Plan Review Details - Permit 14120130
Plan Review Stops For Permit 14120130
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-06-29 Cont ID  
Sent By jwitmer Date 2015-06-29 Time 10:53 Rev Time 0.00
Received By jwitmer Date 2015-06-29 Time 10:39 Sent To  
Notes
2015-06-29 10:52:19BUILDING PLAN REVIEW
 PERMIT: 14120130
 ADD: 1901 S. DIXIE HWY.
 CONT: SISCACONSTRUCTION
 TEL: (561)686-5545
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: MON. JUNE 29/ 2015
 ACTION: BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1C) PROVISO: THE PLANS INDICATE A PROPOSED UNDERGROUND
 FIRE LINE TAP.2010 FBC-B 903.1.2 GROUP A2 WHEN THE FIRE
 AREA HAS AN OCCUPANT LOAD OF 100 OR MORE FIRE
 SPRINKLERS ARE REQUIED. 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS. 107.3.5.1 COMMERCIAL BUILDINGS
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC
 FIRE SPRINKLERS
  
 2A) BUILDING PROVISO: MON. JUNE 29/ 2015 RECEIVED
 SIGNED & SEALED LETTER FROM THE DESIGNER OF RECORD THAT
 A REVISION WILL BE FORTH COMING CORRECTING THE FRONT
 ENTRY DOORS TO BE OUT SWING BUT OVER THE PROPERTY LINE,
 THE REVISION WILL NEED TO BE INTO THE BUILDING
 DEPARTMENT AND APPROVED BEFORE THE FRAMING INSPECTION
 CAN OCCUR.
  
 2B) APPROVED, LETTER FROM THE DESIGNER OF RECORD
 SHOWING COMPLIANCE WITH 2010 FL. ACCESSIBILTY CODE SEE
 SECTION 202.4.1 DISPROPORTIONATE COST.
  
 3A) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR
 DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING
 OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE
 IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING.
 THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED
 UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN
 APPROVED BY THE BUILDING OFFICIAL. 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, EFIS
 SYSTEMS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 4) PROVISO: SUBMIT BEFORE 1ST INSPECTION FOR FOOTINGS.
 SHEET S4.0 ALSO HAS STATEMENTS FOR SOILS REPORTS FOR
 ALL OF THE NEW FOUNDATIONS FOR THE MEZZANINE LEVEL. THE
 ASSUMED SAFE BEARING VALUE OF THE SOILS IS 2500 PSF.
 NOTE 3 READS: SOILS SUPPORTING ALL FOOTING MUST BE
 INSPECTED AND APPROVED BY A REGISETERD SOILS ENGINEER
 BEFORE COMMENCING WORK. APPROVED IN WRITING MUST
 INDICATE THE SOIL IS ADEQUATE TO SAFETLY SUSTAIN
 SPECIFIED SOIL BEARING PRESSURE. 2010 FBC-B 1803.2
 INVESTIGATIONS REQUIRED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-06-19 Cont ID  
Sent By jwitmer Date 2015-06-19 Time 17:29 Rev Time 0.00
Received By jwitmer Date 2015-06-19 Time 15:07 Sent To  
Notes
2015-06-19 17:04:18BUILDING PLAN REVIEW
 PERMIT: 14120130
 ADD: 1901 S. DIXIE HWY.
 CONT: SISCACONSTRUCTION
 TEL: (561)686-5545
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: FRI. JUNE 19/ 2015
 ACTION: DENIED
  
 1) COVERSHEET INDICATES UNDER THE CODE ANALYSIS:
 1A-B) COMPLIED. .
  
 1C) PROVISO: THE PLANS INDICATE A PROPOSED UNDERGROUND
 FIRE LINE TAP.2010 FBC-B 903.1.2 GROUP A2 WHEN THE FIRE
 AREA HAS AN OCCUPANT LOAD OF 100 OR MORE FIRE
 SPRINKLERS ARE REQUIED. 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS. 107.3.5.1 COMMERCIAL BUILDINGS
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC
 FIRE SPRINKLERS
  
 2) SITE PLAN AP 1.0:
  
 2A) 3RD REQUEST. ALL 3 VERSIONS OF THIS PLAN SHOWS A
 NEW FRONT ENTRY, WITH DOORS THAT SWING OUT OVER THE
 PROPERTY LINE. THE CURRENT SET OF DOORS ARE IN SWING
 DOORS. 2010 FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE AND
 BELOW 8 FEET IN HEIGHT. DOORS AND WINDOWS SHALL NOT
 OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 2B) THE CITY HAS AN ISSUE WITH SUBMITTED
 DISPROPORTIONATE COST BREAK DOWN FOR THIS PROJECT. THE
 PERMIT APPLICATION VALUE IS INDICATED AS $336,000.00
 DOLLARS BUTTHE TOTAL DISPROPORTIONATE COST TOTALS
 $304,175.00 DOLLARS. THE MEP SUBCONTRACTORS, FIRE
 SPRINKLER AND OTHER MISC. PERMITS CAN'T ADD UP TO
 $31,825 DOLLARS. PLEASE HAVE THE CONTRACTOR PROVIDE A
 TRUE COST BREAK DOWN OF THE TOTAL JOB COST AND THE COST
 ASSOCIATED WITH THE ACCESSIBLE ELEMENTS THAT MAY MEET
 DISPROPORTIONATE COST.
 2010 FL. ACCESSIBILTY CODE SEE SECTION 202.4.1 AND
 202.4.1 DISPROPORTIONATE COST. EITHER THE CONTRACTOR OR
 DESIGNER OF RECORD ON THEIR LETTER HEAD PROVIDE A COST
 BREAKDOWN WHERE $67,200.00 DOLLORS WILL BE SPENT IN
 ACCESSIBLE UPGRADES. PLEASE NOT THE ORDER IN WHICH THE
 FUNDS ARE TO BE SPENT. FL ACC. CODE 202.4.2. (I) AN
 ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM
 FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (IV)
 ACCESSIBLE TELEPHONES; (V) ACCESSIBLE DRINKING
 FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 2C) COMPLIED
  
 3) COMPLIED.
  
 4) THE OPTION OF DEFERRRED SUBMITTALS IS UP TO THE
 CONTRACTOR AND OR THE DESIGNERS, NOT MY REQUEST. IF
 EITHER THE CONTRACTOR AND OR DESIGNER WOULD PREFER TO
 TAKE ADVANTAGE OF THE DEFERRED SUBMITTALS PLEASE
 INDICATE YOU WOULD LIKE TO DO SO AND THE PRODUCT
 APPROVALS WILL BE DEFERRED UNTIL AFTER PERMIT ISSUANCE.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, EFIS
 SYSTEMS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) COMPLIED.
  
 7) PROVISO: SUBMIT BEFORE 1ST INSPECTION FOR FOOTINGS.
 SHEET S4.0 ALSO HAS STATEMENTS FOR SOILS REPORTS FOR
 ALL OF THE NEW FOUNDATIONS FOR THE MEZZANINE LEVEL. THE
 ASSUMED SAFE BEARING VALUE OF THE SOILS IS 2500 PSF.
 NOTE 3 READS: SOILS SUPPORTING ALL FOOTING MUST BE
 INSPECTED AND APPROVED BY A REGISETERD SOILS ENGINEER
 BEFORE COMMENCING WORK. APPROVED IN WRITING MUST
 INDICATE THE SOIL IS ADEQUATE TO SAFETLY SUSTAIN
 SPECIFIED SOIL BEARING PRESSURE. 2010 FBC-B 1803.2
 INVESTIGATIONS REQUIRED.
  
 8-10) COMPLIED.
  
 12) COMPLIED. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-04-09 Cont ID  
Sent By jwitmer Date 2015-04-09 Time 16:21 Rev Time 0.00
Received By cpuell Date 2015-05-12 Time 13:40 Sent To  
Notes
2015-04-09 15:51:10BUILDING PLAN REVIEW
 PERMIT: 14120130
 ADD: 1901 S. DIXIE HWY.
 CONT: SISCACONSTRUCTION
 TEL: (561)686-5545
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURS. 09/ 2015
 ACTION: DENIED
  
 1) COVERSHEET INDICATES UNDER THE CODE ANALYSIS:
 1A-B) COMPLIED.
  
 1C) 2ND REQUEST SUBMIT FIRE SPRINKLER PLANS. THE PLANS
 INDICATE THERE IS AN EXISTING FIRE SPRINKLER. NOT SHOWN
 ON PLANS NOR IS THERE ANY ADDITIONAL LAYOUT OF FIRE
 SPRINKLER HEADS FOR THE PROPOSED MEZZANINE LEVEL. SINCE
 THIS IS A CHANGE OF OCCUPANCY UNDER THE EXISITNG
 BUILDING CODE SECTION 904.1 REFERS TO SECTION 912.
  
 2010 EXT. BLDG. CODE 912.2.1 FIRE SPRINKLER SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
  
 2010 FBC-B 903.1.2 GROUP A2 WHEN THE FIRE AREA HAS AN
 OCCUPANT LOAD OF 100 OR MORE FIRE SPRINKLERS ARE
 REQUIED.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC
 FIRE SPRINKLERS
  
 2) SITE PLAN AP 1.0:
  
 2A) 2ND REQUEST. NOTE THE SITE PLAN APPEARS THE FRONT
 ENTRY WALL AND DOOR IS WITHIN OR ON THE PROPERTY LINE.
 2010 FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8
 FEET IN HEIGHT. DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 2B) 2ND REQUEST. THE DISPROPORTIONATE COST SUBMITTED
 WAS REJECTED BY THE BUILDING OFFICIAL THERE ARE LINE
 ITEMS THAT DO NOT PERTAIN TO ACCESSIBILITY. PLEASE
 REVIEW SECTION
 202.4.2 ACCESSIBILITY WHICH CAN BE DEDUCTED, : (I) AN
 ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (III) AT LEAST ONE ACCESSIBLE RESTROOM
 FOR EACH SEX OR A SINGLE UNISEX RESTROOM; (V)
 ACCESSIBLE DRINKING FOUNTAINS AND (VI) WHEN POSSIBLE
 PARKING LOTS. THE FRONT ENTRY OVER THE PROPERTY LINE
 THE COST OF REFRAMING, THE DOOR FRAME AND LABOR CAN NOT
 BE COUNTED, A NEW ACCESSIBLE THRESHOLD OR DOOR LATCH
 YES, RESTROOMS COSTS ASSOCIATED WITH MAKING RESTROOMS
 ACCESSIBLE, SUCH AS INSTALLING GRAB BARS, ENLARGING
 TOILET STALLS, INSULATING PIPES, OR INSTALLING
 ACCESSIBLE FAUCET CONTROLS; THE BUILDING OFFICIAL WOULD
 ALLOW THE REFRAMING FOR ACCESSIBLE RESTROOMS.
  
 THE SITE PLAN DOES NOT SHOW THE PARKING LOT DOUBLE
 STRIPED TO THE CITY MUNI CODE. THE SITE PLANS FAILS TO
 SHOW COMPLIANCE WITH THE 2010 FL. EXT. BLDG. CODE 906.1
 WHICH REFERS YOU BACK TO THE 2010 FL. ACCESSIBILTY CODE
 SEE SECTION 202.4.1 AND 202.4.1 DISPROPORTIONATE COST.
 EITHER THE CONTRACTOR OR DESIGNER OF RECORD ON THEIR
 LETTER HEAD PROVIDE A COST BREAKDOWN WHERE $67,200.00
 DOLLORS WILL BE SPENT IN ACCESSIBLE UPGRADES. PLEASE
 NOT THE ORDER IN WHICH THE FUNDS ARE TO BE SPENT. FL
 ACC. CODE 202.4.2. (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 ZONING STATED THAT THE 50% RULE FOR LANDSCAPING BUT IT
 WOULD NOT REQUIRE THE RESTRIPPING OF THE PARKING LOT,
 IT WILL BE DETERMINED BY IF THE FUNDS SENT FOR
 DISPROPORTIONALITY ARE USED UP BEFORE THE PARKING LOT
 GETS INVOLVED FOR ACCESSIBLITY.
  
 2C) NOTE TO GAIN ENTRY TO THE FRONT OF THE BUILDING YOU
 WILL BE CROSSING A ALLEYWAY WHERE DETECTABLE WARNINGS
 WOULD BE REQUIRED SINCE THIS IS A PUBLIC RIGHT OF WAY.
 2010 FL. ACCESSIBILITY CODE 705.
  
 3) COMPLIED, WINDOW PRESSURES ARE GOOD.
  
 4-5) BUILDING PROVISO: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, EFIS
 SYSTEMS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) COMPLIED.
  
 7) 2ND REQUEST. SHEET S4.0 ALSO HAS STATEMENTS FOR
 SOILS REPORTS FOR ALL OF THE NEW FOUNDATIONS FOR THE
 MEZZANINE LEVEL. THE ASSUMED SAFE BEARING VALUE OF THE
 SOILS IS 2500 PSF. NOTE 3 READS: SOILS SUPPORTING ALL
 FOOTING MUST BE INSPECTED AND APPROVED BY A REGISETERD
 SOILS ENGINEER BEFORE COMMENCING WORK. APPROVED IN
 WRITING MUST INDICATE THE SOIL IS ADEQUATE TO SAFETLY
 SUSTAIN SPECIFIED SOIL BEARING PRESSURE. 2010 FBC-B
 1803.2 INVESTIGATIONS REQUIRED.
  
 8) 2ND REQUEST. RESPONCE SEE DETAIL 11/A5.0, THIS
 DETAIL IS FOR A BULKHEAD OR SOFFIT NOT A DROPPED
 CEILING. SHEET A1.1 SHOWS A DROPPED CEILING OVER
 EXPOSITION KITCHEN AND PICK UP AREA, PLEASE PROVIDE
 DETAILS OF HOW THIS SYSTEM WILL BE ATTACHED TO THE
 FRAMING SYSTEM ABOVE THE GIRDERS APPEAR TO BE SPACED
 10'-0" APART.107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 9)COMPLIED> SHEET A1.1 CEILING PLAN THERE IS A SYMBOL T
 THAT APPEARS NUMEROUS TIMES ON THE PLANS, THIS SYMBOL
 IS NOT FOUND IN THE CEILING PLAN LEGEND. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 10) 2ND REQUEST SHEET A1.0, A1.2 THE MAIN FLOOR PLAN
 DOES NOT PROVIDE ANY INTERIOR ELEVATIONS FOR THE PICK
 UP AREA SHOWING COMPLIANCE WITH 2010 FL ACCESS. CODE
 904.4. SALES AND SERVICE COUNTERS. SALES COUNTERS AND
 SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
 THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND
 THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
  
 11) COMPLIED.
  
 12) COMPLIED.
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-01-05 Cont ID  
Sent By jwitmer Date 2014-12-19 Time 16:55 Rev Time 0.00
Received By jwitmer Date 2014-12-18 Time 13:15 Sent To  
Notes
2014-12-19 14:40:35BUILDING PLAN REVIEW
 PERMIT: 14120130
 ADD: 1901 S. DIXIE HWY.
 CONT: SISCACONSTRUCTION
 TEL: (561)686-5545
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. DEC. 19/ 2014
 ACTION: DENIED
  
 1) COVERSHEET INDICATES UNDER THE CODE ANALYSIS:
 1A) THIS PLAN IS DESIGNED UNDER THE 2010 FBC-EXISTING
 BUILDING CODE AS A LEVEL II ALTERATION. PLEASE NOTE FOR
 THIS ADDRESS THE CITY HAS A CURRENT BUSINESS TAX
 (OCCUPATIONAL LICENSE) FOR REWARDS LIGHTING. WITH A
 CHANGE OF OCCUPANCY PLANS ARE TO BE DESIGNED IN
 ACCORDANCE WITH CHAPTER 9 OF THE EXISTING BUILDING
 CODE, CHANGE OF OCCUPANCY SEE SECTIONS 901.3 . WHERE
 THE OCCUPANCY CLASSIFICATION OF A BUILDING CHANGES, THE
 PROVISIONS OF SECTIONS 902 THROUGH 912 SHALL APPLY.
  
 1B) THE CODE ANALYSIS DOES NOT PROVIDE WHAT TYPE OF
 CONSTRUCTION THIS BUILDING IS? 2010 FBC-B TABLE 503.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS: (3) MINIMUM TYPE OF
 CONSTRUCTION SHALL BE DETERMINED (SEE TABLE 503).
  
 1C) THE PLANS INDICATE THERE IS AN EXISTING FIRE
 SPRINKLER. NOT SHOWN ON PLANS NOR IS THERE ANY
 ADDITIONAL LAYOUT OF FIRE SPRINKLER HEADS FOR THE
 PROPOSED MEZZANINE LEVEL. SINCE THIS IS A CHANGE OF
 OCCUPANCY UNDER THE EXISITNG BUILDING CODE SECTION
 904.1 REFERS TO SECTION 912.
  
 2010 EXT. BLDG. CODE 912.2.1 FIRE SPRINKLER SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
  
 2010 FBC-B 903.1.2 GROUP A2 WHEN THE FIRE AREA HAS AN
 OCCUPANT LOAD OF 100 OR MORE FIRE SPRINKLERS ARE
 REQUIED.
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS
 5. FIRE SUPPRESSION SYSTEMS SHALL INCLUDE: SCHEMATIC
 FIRE SPRINKLERS
  
 2) SITE PLAN AP 1.0:
  
 2A) NOTE THE SITE PLAN APPEARS THE PROPERTY LINE IS
 WITHIN OR ON THE PROPERTY LINE. THE LIFE SAFETY PLANS
 INDICATE REAR DOORS THA WILL SWING OUT OVER THE
 PROPERTY LINE INTO THE TRAFFIC LANE OF THE ALLEYWAY.
 2010 FBC-B 3202.2 ENCROACHMENTS ABOVE GRADE AND BELOW 8
 FEET IN HEIGHT. DOORS AND WINDOWS SHALL NOT OPEN OR
 PROJECT INTO THE PUBLIC RIGHT-OF-WAY.
  
 2B) THE SITE PLAN DOES NOT SHOW THE PARKING LOT DOUBLE
 STRIPED TO THE CITY MUNI CODE. THE SITE PLANS FAILS TO
 SHOW COMPLIANCE WITH THE 2010 FL. EXT. BLDG. CODE 906.1
 WHICH REFERS YOU BACK TO THE 2010 FL. ACCESSIBILTY CODE
 SEE SECTION 202.4.1 AND 202.4.1 DISPROPORTIONATE COST.
 EITHER THE CONTRACTOR OR DESIGNER OF RECORD ON THEIR
 LETTER HEAD PROVIDE A COST BREAKDOWN WHERE $67,200.00
 DOLLORS WILL BE SPENT IN ACCESSIBLE UPGRADES. PLEASE
 NOT THE ORDER IN WHICH THE FUNDS ARE TO BE SPENT. FL
 ACC. CODE 202.4.2. (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 2C) NOTE TO GAIN ENTRY TO THE FRONT OF THE BUILDING YOU
 WILL BE CROSSING A ALLEYWAY WHERE DETECTABLE WARNINGS
 WOULD BE REQUIRED SINCE THIS IS A PUBLIC RIGHT OF WAY.
 2010 FL. ACCESSIBILITY CODE 705.
  
 3) SHEET A2.0 THERE IS A SECTION THRU THE BUILDING
 PROVIDING SCALED MEAN ROOF HEIGHT OF 18.22 FT. AND THE
 PARAPET HEIGHT OF APPROX. 19.90 FT. THE ROOF PRESSURES
 FOUND ON SHEET S-4 ARE TAKEN AS A EXPOSURE C AT 20'-0"
 WHERE AS THE WINDOW AND DOOR PRESSURES ARE LOW FOR A
 BUILDING 20 FT HIGH, THEY ARE TAKEN FOR A 15 FOOT HIGH
 BUILDING C EXPOSURE. IT ALSO APPEARS THE PREESURES ARE
 LOW ON SHEET S7.0. NOTE THE PLANS ARE DRAWN IN 3/16
 INCH SCALE BUT THERE IS NO MEASUREMENTS GIVEN TO DERIVE
 THE SIZE OF WINDOWS AND DOORS FOR ACCURATE SQ. FT OF
 AREA VERSES PRESSURES.
  
  
 4) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, WALL LOUVERS, EFIS
 SYSTEMS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (G) PRE-ENGINEERED A/C STANDS
  
 5) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 6) NEITHER THE ARCHITECTURAL, STRUCTURAL OR MECHANICAL
 SHEETS SHOW THE ATTACHMENT METHOD FOR THE ROOFTOP UNITS
 (CURBS) WALK IN COOLER CONDENSING UNIT ROOF TOP STANDS
 OR THE HOOD EXHAUST FANS AND STANDS. PLEASE SHOW HOW
 THESE UNITS WILL BE ATTACHED TO THE ROOF FRAMING
 MEMBERS, HOW THE INFILE FRAMING TO SUPPORT THESE UNITS
 WIL BE DESIGNED, STRAPPING AND ANCHORING OF CURBS AND
 ANCHORING OF THE RTU,S AND EXHAUST FANS O THEIR CURBS.
 2010 FBC-B
 1609.8 ROOFTOP STRUCTURES AND EQUIPMENT.
  
 7) SHEET S4.0 ALSO HAS STATEMENTS FOR SOILS REPORTS FOR
 ALL OF THE NEW FOUNDATIONS FOR THE MEZZANINE LEVEL. THE
 ASSUMED SAFE BEARING VALUE OF THE SOILS IS 2500 PSF.
 NOTE 3 READS: SOILS SUPPORTING ALL FOOTING MUST BE
 INSPECTED AND APPROVED BY A REGISETERD SOILS ENGINEER
 BEFORE COMMENCING WORK. APPROVED IN WRITING MUST
 INDICATE THE SOIL IS ADEQUATE TO SAFETLY SUSTAIN
 SPECIFIED SOIL BEARING PRESSURE. 2010 FBC-B 1803.2
 INVESTIGATIONS REQUIRED.
  
 8) SHEET A1.1 SHOWS A DROPPED CEILING OVER EXPOSITION
 KITCHEN AND PICK UP AREA, PLEASE PROVIDE DETAILS OF HOW
 THIS SYSTEM WILL BE ATTACHED TO THE FRAMING SYSTEM
 ABOVE THE GIRDERS APPEAR TO BE SPACED 10'-0"
 APART.107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 9) SHEET A1.1 CEILING PLAN THERE IS A SYMBOL T THAT
 APPEARS NUMEROUS TIMES ON THE PLANS, THIS SYMBOL IS NOT
 FOUND IN THE CEILING PLAN LEGEND. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 10) SHEET A1.0 THE MAIN FLOOR PLAN DOES NOT PROVIDE ANY
 INTERIOR ELEVATIONS FOR THE PICK UP AREA SHOWING
 COMPLIANCE WITH 2010 FL ACCESS. CODE 904.4.
  
 11) THE PLANS WILL ALSO NEED TO SHOW COMPLIANCE WITH
 THESE ACCESSIBLE ELEMENTS: 902.1 GENERAL. DINING
 SURFACES AND WORK SURFACES SHALL COMPLY WITH 902.2 AND
 902.3.
 EXCEPTION: DINING SURFACES AND WORK SURFACES FOR
 CHILDREN?S USE SHALL BE PERMITTED TO COMPLY WITH 902.4.
 ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ABA SCOPING
 PROVISIONS, EMPLOYEE WORK STATIONS.
  
 11A) 2010 FL ACC CODE 902.2 CLEAR FLOOR OR GROUND
 SPACE. A CLEAR FLOOR SPACE COMPLYING WITH 305
 POSITIONED FOR A FORWARD APPROACH SHALL BE PROVIDED.
 KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE
 PROVIDED.
  
 11B) 2010 FL ACC CODE 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES AND WORK SURFACES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 12) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-04-02 Cont ID  
Sent By rlecky Date 2015-04-02 Time 12:20 Rev Time 0.00
Received By rlecky Date 2015-04-02 Time 11:35 Sent To  
Notes
2015-04-02 12:23:07NOTE PLACED ON PLANS INDICATING THAT THE ELECTRIC
 EQUIPMENT, GRILLS, OVENS, ETC. MUST BE LISTED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY. NEC 90.7

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-01-27 Cont ID  
Sent By rlecky Date 2015-01-27 Time 12:53 Rev Time 0.00
Received By rlecky Date 2015-01-22 Time 12:20 Sent To  
Notes
2015-01-27 12:53:4414120130
 1901 S DIXIE HWY
 INTERIOR IMPROVEMENT
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENT.
  
 VERIFY THIS BUILDING WILL HAVE ONLY ONE POINT OF
 ELECTRICAL SERVICE. INDICATE
 THE INTENDED USE FOR THE ELECTRICAL PANELS SHOW ON THE
 WEST EXTERIOR ELEVATION OF SHEET A3. NEC 230.2
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR ALARM
 SYSTEMS, SECURITY, SITE LIGHTING AND DATA SYSTEMS.
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-05-20 Cont ID  
Sent By wjolin Date 2015-05-20 Time 15:44 Rev Time 0.00
Received By wjolin Date 2015-05-20 Time 14:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2015-04-16 Cont ID  
Sent By wjolin Date 2015-04-16 Time 16:52 Rev Time 0.00
Received By wjolin Date 2015-04-16 Time 15:35 Sent To  
Notes
2015-04-16 16:52:401901 SOUTH DIXIE HIGHWAY
 PERMIT #14120130
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SOLID FUEL COOKING OPERATIONS NEED TO CONFORM TO ALL
 THE REQUIREMENTS OF NFPA 96 (HOODS, EXHAUST, AIR
 MOVEMENT, FIRE PROTECTION, CLEANING/MAINTENANCE, FUEL
 STORAGE, EMBER/ASH MANAGEMENT, ETC.). THE PLANS AND
 EQUIPMENT ARE SEVERLY LACKING INFORMATION TO SHOW
 COMPLIANCE WITH ALL THE DETAILED REQUIREMENTS OF NFPA
 96.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. PER FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE
 PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2014-12-23 Cont ID  
Sent By wjolin Date 2014-12-23 Time 14:29 Rev Time 0.00
Received By wjolin Date 2014-12-23 Time 11:23 Sent To  
Notes
2014-12-23 11:49:221901 SOUTH DIXIE HIGHWAY
 CHANGE OF OCCUPANCY FROM MERCANTILE TO ASSEMBLY
 PERMIT #14120130
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: PROVIDE DRAWING NOTE INDICATING, "FIRE
 PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY."
  
 GENERAL: PER SECTION 10.12.1.2 (NFPA 1), PROVIDE
 BUILDING ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL
 BE ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES
 IN HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 CIVIL SITE: NO PARKING SIGNS WILL BE NEEDED ON KANUGA
 DRIVE TO PROVIDE FIRE DEPARTMENT ACCESS TO PROPOSED
 FIRE DEPARTMENT CONNECTION, BACKFLOW PREVENTER AND
 EXISTING FIRE HYDRANT. BACKFLOW PREVENTER WILL NEED TO
 BE PROTECTED FROM VEHICULAR TRAFFIC.
  
 SHEET LS: SECONDARY EXIT (KANUGA DRIVE) DOOR SWINGS
 INTO THE PUBLIC RIGHT OF WAY.
  
 SHEET A1.0: MAIN ENTRY DOOR EQUIPPED WITH THUMB TURN
 LOCK. FOR ASSEMBLY AND EDUCATIONAL OCCUPANCIES WITH AN
 OCCUPANT LOAD OF 100 OR MORE PERSONS (50 PERSONS PER
 THE FLORIDA BUILDING CODE), PANIC HARDWARE SHALL BE
 PROVIDED ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER
 LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC HARDWARE. AS A SUBSTITUTE FOR
 PANIC HARDWARE, THE MAIN ENTRANCE IS PERMITTED TO HAVE
 AN INTERIOR KEYED DOOR LOCK (AND NO LATCH) WITH A
 READILY VISIBLE SIGN STATING THIS DOOR TO REMAIN
 UNLOCKED WHEN THE BUILDING IS OCCUPIED. SIGN LETTERS
 SHALL BE AT LEAST 1 INCH IN HEIGHT. KEYED LOCK TO BE
 EQUIPPED WITH AN ?OPEN/LOCKED? INDICATOR WINDOW (SUCH
 AS ADAMS RITE 4089 OR SIMILAR). A THUMB TURN STYLE LOCK
 IS NOT PERMITTED TO BE SUBSTITUTED FOR A KEYED LOCK.
  
 SHEET A1.2: AREA AT BOTTOM OF STAIR INDICATED AS
 RECEIVING AREA. WHAT SAFE GUARDS WILL BE IN PLACE TO
 ENSURE THE EXIT STAIR (SINGLE MEANS OF EGRESS) IS NEVER
 BLOCKED OR OBSTRUCTED?
  
 SHEET A2.0: THE CEILING AND STRUCTURE HEIGHTS CANNOT BE
 DETERMINED FOR THE UPPER LEVEL. HEAD CLEARANCES OF
 7'-6" SHALL BE PROVIDED AND INDICATED ON THE PLANS.
  
 SHEET A2.0: PROVIDE A STORAGE LAYOUT. IN GENERAL,
 INDICATE THE COMMODITIES TO BE STORED, THE QUANTITY TO
 BE STORED, AND THE HEIGHT OF STORAGE, ETC.
  
 SHEET P2.1: EQUIPMENT SCHEDULE INDICATES A CHARCOAL
 GRILL (ITEM #74). SOLID FUEL AND FIRE PROTECTION
 INFORMATION AND DETAILS NEEDED FOR APPROVAL.
  
 FIRE PROTECTION: FOR ISSUANCE OF A GENERAL BUILDING
 PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA BUILDING
 CODE REQUIRES SEALED FIRE PROTECTION CONSTRUCTION
 DOCUMENTS FOR THE DESIGN OR ALTERATION OF 50 OR MORE
 AUTOMATIC FIRE SPRINKLERS. PER FLORIDA ADMINISTRATIVE
 CODE SECTION 61G15-32.004, FIRE PROTECTION ENGINEERING
 DOCUMENTS SHALL INCLUDE THE POINT OF SERVICE FOR THE
 WATER SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS
 APPLICABLE TO THE PROJECT, CLASSIFICATION OF HAZARD
 OCCUPANCY FOR EACH ROOM OR AREA, SUPPRESSION SYSTEM
 TYPE, DESIGN DENSITIES, WATER SUPPLY DATA (FIRE PUMP
 DATA, HYDRANT FLOW TEST DATA) AND ANY PERFORMANCE BASED
 INFORMATION SUCH AS PRE-ENGINEERED SYSTEMS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2015-06-28 Cont ID  
Sent By tklarge Date 2015-06-28 Time 09:12 Rev Time 0.00
Received By tklarge Date 2015-06-28 Time 09:00 Sent To  
Notes
2015-06-28 09:15:18THE GAS IS NOT APPROVED UNDER THIS PERMIT. A SEPARATE
 GAS PERMIT APPLICATION ALONG WITH SIGNED AND SEALED
 DRAWINGS AND COMBUSTION AIR CALCULATIONS SHALL BE
 SUBMITTED FOR REVIEW AND APPROVAL.
 T.LARGE

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2015-06-10 Cont ID  
Sent By tklarge Date 2015-06-10 Time 09:41 Rev Time 0.00
Received By tklarge Date 2015-06-10 Time 09:41 Sent To  
Notes
2015-06-10 09:24:051) SHT. P1.2 - PLEASE EXPLAIN HOW YOU ARRIVED AT THE
 CUBIC FOOTAGE OF 94,880 FOR THE RESTAURANT. IT IS
 UNCLEAR TO ME HOW YOU ARRIVED AT YOUR COMBUSTION AIR
 CALCULATIONS. IN ACCORDANCE WITH THE STANDARD METHOD IN
 THE 2010 FGC SEC.304.5.1, 50 CU. FT. OF COMBUSTION AIR
 IS REQUIRED FOR EACH 1,000 BTU OF THE APPLIANCE RATING.
 TAKING THE TOTAL BTU LOAD THAT I HAVE CALCULATED AS THE
 BASIS FOR THE REQUIRED COMBUSTION AIR (1,559,000
 DIVIDED BY 1000 = (1,559 ) X (50 CU. FT. ) = 77,950 CU.
 FT. OF COMBUSTION AIR REQUIRED. THE CUBIC FOOTAGE OF
 THE RESTAURANT ON P1.2 IS SHOWN AS 94,880 AND ALSO AS
 81,900 BEING DIVIDED BY 50 CU.FT.AND ARRIVING AT AN
 ALLOWABLE BTU LOAD OF 1,897,000 BTU'S. PLEASE ENLIGHTEN
 ME AS I HAVE ABSOLUTELY NO IDEA AS TO HOW THESE REULTS
 WERE ATTAINED FOR THE REQUIREMENTS FOR THE COMBUSTION
 AIR. THERE IS NO REVISED DRAWING P1.2 THAT WAS
 SUBMITTED AS STATED IN YOUR RESPONSE OF 4/20/15. THERE
 IS VERSION 2 WHICH IS WHAT MY REVIEW COMMENTS ARE BASED
 UPON. CLARIFY.
 2) THE BTU LOAD OF THE APPLIANCES LISTED ON SHT. P1.2
 AND SHT. P0.3 DO NOT CORRELATE NOR DO THE TOTAL BTU'S.I
 HAVE ADDED THE BTU'S ON SHT. P1.2 AND IT TOTALS
 1,559,000, NOT 1,649,000 AS SHOWN. CLARIFY.
 3) SHT. P0.3 SHOWS THE BTU LOAD FOR RANGE #2 AS 70,000
 AND SHT. P1.2 HAS THE BTU LOAD AS 140,000. CLARIFY.
 4) SHT. P0.3 - TOTAL GAS CONSUMPTION TABLE SHOWS ONE
 (1) RANGE #1 LISTED AND SHT. P1.2 SHOWS TWO (2) RANGE
 #1 UNITS LISTED FOR A TOTAL OF 490,000 BTU'S. CLARIFY.
 5) SHT. P0.3 - RANGE #3 IS SHOWN ON THE GAS RISER AND
 ON THE GAS CONSUMPTION LIST BUT NOT ON SHT.P1.2.
 CLARIFY.
  
 NOTE: A COMPREHENSIVE GAS REVIEW CANNOT BE DONE UNTIL
 ALL THE CORRECT BTU LOADS AND COMBUSTION AIR
 CALCULATIONS ARE SUBMITTED.I SUGGEST CONTACTING ME TO
 SET UP A MEETING TO REVIEW AND DISCUSS THESE COMMENTS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-04-19 Cont ID  
Sent By tklarge Date 2015-04-19 Time 09:29 Rev Time 0.00
Received By tklarge Date 2015-04-19 Time 09:29 Sent To  
Notes
2015-04-23 13:37:341) SUBMIT MANUF. SPECIFICATIONS FOR ALL GAS
 APPLIANCES/EQUIPMENT.ALL EQUIPMENT SHALL BE LISTED AND
 LABELED PER THE 2010 FUEL GAS CODE SEC.301.3. THE
 NARRATIVE RESPONSE REFERS TO SHT. QF 101FOR GAS
 EQUIPMENT AND SPECIFICATIONS. THERE IS NO SHT. QF 101.
 CLARIFY.
 2) SUBMIT VENTING DETAILS FOR THE TANKLESS WATER
 HEATERS. THE TANKLESS WATER HEATERS ARE DIRECT VENT
 APPLIANCES AND THE VENTING IS USUALLY SHOWN IN THE
 MANUFACTURER'S INSTALLATION MANUAL. SUBMIT THE VENT
 DETAILS FROM THE MANUFACTURER.THE NARRATIVE RESPONSE
 STATES TO SEE SHT.P0.2 FOR WATER HEATER VENT
 DETAIL.THERE IS NO VENT DETAIL ON P0.2, JUST A CLOUDED
 EMPTY BOX. WPB AMEND. TO 2010 FBC SEC. 107.3.5.1.5.
 3) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE VENTLESS
 GAS REGULATORS. THE NARRATIVE RESPONSE REFERS TO SHT.
 P1.1B & ATTACHED CUT SHEET.THERE IS NO ADDITIONAL
 INFORMATION ON SHT.P1.1B & NO ATTACHED CUT SHEET.
 CLARIFY.
 4) THE BTU LOAD OF THE APPLIANCES LISTED ON SHT. P1.2
 AND SHT.P0.3 DO NOT CORRELATE. I HAVE ADDED THE BTU
 LOAD A FEW TIMES ON SHT. P1.2 AND THE TOTAL BTU LOAD I
 CALCULATED IS 1,559,000. CLARIFY.
 5) SHT. P1.2 - PLEASE EXPLAIN HOW YOU ARRIVED AT THE
 CUBIC FOOTAGE OF 94,880 FOR THE RESTAURANT. IT IS
 UNCLEAR TO ME HOW YOU ARRIVED AT YOUR COMBUSTION AIR
 CALCULATIONS. IN ACCORDANCE WITH THE STANDARD METHOD IN
 THE 2010 FGC SEC.304.5.1, 50 CU. FT. OF COMBUSTION AIR
 IS REQUIRED FOR EACH 1,000 BTU OF THE APPLIANCE RATING.
 TAKING THE TOTAL BTU LOAD FROM COMMENT #4, 1,559,000
 DIVIDED BY 1000 = (1,559 ) X (50 CU. FT. ) = 77,950 CU.
 FT. OF COMBUSTION AIR REQUIRED. THE CUBIC FOOTAGE OF
 THE RESTAURANT ON P1.2 IS SHOWN AS 94,880 AND ALSO AS
 81,900 BEING DIVIDED BY 50 CU.FT. I DO NOT KNOW HOW YOU
 ARRIVED AT YOUR BTU PARAMETERS FOR THE COMBUSTION AIR.
 CLARIFY.
 6) THE VENTING OF THE TANKLES WATER HEATRS SHALL COMPLY
 WITH THE APPROPRIATE TABLE FROM FGC SEC.504 AND TABLE
 504.2 FOR THE APPLICABLE TYPE OF VENT MATERIAL BEING
 USED OR SUBMIT THE MANUFACTURER'S INSTALLATION DETAILS
 FOR THE VENTING OF MULTIPLE UNITS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-04-14 Cont ID  
Sent By fmittner Date 2015-04-14 Time 14:49 Rev Time 0.00
Received By fmittner Date 2015-04-14 Time 14:49 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-03-02 Cont ID  
Sent By fmittner Date 2014-12-30 Time 15:51 Rev Time 0.00
Received By fmittner Date 2014-12-30 Time 15:51 Sent To  
Notes
2015-03-02 15:20:50APPROVED BY HPB WITH CLEAR GLAZING.
2014-12-30 15:53:31NOT CLEAR IF ORIGINAL WINDOW OPENINGS ARE BEING
 MODIFIED. FRAME COLOR, GLAZING COLOR? ADDITIONAL
 INFORMATION IS NEEDED INCLUDING RESOLUTION OF
 APPLICATION THAT HAS BEEN SUBMITTED FOR HEARIGN BY THE
 HISTORIC PRESERVATION BOARD ON 1/27. QUESTIONS CONTACT
 FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION PLANNER
 AT (561) 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-06-26 Cont ID  
Sent By jwitmer Date 2015-06-24 Time 09:40 Rev Time 0.00
Received By lmarchan Date 2015-05-12 Time 13:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-27 Cont ID  
Sent By hmoser Date 2015-04-27 Time 14:44 Rev Time 0.00
Received By hmoser Date 2015-03-24 Time 16:23 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-01-27 Cont ID  
Sent By cpuell Date 2015-01-27 Time 13:00 Rev Time 0.00
Received By cpuell Date 2014-12-05 Time 14:51 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2015-03-16 Cont ID  
Sent By jwitmer Date 2015-03-16 Time 16:32 Rev Time 0.00
Received By jwitmer Date 2015-03-16 Time 16:29 Sent To  
Notes
2015-03-16 16:31:58P. B. C. IMPACT FEE ASSESSMENT:
 MU-2015-5863
 RECEIPT: 2015-0317-97
 $178.08

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-12-19 Cont ID  
Sent By jwitmer Date 2014-12-19 Time 16:56 Rev Time 0.00
Received By jwitmer Date 2014-12-19 Time 16:56 Sent To  
Notes
2014-12-19 16:56:05BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2015-06-23 Cont ID  
Sent By rcaranci Date 2015-06-23 Time 16:23 Rev Time 0.00
Received By rcaranci Date 2015-06-23 Time 16:23 Sent To Z
Notes
2015-06-23 16:24:39WITH PROVISOS:
  
 A SEPARATE LANDSCAPE PERMIT SHALL BE SUBMITTED WITH
 COST ESTIMATE THAT ADDRESSES ALL THE FOLLOWING ITEMS:
  
 1. PARKING SPACE IS NOT FUNCTIONAL WEST OF PROPOSED
 DUMPSTER, CONVERT TO LANDSCAPE AREA, COMPLETE CLUSIA
 HEDGE.
  
 2. WHEEL STOPS MUST BE PROVIDED TO PROTECT LANDSCAPE
 AREAS PER CODE.
  
 3. REMOVE INVASIVE EXOTIC SCHEFFLERA TREE AND REPLACE
 WITH SHADE OR FLOWERING TREE.
  
 4. ADJUST SITE PLAN TO MATCH CHANGES

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-06-15 Cont ID  
Sent By hmoser Date 2015-06-15 Time 15:38 Rev Time 0.00
Received By hmoser Date 2015-06-15 Time 11:02 Sent To  
Notes
2015-06-15 15:38:04PASS PROVISO
 1) KITCHEN HOODS ARE NOT PART OF THIS REVIEW.
 HOODS REQUIRE SEPARATE APPLICATION, PLANS AND PERMIT
 2) PROVIDE A DETAIL FROM THE ENGINEER ON CURB TO ROOF
 AND RTU TO CURB TIE DOWN, SHOW TYPE AND SIZE OF
 ANCHOR USED. PER SECTION 301.12 WIND RESISTANCE
 2010 FBC (M)
 3) CALL IN INSPECTION BEFOR RTU IS INSTALLED SO
 INSPECTOR CAN SEE SECURE STRAP AND TEX SCREWS.
 4) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-04-27 Cont ID  
Sent By hmoser Date 2015-04-27 Time 13:51 Rev Time 0.00
Received By hmoser Date 2015-04-27 Time 13:21 Sent To  
Notes
2015-04-27 14:43:19PLAN DENIED
 1) PROVIDE ENERGY CALCULATION WITH THE PLAN
 PER SECTION 503.2.1CALCULATION OF HEATING AND COOLING
 2010 FLORIDA ENERGY CODE 2010
 2) REFER TO SECTION 304.1 GENERAL PROVIDE
 INSTALLATION INSTRUCTION FOR TUSCANY
 WOOD FUELED BBQ
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-01-05 Cont ID  
Sent By hmoser Date 2015-01-05 Time 12:19 Rev Time 0.00
Received By hmoser Date 2015-01-05 Time 12:15 Sent To  
Notes
2015-01-05 12:19:49PASS PROVISO
 1) REFER TO SECTION 304.11 GUARDS 2010 FBC (M)
 2) REFER TO SECTION 503.2.5.4 SHUTOFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODS
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-06-10 Cont ID  
Sent By tklarge Date 2015-06-10 Time 09:41 Rev Time 0.00
Received By tklarge Date 2015-06-10 Time 09:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-04-19 Cont ID  
Sent By tklarge Date 2015-04-19 Time 09:29 Rev Time 0.00
Received By tklarge Date 2015-04-19 Time 06:06 Sent To  
Notes
2015-04-19 09:22:201) SUBMIT MANUF. SPECIFICATIONS FOR ALL GAS
 APPLIANCES/EQUIPMENT.ALL EQUIPMENT SHALL BE LISTED AND
 LABELED PER THE 2010 FUEL GAS CODE SEC.301.3. THE
 NARRATIVE RESPONSE REFERS TO SHT. QF 101FOR GAS
 EQUIPMENT AND SPECIFICATIONS. THERE IS NO SHT. QF 101.
 CLARIFY.
 2) SUBMIT VENTING DETAILS FOR THE TANKLESS WATER
 HEATERS. THE TANKLESS WATER HEATERS ARE DIRECT VENT
 APPLIANCES AND THE VENTING IS USUALLY SHOWN IN THE
 MANUFACTURER'S INSTALLATION MANUAL. SUBMIT THE VENT
 DETAILS FROM THE MANUFACTURER.THE NARRATIVE RESPONSE
 STATES TO SEE SHT.P0.2 FOR WATER HEATER VENT
 DETAIL.THERE IS NO VENT DETAIL ON P0.2, JUST A CLOUDED
 EMPTY BOX. WPB AMEND. TO 2010 FBC SEC. 107.3.5.1.5.
 3) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE VENTLESS
 GAS REGULATORS. THE NARRATIVE RESPONSE REFERS TO SHT.
 P1.1B & ATTACHED CUT SHEET.THERE IS NO ADDITIONAL
 INFORMATION ON SHT.P1.1B & NO ATTACHED CUT SHEET.
 CLARIFY.
 4) THE BTU LOAD OF THE APPLIANCES LISTED ON SHT. P1.2
 AND SHT.P0.3 DO NOT CORRELATE. I HAVE ADDED THE BTU
 LOAD A FEW TIMES ON SHT. P1.2 AND THE TOTAL BTU LOAD I
 CALCULATED IS 1,559,000. CLARIFY.
 5) SHT. P1.2 - PLEASE EXPLAIN HOW YOU ARRIVED AT THE
 CUBIC FOOTAGE OF 94,880 FOR THE RESTAURANT. IT IS
 UNCLEAR TO ME HOW YOU ARRIVED AT YOUR COMBUSTION AIR
 CALCULATIONS. IN ACCORDANCE WITH THE STANDARD METHOD IN
 THE 2010 FGC SEC.304.5.1, 50 CU. FT. OF COMBUSTION AIR
 IS REQUIRED FOR EACH 1,000 BTU OF THE APPLIANCE RATING.
 TAKING THE TOTAL BTU LOAD FROM COMMENT #4, 1,559,000
 DIVIDED BY 1000 = (1,559 ) X (50 CU. FT. ) = 77,950 CU.
 FT. OF COMBUSTION AIR REQUIRED. THE CUBIC FOOTAGE OF
 THE RESTAURANT ON P1.2 IS SHOWN AS 94,880 AND ALSO AS
 81,900 BEING DIVIDED BY 50 CU.FT. I DO NOT KNOW HOW YOU
 ARRIVED AT YOUR BTU PARAMETERS FOR THE COMBUSTION AIR.
 CLARIFY.
 6) THE VENTING OF THE TANKLES WATER HEATRS SHALL COMPLY
 WITH THE APPROPRIATE TABLE FROM FGC SEC.504 AND TABLE
 504.2 FOR THE APPLICABLE TYPE OF VENT MATERIAL BEING
 USED OR SUBMIT THE MANUFACTURER'S INSTALLATION DETAILS
 FOR THE VENTING OF MULTIPLE UNITS.
 7) SHT. P0.2 - THE SANITARY RISER AS DRAWN DOES NOT
 COMPLY WITH 2010 FPC SEC. 909 FOR A WET VENT SYSTEM.THE
 WATER CLOSETS SHALL BE INDIVIDUALLY VENTED OR THE
 SYSTEM SHALL BE DESIGNED AS A CIRCUIT VENT IN
 COMPLIANCE WITH FPC SEC.911.
 8) THE MOP SINK IS SHOWN WITH A VENT ON THE PLAN VIEW
 DRAWING ( P1.1A ) BUT NOT ON THE RISER. CLARIFY.
 9) THE STAFF RESTROOM CLEARLY OPENS INTO THE FOOD PREP
 AREA. THERE IS A DOUGH PREP AREA ALMOST DIRECTLY IN
 FRONT OF IT.TOILET ROOMS SHALL NOT OPEN DIRECTLY INTO A
 ROOM USED FOR THE PREPARATION OF FOOD FOR SERVICE TO
 THE PUBLIC PER THE 2010 FBC SEC.1210.5.
 10) SUBMIT A COMPLETE FOOD SERVICE EQUIPMENT PLAN.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2014-12-22 Cont ID  
Sent By tklarge Date 2014-12-22 Time 06:06 Rev Time 0.00
Received By tklarge Date 2014-12-21 Time 09:09 Sent To  
Notes
2014-12-22 05:18:261) SHT.A4.0 - DETAIL #1 - STAFF R.R.- THE HEIGHT OF THE
 GRAB BAR ABOVE THE FINISH FLOOR SHALL BE MEASURED TO
 THE TOP OF THE GRIPPING SURFACE, NOT TO THE CENTERLINE
 OF THE BAR AS SHOWN.2010 FL. ACCESS. CODE SEC.609.4.
 2) LIFE SAFETY PLAN - INDICATE THE PREVIOUS OCCUPANCY
 ON THE PLAN. WPB AMEND. TO 2010 FBC SEC.107.2.1.. SEE
 THE BUILDING PLAN REVIEW COMMENT.
 3) A SERVICE SINK IS REQUIRED PER TABLE 403.1.
 4) SUBMIT MANUFACTURER SPECIFICATION SHEETS AND
 INSTALLATION MANUAL FOR THE TANKLESS WATER HEATERS. THE
 TANKLESS WATER HEATERS SHALL BE LISTED AND LABELED PER
 THE 2010 FL. GAS CODE SEC. 301.3.
 5) SUBMIT MANUFACTURER'S SPECIFICATION SHEETS FOR ALL
 THE GAS APPLIANCES/EQUIPMENT. ALL EQUIPMENT SHALL BE
 LISTED AND LABELED PER SEC. 301.3 OF THE 2010 FGC.
 6) SHT. P0.2 - THE SANITARY RISER DOES NOT COMPLY WITH
 SEC.909 OF THE FL. PLUMBING CODE FOR THE NUMBER AND
 TYPE OF FIXTURES PERMITTED ON A WET VENT.
 7) SHT.P1.1A - A FLOOR DRAIN IS SHOWN IN THE WARE
 WASHING AREA (#113) BUT IS NOT SHOWN ON THE GREASY
 WASTE RISER ON P0.2.CLARIFY.
 8) SHT.P1.1A - SHOW THE INDIRECT WASTE FROM FIXTURE #7
 TO THE FLOOR DRAIN ON RISER P0.2.
 9) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE
 TANKLESS WATER HEATERS & ALL THE GAS APPLIANCES ON THE
 FIRST FLOOR. 201 FL. GAS CODE SEC.304.
 10) SUBMIT VENTING DETAILS FOR THE TANKLESS WATER
 HEATERS. 201 FGC SEC.503.THE PLUMBING PLANS REFER TO
 THE MECHANICAL SHEETS FOR DETAILS BUT THERE IS JUST A
 PLAN VIEW WITH NO DETAILS.
 11) SUBMIT MANUF. SPECS FOR THE VENTLESS GAS
 REGULATORS. WPB AMEND. TO 2010 FBC SEC.107.2.1, FGC
 SEC.410.0.
 12) SHOW THE INCREMENTAL BTU/CFH LOAD ON THE GAS PIPING
 SYSTEMFROM THE ENTRANCE METER TO THE FURTHEST OUTLET.
 13) WHERE IS PAGE 2 OF 2 FOR THE GREASE INTERCEPTOR
 DETAILS.?
 14) THE GREASE TRAPS APPEAR TO BE LOCATED ON LOT 6. IS
 THIS PROPERTY OWNED BY THE RESTAURANT?
 15) PROVIDE A LEGEND FOR THE HOT, COLD, HOT WATER
 RETURN AND THE TEMPERED WATER. THE RISER SHOWS THE
 INDIVIDUAL WATER IDENTIFIED WITH DOTS AND DASHES.WPB
 AMEND. TO 2010 FBC SEC.107.2.1
 16) PROVIDE INFORMATION/DETAILS FOR THE REGULATOR VENT
 FOR THE TANKLESS WATER HEATERS. WPB AMEND. TO 2010 FBC
 SEC.107.2.1.COMPLY W/ 2010 FGC SEC.410.3.1.
 17) TOILET ROOMS SHALL NOT OPEN DIRECTLY INTO A ROOM
 USED FOR THE PREPARATION OF FOOD FOR SERVICE TO THE
 PUBLIC. 2010 FL. BLDG. CODE. SEC.1210.5.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2015-07-01 Cont ID  
Sent By skennedy Date 2015-07-01 Time 12:08 Rev Time 0.00
Received By skennedy Date 2015-07-01 Time 10:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2015-06-29 Cont ID  
Sent By skennedy Date 2015-06-29 Time 15:23 Rev Time 0.00
Received By skennedy Date 2015-06-29 Time 12:05 Sent To  
Notes
2015-06-29 15:26:261ST REVIEW: FBC 2010
  
 THERE ARE 48 FILES BUT YOU HAVE SUBMITTEED SIGNATURE
 DOCUMENTS AND REPORTS FOR ONLY 10 FILES.
  
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  
2015-06-16 15:18:52PEDDS SUBMITTED 6/16/15 WAITING ON PASSED PLAN REVIEW.
 CP

Review Stop Z ZONING
Rev No 3 Status P Date 2015-06-24 Cont ID  
Sent By rbrown Date 2015-06-24 Time 14:23 Rev Time 0.00
Received By rbrown Date 2015-06-24 Time 14:23 Sent To  
Notes
2015-06-24 14:24:45PER FRIEDERIKE MITTNER: OK TO PASS ZONING REVIEW
 BECAUSE IT WAS PENDING SUBMITTAL OF A LANDSCAPE PLAN
 WHICH HAS NOW BEEN SUBMITTED AND REVIEWED.

Review Stop Z ZONING
Rev No 2 Status F Date 2015-04-29 Cont ID  
Sent By fmittner Date 2015-04-29 Time 09:37 Rev Time 0.00
Received By fmittner Date 2015-04-14 Time 16:05 Sent To  
Notes
2015-04-14 16:05:44STILL MISSING LANDSCAPE PLAN.

Review Stop Z ZONING
Rev No 1 Status F Date 2014-12-30 Cont ID  
Sent By fmittner Date 2014-12-30 Time 15:53 Rev Time 0.00
Received By fmittner Date 2014-12-30 Time 15:53 Sent To  
Notes
2014-12-30 16:04:39VALUE OF PERMIT $336,000 EXCEEDS 50% OF $268,897 VALUE
 OF IMPROVEMENT. REQUIRES A LANDSCAPE PLAN.
2014-12-16 18:10:0612/16/14


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved