Plan Review Details - Permit 14120171
Plan Review Stops For Permit 14120171
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-12-18 Cont ID  
Sent By sgraham Date 2014-12-18 Time 14:23 Rev Time 0.00
Received By dhayes Date 2014-12-18 Time 14:23 Sent To Z
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2014-12-09 Cont ID  
Sent By dhayes Date 2014-12-09 Time 14:09 Rev Time 0.00
Received By dhayes Date 2014-12-09 Time 14:08 Sent To  
Notes
2014-12-09 14:30:57FBC- 107.3.5.3. PROVIDE A DETAILED ELECTRICAL SERVICE
 RISER TO INCLUDE THE FOLLOWING: A GROUNDING ELECTRODE
 SYSTEM. ALL SERVICE DISCONNECTS, TRANSFER SWITCHES AND
 PANELS. ALL CONDUIT AND WIRE SIZES. A COMPLETE DETAILED
 LOAD CALCULATION(S). CLEAR AND SPECIFIC PANEL
 DIRECTORIES. ALL CIRCUIT NUMBERS AS INDICATED ON THE
 PANEL DIRECTORIES SHOWN ON THE FLOOR PLAN.. PROVIDE ALL
 NECESSARY ELECTRICAL PLANS TO INDICATE THE RELOCATION
 OF THE GENERATOR, THE LOCATION OF THE GENERATOR
 DISCONNECT(S), AND THE LOCATION, ROUTING, TYPE AND SIZE
 OF CONDUITS AND WIRING.

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2015-01-15 Cont ID  
Sent By tklarge Date 2015-01-15 Time 04:28 Rev Time 0.00
Received By tklarge Date 2015-01-15 Time 04:23 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2014-12-23 Cont ID  
Sent By tklarge Date 2014-12-23 Time 05:55 Rev Time 0.00
Received By tklarge Date 2014-12-20 Time 03:22 Sent To  
Notes
2014-12-20 03:28:381) YOU HAVE SUBMITTED A COPY OF THE SIZING TABLE FOR PE
 PIPE YET PE PIPE IS NOT SHOWN ON THE PLANS AS BEING
 INSTALLED. SUBMIT A COPY OF THE SIZING TABLE FROM THE
 2010 FL. BUILDING CODE, RESIDENTIAL, SECTION G2413.3
 AND TABLES G2413.4 (5) OR 2413.4 (6) FOR THE TYPE OF
 PIPE MATERIAL BEING USED.THE PLAN INDICATES FSP ? I
 ASSUME THIS IS CSST. IF SO, PLEASE REFER TO IT AS SUCH
 ON THE PLAN.
 2) IF CSST IS BEING INSTALLED, SHOW THE CORRESPONDING
 EHD NUMBER FOR THE PIPE SIZE IN ACCORDANCE WITH 2010
 FBCR, SEC.G2413.3 AND THE APPLICABLE SIZING TABLE.
 3) INDICATE THE GAS PRESSURE ( PSI ) ON THE PLANS AND
 THE LOCATION OF THE 2ND STAGE REGULATOR IF APPLICABLE.
 REGULATORS LOCATED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION.2010 FBCR,
 SEC. G2421.1.
 4) SUBMIT TWO CLEAN COPIES OF THE GAS PLAN THAT CLEARLY
 SHOWS THE TYPE OF PIPING THROUGH THE ATTIC SPACE, THE
 TOTAL BTU LOAD ON THE SYSTEM ( SINCE THE BRANCH LINE
 FOR THE GENERATOR IS BEING CONNECTED TO THE EXISTING
 SYSTEM, ALL THE APPLIANCES CONNECTED TO THE SYSTEM
 SHALL BE INCLUDED IN THE TOTAL BTU. IS THE LOAD OF
 300,000 THE TOTAL LOAD OR JUST THE GENERAROR LOAD?
 INDICATE ON THE PLANS. THE PLANS HAVE ITEMS CROSSED OUT
 AND ARE SOMEWHAT VAGUE IN NATURE.IN ORDER FOR A
 COMPLETE REVIEW TO BE DONE, 2 COPIES OF CLEAN DRAWINGS
 SHALL BE SUBMITTED. I WILL NOT APPROVE THESE PLANS AS
 THEY ARE.
 5) THE NOTE ON THE GAS DRAWING STATES THE TOTAL FOOTAGE
 OF PIPE IS 30 FEET BUT THE DIMENSIONS SHOWN ON THE
 SURVEY CLEARLY INDICATE THAT THE TOTAL RUN FROM THE GAS
 METER TO THE GENERATOR IS MORE THAN 30 FEET. SHOW THE
 DISTANCE FROM THE GAS METER TO THE FURTHEST OUTLET
 /GENERATOR.
 **NOTE** - I SUGGEST THAT SOMEONE CONTACT ME AT
 561-805-6692 TO SET UP AN APPOINTMENT TO COME INTO THE
 BUILDING DIVISION AND MEET WITH ME TO DISCUSS THESE
 COMMENTS AND ARRIVE AT A RESOLUTION SO WE CAN GET THIS
 PERMIT ISSUED. THANK YOU.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2014-12-09 Cont ID  
Sent By tklarge Date 2014-12-09 Time 13:20 Rev Time 0.00
Received By tklarge Date 2014-12-09 Time 13:20 Sent To  
Notes
2014-12-09 13:40:571) HOW CAN ONLY 10 FT. OF PE PIPE BE RUN WHEN THE GAS
 METER IS SHOWN ON THE EAST SIDE OF THE STRUCTURE AND
 THE GENERATOR IS SHOWN ON THE WEST SIDE? SUBMIT TWO
 COPIES OF THE SURVEY THAT CLEARLY SHOW THE LOCATION OF
 THE GENERATOR AND THE LOCATUION OF THE NATURAL GAS
 METER. WPB AMEND. TO 201 FBC SEC. 107.2.1.
 2) SUBMIT TWO CLEAN COPIES OF A GAS PLAN THAT CLEARLY
 SHOWS THE LOCATION OF THE GENERATOR, THE LOCATION AND
 LENGTH OF THE PIPING,& THE TOAT DISTANCE FROM THE GAS
 METER TO THE GENERATOR. DO NOT USE COPIES OF PREVIOUSLY
 PERMITTED AND SIGNED PLANS. WPB AMEND. TO 2010 FBC SEC.
 107.2.1, 107.1.
 3) THE GAS PLAN SHOWS THE PE PIPE RUNNING THROUGH THE
 STRUCTURE. PE PIPE CAN ONLY BE USED OUTSIDE
 UNDERGROUND. FGC SEC.404.15.1.
 4) SHOW THE LOCATION OF THE 2ND STAGE REGULATOR ON THE
 PLAN.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-01-15 Cont ID  
Sent By tklarge Date 2015-01-15 Time 04:28 Rev Time 0.00
Received By tklarge Date 2015-01-15 Time 04:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-12-23 Cont ID  
Sent By tklarge Date 2014-12-23 Time 05:55 Rev Time 0.00
Received By tklarge Date 2014-12-18 Time 14:23 Sent To  
Notes
2014-12-18 14:23:21R08

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2014-12-09 Cont ID  
Sent By sgraham Date 2014-12-09 Time 14:31 Rev Time 0.00
Received By dhayes Date 2014-12-04 Time 08:45 Sent To Z
Notes
2014-12-09 12:49:23SENT TO T LARGE
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
2014-12-05 08:45:00R01

Review Stop Z ZONING
Rev No 2 Status P Date 2014-12-19 Cont ID  
Sent By sgraham Date 2014-12-19 Time 13:30 Rev Time 0.00
Received By sgraham Date 2014-12-19 Time 13:30 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2014-12-05 Cont ID  
Sent By dhayes Date 2014-12-09 Time 14:31 Rev Time 0.00
Received By sgraham Date 2014-12-05 Time 13:59 Sent To G
Notes
***NONE***