Plan Review Details - Permit 14120169
Plan Review Stops For Permit 14120169
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-01-30 Cont ID  
Sent By jwitmer Date 2015-01-30 Time 07:24 Rev Time 0.00
Received By jwitmer Date 2015-01-30 Time 07:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-01-15 Cont ID  
Sent By jwitmer Date 2015-01-15 Time 08:26 Rev Time 0.00
Received By jwitmer Date 2015-01-15 Time 08:01 Sent To HIST
Notes
2015-01-15 08:26:09BUILDING PLAN REVIEW
 PERMIT: 14120169
 ADD: 716 N. SAPODILLA AVE.
 CONT: NUJAK DEV.
 TEL: (561)847-3291
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. JAN. 15/ 2015
 ACTION: DENIED
  
 NOTICE!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA STATUTES
 STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF
 FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 1) COMPLIED.
 PLEASE PROVIDE A SURVEY, EXTERIOR DOORS CAN NOT SWING
 OVER THE PROPERTY LINES. 2010 FBC-B 3202.2
 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN HEIGHT.
 ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE
 AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE
 PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1
 THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 2) COMPLIDED.
 ALSO NOTE HOW FAR THE BUILDING IS FROM THE PROPERT
 LINE. 2010 FBC-B TABLE 705.8 MAXIMUM AREA OF EXTERIOR
 WALL OPENINGS BASED ON FIRE SEPARATION DISTANCE AND
 DEGREE OF OPENING PROTECTION.
  
 3) 2ND REQUEST, THIS APPEARS TO BE A FLORIDA APPROVAL
 PLEASE SUBMIT THE COVERSHEET TO THE CURRENT CODE. THE
 PRODUCT APPROVAL SUBMITTED DOES NOT HAVE THE
 COVERSHEETS TO WHICH CODE THIS WAS APPROVED. SHEET # 3
 INDICATES THIS REPORT EXPIRED 03/31/2010.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 4) 2ND REQUEST. 2010 FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) COMPLIED> . SHEET A-1 WIND DESIGN CRITERIA:
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2014-12-10 Cont ID  
Sent By jwitmer Date 2014-12-10 Time 07:27 Rev Time 0.00
Received By jwitmer Date 2014-12-10 Time 07:04 Sent To HIST
Notes
2014-12-10 07:27:10BUILDING PLAN REVIEW
 PERMIT: 14120169
 ADD: 716 N. SAPODILLA AVE.
 CONT: NUJAK DEV.
 TEL: (561)847-3291
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. DEC. 10/ 2014
 ACTION: DENIED
  
 1) PLEASE PROVIDE A SURVEY, EXTERIOR DOORS CAN NOT
 SWING OVER THE PROPERTY LINES. 2010 FBC-B 3202.2
 ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET IN HEIGHT.
 ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY ABOVE GRADE
 AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL BE
 PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS 3202.2.1
 THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 2) ALSO NOTE HOW FAR THE BUILDING IS FROM THE PROPERT
 LINE. 2010 FBC-B TABLE 705.8 MAXIMUM AREA OF EXTERIOR
 WALL OPENINGS BASED ON FIRE SEPARATION DISTANCE AND
 DEGREE OF OPENING PROTECTION.
  
 3) THE PRODUCT APPROVAL SUBMITTED DOES NOT HAVE THE
 COVERSHEETS TO WHICH CODE THIS WAS APPROVED. SHEET # 3
 INDICATES THIS REPORT EXPIRED 03/31/2010.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 4) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 5) SHEET A-2 DOES NOT PROVIDE THE WIND DESIGN CRITERIA:
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 5.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 5.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 5.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 5.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 5.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 3 Status P Date 2015-01-28 Cont ID  
Sent By fmittner Date 2015-01-28 Time 10:46 Rev Time 0.00
Received By fmittner Date 2015-01-28 Time 10:46 Sent To B
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2015-01-20 Cont ID  
Sent By fmittner Date 2015-01-20 Time 11:37 Rev Time 0.00
Received By fmittner Date 2015-01-20 Time 11:37 Sent To  
Notes
2015-01-20 11:38:24STILL NO EXPLANATION OF DOOR TYPE....DOES IT HAVE
 GLAZING, IS IT CLEAR, ETC? FILED UNDER SMALL PLANS
 DENIED N

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2014-12-11 Cont ID  
Sent By fmittner Date 2014-12-11 Time 16:12 Rev Time 0.00
Received By fmittner Date 2014-12-11 Time 16:11 Sent To  
Notes
2014-12-11 16:12:54NEED ELEVATION OF WHAT DOOR WILL LOOK LIKE. QUESTIONS
 CONTACT FRIEDERIKE MITTNER 822-1457. FILED UNDER SMALL
 PLANS DENIED "N".

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-01-30 Cont ID  
Sent By   Date 2015-01-30 Time   Rev Time 0.00
Received By jgomez Date 2015-01-26 Time 12:24 Sent To  
Notes
2015-01-27 12:25:38RE-SUBMITTAL SENT TO ZONING BIN FOR HISTORIC REVIEW.
 JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-01-22 Cont ID  
Sent By skennedy Date 2015-01-20 Time 07:36 Rev Time 0.00
Received By skennedy Date 2015-01-13 Time 18:14 Sent To  
Notes
2015-01-22 07:37:18I STOPPED OUT WITH 1/20/15 DATE COSISTANT WITH LAST
 REVIEW.
2015-01-13 18:14:25SENT TO J WITMER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2015-01-13 Time   Rev Time 0.00
Received By spalmer Date 2014-12-04 Time 13:21 Sent To  
Notes
2014-12-11 10:30:29SENT TO HISTORIC
2014-12-04 13:21:24ROUTED TO BLDG $5000 & UNDER

Review Stop Z ZONING
Rev No 1 Status P Date 2014-12-11 Cont ID  
Sent By aaponte Date 2014-12-11 Time 10:29 Rev Time 0.00
Received By aaponte Date 2014-12-11 Time 10:29 Sent To  
Notes
***NONE***