |
| A TERM DEFINING THE ABILITY OF LIGHTWEIGHT INSULATING |
| CONCRETE TO WITHSTAND ANTICIPATED CONSTRUCTION FOOT |
| TRAFFIC DURING THE ROOF MEMBRANE APPLICATION WITHOUT |
| SIGNIFICANT INDENTATIONS IN THE LIGHTWEIGHT INSULATING |
| CONCRETE SURFACE. |
| |
| 1917.2 INSPECTION. |
| |
| 1917.2.1 |
| APPLICATION OF ALL LIGHTWEIGHT INSULATING CONCRETE ROOF |
| DECKS SHALL BE BY APPLICATORS APPROVED BY THE |
| LIGHTWEIGHT INSULATING CONCRETE DECK MANUFACTURER. |
| PRODUCT APPROVAL SHALL BE REQUIRED FOR ALL LIGHTWEIGHT |
| INSULATING CONCRETE SYSTEMS. |
| |
| 1917.2.2 |
| THE PERMIT HOLDER SHALL NOTIFY THE BUILDING OFFICIAL 48 |
| HOURS PRIOR TO THE POURING OF LIGHTWEIGHT INSULATING |
| CONCRETE. |
| |
| 1917.2.3 |
| THE PERMIT HOLDER SHALL MAKE AVAILABLE TO THE BUILDING |
| OFFICIAL A JOB LOG WITH THE FOLLOWING MINIMUM ITEMS. |
| 1. CAST DENSITY RECORDINGS/HOUR. |
| 2. PRODUCT EVALUATION FOR APPLICATION. |
| 3. DATE AND JOB LOCATIONS IDENTIFIED. |
| 4. RESULTS OF ANY FIELD TEST CONDUCTED. |
| |
| 1917.2.4 |
| ONCE THE ROOF DECK SYSTEM CAN SUPPORT FOOT TRAFFIC, THE |
| BUILDING OFFICIAL SHALL HAVE CLEAR ACCESS AND CLEAR |
| PATH AT HIS OPTION FOR INSPECTION OF LIGHTWEIGHT |
| INSULATING CONCRETE. |
| |
| 1917.3 TESTING. |
| THE BUILDING OFFICIAL MAY REQUIRE TESTS OF THE |
| LIGHTWEIGHT INSULATING CONCRETE TO CONFIRM THE FASTENER |
| WITHDRAWAL RESISTANCE, COMPRESSIVE STRENGTH OR DRAINAGE |
| ABILITY. |
| |
| THE STRUCTURAL ROOF DECK HAS NOT EVEN BEEN POURED |
| YET!!!! IT WOULD APPEAR THE WRONG PRODUCT APPROVAL HAS |
| BEEN SUBMITTED, NOA 13-0129.16 PAGE 21 OF 39 HAS BEEN |
| SUBMITTED WHICH INDICATES THE USE OF RIGID INSULATION |
| PANELS AND A TOP COAT OF 2 ? INCHES OF CONCRECEL. |
| PLEASE NOTE SHEET A12.19 DETAILS 2 & 3 BOTH SHOW THE |
| USE OF LIGHTWEIGHT INSULATING CONCRETE, IN NEITHER OF |
| THE DETAILS DOES THE DETAILS SHOW THE USE OF RIGID |
| INSULATION PANELS, NOTE IF THIS PRODUCT IS TO BE USED, |
| THE VARIOUS ROOF DETAILS THROUGHOUT THE PLANS WILL NEED |
| TO SHOW THE RIGID INSULATION BOARDS AS A REVISION, PLUS |
| A LAYOUT SHEET OF THE PANELS, SHOWING THE THICKNESS OF |
| THE PANELS & SLOPE TO THE POINT OF DRAINAGE, |
| ATTACHMENT OF PANELS AND MEETING THE REQUIREMENTS OF |
| SECTION 1917 FOR LIGHTWEIGHT CONCRETE. |
| |
| 3) PLEASE PROVIDE DOCUMENTATION WHERE THE PLANTATION |
| ROOF TILE (NOA 10-1201.01) IS GOING TO BE INSTALLED ON |
| THE BUILDING, THE MEAN ROOF HEIGHT, SLOPE AND ROOF ZONE |
| AND ASSOCIATED PRESSURES FOR ALL ROOF ZONES. THE |
| DESIGNER OF RECORD (ENGINEER) AGAIN HAS NOT REVIEWED |
| THIS SYSTEM FOR CODE COMPLIANCE FOR THE MOMENT OF OVER |
| TURNING PER SECTION 1609.5.3. |
| |
| 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| CONSTRUCTION DOCUMENTS SHALL |
| ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING |
| SYSTEM, MATERIALS, FASTENING |
| REQUIREMENTS, FLASHING REQUIREMENTS AND WIND RESISTANCE |
| RATING THAT ARE REQUIRED TO BE |
| INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL |
| INDICATE COMPLIANCE WITH THE WIND |
| CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT |
| BY AN ARCHITECT OR ENGINEER FOR THE |
| SPECIFIC SITE MUST BE SUBMITTED WITH THE CONSTRUCTION |
| DOCUMENTS. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |
| |
| |
2014-12-07 09:57:41 | BUILDING PLAN REVIEW |
| PERMIT: |
| ADD: |
| CONT: |
| TEL: (561 |
| |
| 2010 FLORIDA BUILDING CODE W |
| * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| |
| 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SUN. DEC. 07/2014 |
| ACTION: DENIED |
| |
| 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| SHOP DRAWINGS ETC.. |
| |
| 2) TO DATE THERE HAS BEEN NO SUBMITTALS IN REGARDS TO |
| THE INSULATED CONCRETE ROOF DECKING. THE FOLLOWING |
| REQUIREMENTS WOULD NEED TO SHOW CODE COMPLIANCE FOR THE |
| USE OF A LIGHTWEIGHT INSULATING ROOF DECK SYSTEM: |
| 1917.1.3 CELLULAR/AGGREGATE (HYBRID) LIGHTWEIGHT |
| INSULATING CONCRETE. |
| INSULATED CONCRETE FORMULATED BY COMBINING PREFORMED |
| FOAM WITH LOW DENSITY AGGREGATES TO IMPART PROPERTIES |
| OF BOTH AGGREGATE AND CELLULAR LIGHTWEIGHT INSULATING |
| CONCRETE. IT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH |
| OF 200 PSI (1379 KPA) WHEN TESTED IN COMPLIANCE WITH |
| ASTM C 495 AND C 796. |
| |
| 1917.1.4 WALKABILITY. |
| A TERM DEFINING THE ABILITY OF LIGHTWEIGHT INSULATING |
| CONCRETE TO WITHSTAND ANTICIPATED CONSTRUCTION FOOT |
| TRAFFIC DURING THE ROOF MEMBRANE APPLICATION WITHOUT |
| SIGNIFICANT INDENTATIONS IN THE LIGHTWEIGHT INSULATING |
| CONCRETE SURFACE. |
| |
| 1917.2 INSPECTION. |
| |
| 1917.2.1 |
| APPLICATION OF ALL LIGHTWEIGHT INSULATING CONCRETE ROOF |
| DECKS SHALL BE BY APPLICATORS APPROVED BY THE |
| LIGHTWEIGHT INSULATING CONCRETE DECK MANUFACTURER. |
| PRODUCT APPROVAL SHALL BE REQUIRED FOR ALL LIGHTWEIGHT |
| INSULATING CONCRETE SYSTEMS. |
| |
| 1917.2.2 |
| THE PERMIT HOLDER SHALL NOTIFY THE BUILDING OFFICIAL 48 |
| HOURS PRIOR TO THE POURING OF LIGHTWEIGHT INSULATING |
| CONCRETE. |
| |
| 1917.2.3 |
| THE PERMIT HOLDER SHALL MAKE AVAILABLE TO THE BUILDING |
| OFFICIAL A JOB LOG WITH THE FOLLOWING MINIMUM ITEMS. |
| 1. CAST DENSITY RECORDINGS/HOUR. |
| 2. PRODUCT EVALUATION FOR APPLICATION. |
| 3. DATE AND JOB LOCATIONS IDENTIFIED. |
| 4. RESULTS OF ANY FIELD TEST CONDUCTED. |
| |
| 1917.2.4 |
| ONCE THE ROOF DECK SYSTEM CAN SUPPORT FOOT TRAFFIC, THE |
| BUILDING OFFICIAL SHALL HAVE CLEAR ACCESS AND CLEAR |
| PATH AT HIS OPTION FOR INSPECTION OF LIGHTWEIGHT |
| INSULATING CONCRETE. |
| |
| 1917.3 TESTING. |
| THE BUILDING OFFICIAL MAY REQUIRE TESTS OF THE |
| LIGHTWEIGHT INSULATING CONCRETE TO CONFIRM THE FASTENER |
| WITHDRAWAL RESISTANCE, COMPRESSIVE STRENGTH OR DRAINAGE |
| ABILITY. |
| |
| THE STRUCTURAL ROOF DECK HAS NOT EVEN BEEN POURED |
| YET!!!! IT WOULD APPEAR THE WRONG PRODUCT APPROVAL HAS |
| BEEN SUBMITTED, NOA 13-0129.16 PAGE 21 OF 39 HAS BEEN |
| SUBMITTED WHICH INDICATES THE USE OF RIGID INSULATION |
| PANELS AND A TOP COAT OF 2 1/4 INCHES OC CONCRECEL. |
| PLEASE NOTE SHEET A12.19 DETAILS 2 & 3 BOTH SHOW THE |
| USE OF LIGHTWEIGHT INSULATING CONCRETE, IN NEITHER OF |
| THE DETAILS DOES IT SHOW THE USE OF RIGID INSULATION |
| PANELS, NOTE IF THIS PRODUCT IS TO BE USED, THE VARIOUS |
| ROOF DETILS THROUGHOUT THE PLANS WILL NEED TO SHOW THE |
| RIGID INSULATION PANELS AND ALSO WE WILL NEED A LAYOUT |
| SHEET FOR THE THICKNESS OF THE PANELS. SLOPE TO THE |
| POINT OF DRAINAGE PLUS THE MEETING THE REQUIREMENTS OF |
| SECTION 1917 FOR LIGHT WEIGHT CONCRETE. |
| |
| 3) PLEASE PROVIDE DOCUMENTATION WHERE THE PLANTATION |
| ROOF TILE (NOA: 10-1202.01) IS GOING TO BE INSTALLED ON |
| THE BUILDING, THE MEAN ROOF HEIGHT, ROOF ZONE, AND |
| ASSOCIATED PRESSURES FOR THIS ZONE. THE DESIGNER OF |
| RECORD AGAIN HAS NOT REVIEWED THIS SYSTEM FOR CODE |
| COMPLIANCE FOR THE MOMENT OF OVER TURNING PER SECTION |
| 1609.5.3. |
| |
| 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND |
| RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED. |
| PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE |
| COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE |
| SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR |
| ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH |
| THE CONSTRUCTION DOCUMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| . |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |